Section 2 – Operation

QUIETPACT™ 65D Recreational Vehicle Generator

2.6.2 DO NOT OVERLOAD THE GENERATOR

If the engine does not start after it has been cranking for 15 seconds, release the Start/Stop switch, wait 15 seconds, and try again. Holding the switch for longer than 15 seconds can damage the starter motor.

4.Let the engine run at no-load for a few minutes to stabilize and warm up.

5.Turn ON electrical loads, using the means provided in your vehicle (such as, a main-line cir- cuit breaker or transfer switch).

2.5STOPPING THE GENERATOR

1.Turn OFF all electrical loads, using the means provided in your vehicle (such as, a main-line cir- cuit breaker or transfer switch).

2.Let the generator run at no-load for a few minutes, to stabilize internal engine generator temperatures.

Do not stop the engine/generator immediately after running under load. This can overheat and damage the engine and/or generator.

3.Press and hold the Start/Stop switch in the STOP position, until the engine shuts off.

2.6APPLYING LOADS TO GENERATOR

When applying electrical loads to the generator, observe these guidelines:

Before applying electrical loads, let the generator stabilize and warm up for a minute or two.

DO NOT overload the generator.

2.6.1 LETTING THE ENGINE STABILIZE

The generator supplies correctly rated voltage only at the proper governed speed. Some electrical appli- ances may be extremely sensitive to voltage. Incorrect voltages can damage such appliances.

Electrical loads applied on the engine at reduced operating speeds, such loads imposed on the engine, when sufficient power is not available, may shorten engine life. Never turn ON electrical loads until after the generator engine has started and stabilized at no- load.

You can read the rated wattage/amperage capacity of your generator on the generator data decal located below the user control panel.

Applying electrical loads in excess of the unit’s rated capacity may trip the line breaker or cause the engine/generator to shut down.

To avoid overloading, add up the wattage of all con- nected electrical lighting, appliance, tool, and motor loads. This total should not be greater than the gen- erator’s rated wattage capacity.

Most lighting, appliance, tool, and motor loads indicate their required watts on their nameplate or data plate. For light bulbs, simply note the wattage rating of the bulb.

If a load does not show its rated wattage, multiply that load’s rated VOLTS times AMPS to obtain

WATTS.

Induction-type motors (such as, those that run the vehicle’s furnace fan, refrigerator, air conditioner, etc.) need about 2-1/2 time more watts of power for starting than for running (for a few seconds during motor starting). Be sure to allow for this when con- necting electrical loads to the generator. First, cal- culate the watts needed to start electric motors in the system. To that figure, add the running wattages of other items that will be operated by the generator.

For the first two or three hours of operation, do not apply electrical loads over 75 percent of the unit’s rating.

2.7PROTECTION SYSTEMS

The engine has several safety switches that cause it to automatically shut down, under the following conditions: low oil pressure, high coolant tempera- ture, and engine overspeed. See Figure 2.2 (Page 10) for the location of these devices. If automatic shut- down does occur, refer to “Troubleshooting Guide”, on page 37.

2.7.1 LOW OIL PRESSURE SWITCH

This switch is normally closed (N.C.) but is held open by engine oil pressure during engine running. Should operating oil pressure drop below approximately 10 psi, the switch contacts close, and the engine shuts down automatically.

2.7.2 HIGH COOLANT TEMPERATURE SWITCH

This normally-open (N.O.) thermostatic switch has a sensing tip that is immersed in captive coolant. Should the coolant temperature exceed approximate- ly 115° C (240° F), the switch contacts close, and the engine shuts down automatically.

Generac® Power Systems, Inc. 9

Image 11
Contents Power SYSTEMS, INC Introduction Authorized Service Dealer LocationPart II Installation Instructions General Hazards Electrical Hazards Quietpact 65D Generator IdentificationGenerator AC Connection System SafetySpecifications Generator ApplicabilityGenerator Fuel Consumption GAL/HREngine OIL Requirements Before Starting the Engine Generator Control PanelOptional Remote START/STOP Starting the Generator Protection Systems Stopping the Generator1 25-HOUR BREAK-IN Period Additional InformationOverspeed Shutdown Overvoltage ProtectionEffects of Moisture and Dirt Checking the Engine OIL LevelChanging the Engine OIL AND/OR OIL Filter Operation in High Grass or BrushSpark Arrestor Muffler Servicing the Engine AIR FilterBattery Maintenance Cleaning the GeneratorDrive Belt OUT-OF-SERVICE ProcedureCooling System Engine CoolantReturn to Service SYSTEM/COMPONENT Procedure Frequency Service SchedulePart General Hazards Electrical Hazards Generator Engine Operating Speed Purpose and Scope ManualStandards Booklets Equipment DescriptionMajor Features and Dimensions Suspended Mounting Location and SupportGenerator Location Generator SupportCompartment Construction Generator CompartmentsGenerator Restraint Acoustics Sound Insulating MaterialsTypical Noise Abatement Compartment Floor CutoutsGenerator Airflow Cooling and Ventilating AIRCooling AIR Inlet Openings Compensating for Restrictions Testing the InstallationDiesel Fuel System Generator Fuel Return Lines Generator Fuel Supply LinesMuffler and Spark Arrestor Exhaust System SafetyExhaust System Generator AC Connections Electrical ConnectionsElectrical Junction BOX Isolating Different Power Sources Power Supply CordGround Fault Circuit Interrupters Battery Cable Connections Battery InstallationBattery Cables Recommended BatteryBattery Compartment Optional AccessoriesInitial Start Post Installation TestsTesting Under Load Before Initial StartupInstallation Checklist Problem Cause Correction Troubleshooting GuideAppendix 2 Electrical Data Appendix 2 Electrical Data Appendix 2 Electrical Data Appendix 3 Exploded Views and Parts Lists QTY Description Base Frame Weldment 174 Appendix 3 Exploded Views and Parts Lists Cooling System Drawing No. D2360 1926 Exhaust Gasket Description QTY Start / Stop Switch Camshaft Assembly Complete Cylinder Block Cylinder Head Assembly Crankshaft Assembly Part NO. QTY Description Rocker ARM Shaft Injector Pump Assembly Fuel Filter Support Appendix 3 Exploded Views and Parts Lists HOUSING, Timing Gear 3114 Water Pump Assembly Appendix 4 Notes Appendix 4 Notes Parts Covered Federal and California Emissions Control Warranty StatementYour Warranty Rights and Obligations Manufacturers Warranty CoverageLimitations Obtaining Warranty ServiceObligations and Rights of the Manufacturer and Owner Generac Power SYSTEMS, INC