Generac 004614-1 owner manual Post Installation Tests, Testing Under Load, Before Initial Startup

Page 36

Section 3 – Post-installation Start-up Checks

QUIETPACT™ 65D Recreational Vehicle Generator

CHECKS

2.8.1 REMOTE START/STOP CONNECTIONS

The following steps are necessary to connect the remote start/stop option:

1.If the six-wire remote connector is visible below the control panel, as shown in Figure 2.20, skip to step 5. Otherwise, proceed with step 2.

2.Remove the electrical access panel located just below the knock-out labeled “REMOTE.” The remote connector will be located inside the elec- trical enclosure, along the right side.

3.Remove the “REMOTE” knock-out, taking care not to damage the wiring behind it.

4.Feed the remote connector through the hole, and fit the supplied grommet into position.

5.Wire the remote harness (Part # C6712C, sup- plied as an accessory with the generator) to the vehicle’s remote start panel. Refer to Figure 2.20 for a wiring legend.

6.Plug the remote harness into the mating remote connector on the generator.

3.1POST INSTALLATION TESTS

The generator set was factory-tested and adjusted. You should not be required to adjust the unit any fur- ther, except under special circumstances.

Do not make any unnecessary adjustments. Factory settings are correct for most applica- tions. When making adjustments, however, be careful to avoid overspeeding the engine.

2.Refer to Part I, Section 2.4, “Starting the Generator” (Page 8), for cranking and starting instructions. The engine may require more cranking for initial starting, since the fuel lines have to be primed (use of the preheat switch will operate the generator’s electrical fuel pump and shorten this time).

3.Let the engine warm up for about five minutes to allow internal temperatures to stabilize.

4.Carefully inspect the engine/generator for fuel, oil, and exhaust system leaks. Before proceeding to the next step, correct any leakage immediately.

5.When all tests and adjustments at no-load are completed, apply electrical loads and check for proper operation under load. See Section 3.4. Run the unit at least 30 minutes, with loads applied.

6.Turn off all electrical loads by setting the gen- erator’s line breakers to their “OFF” (or open) position.

7.Let the unit run at no-load for a few minutes to stabilize internal engine/generator temperatures. Then, shut down the engine.

NOTE:

The generator set was thoroughly tested and adjusted at the factory before shipping. No addi- tional adjustment should be necessary. Only trained, qualified service technicians should perform adjustments outlined in this manual.

3.4TESTING UNDER LOAD

Apply electrical loads equal to about 50 to 75 percent of the unit's rated wattage/amperage capacity.

3.2BEFORE INITIAL STARTUP

Before starting, complete the following:

1.Check the engine crankcase oil level and, if nec- essary, fill to the dipstick “FULL” mark (cross- hatched area) with the recommended oil. Do not fill above the FULL mark.

2.Check the fuel supply. Fuel lines must have been properly purged and leak-tested in accordance with applicable fuel codes. All fuel shutoff valves in the fuel supply lines must be open.

3.3INITIAL START

When you are absolutely certain that the unit has been properly installed and prepared for use, start the engine as follows:

1.Turn off all electrical loads. Do this by setting the generator’s line breakers to their “OFF” (or open) position.

Let the unit run at least 30 minutes with load applied. During this part of the test, check that the unit is not running excessively hot and that adequate cooling air- flow is available. You must not allow the unit to over- heat during prolonged operation.

NOTE:

The generator engine is equipped with a high coolant temperature switch. The switch has normal- ly open (N.O.) contacts. When the engine coolant temperature is too high, switch contacts close, and the engine shuts down automatically.

GENERAC RECOMMENDS THAT YOU TEST THE GENERATOR FOR ADEQUATE COOLING.

34 Generac® Power Systems, Inc.

Image 36
Contents Power SYSTEMS, INC Authorized Service Dealer Location IntroductionPart II Installation Instructions General Hazards Electrical Hazards Generator Identification Quietpact 65DSafety SpecificationsGenerator Applicability Generator AC Connection SystemFuel Consumption GAL/HR Engine OIL RequirementsGenerator Generator Control Panel Optional Remote START/STOPBefore Starting the Engine Starting the Generator Stopping the Generator Protection SystemsAdditional Information Overspeed ShutdownOvervoltage Protection 1 25-HOUR BREAK-IN PeriodChecking the Engine OIL Level Changing the Engine OIL AND/OR OIL FilterOperation in High Grass or Brush Effects of Moisture and DirtServicing the Engine AIR Filter Spark Arrestor MufflerCleaning the Generator Battery MaintenanceOUT-OF-SERVICE Procedure Cooling SystemEngine Coolant Drive BeltReturn to Service Service Schedule SYSTEM/COMPONENT Procedure FrequencyPart General Hazards Electrical Hazards Purpose and Scope Manual Standards BookletsEquipment Description Generator Engine Operating SpeedMajor Features and Dimensions Location and Support Generator LocationGenerator Support Suspended MountingGenerator Compartments Generator RestraintCompartment Construction Sound Insulating Materials AcousticsCompartment Floor Cutouts Typical Noise AbatementCooling and Ventilating AIR Cooling AIR Inlet OpeningsGenerator Airflow Testing the Installation Diesel Fuel SystemCompensating for Restrictions Generator Fuel Supply Lines Generator Fuel Return LinesExhaust System Safety Exhaust SystemMuffler and Spark Arrestor Electrical Connections Electrical Junction BOXGenerator AC Connections Power Supply Cord Ground Fault Circuit InterruptersIsolating Different Power Sources Battery Installation Battery CablesRecommended Battery Battery Cable ConnectionsOptional Accessories Battery CompartmentPost Installation Tests Testing Under LoadBefore Initial Startup Initial StartInstallation Checklist Troubleshooting Guide Problem Cause CorrectionAppendix 2 Electrical Data Appendix 2 Electrical Data Appendix 2 Electrical Data Appendix 3 Exploded Views and Parts Lists QTY Description Base Frame Weldment 174 Appendix 3 Exploded Views and Parts Lists Cooling System Drawing No. D2360 1926 Exhaust Gasket Description QTY Start / Stop Switch Camshaft Assembly Complete Cylinder Block Cylinder Head Assembly Crankshaft Assembly Part NO. QTY Description Rocker ARM Shaft Injector Pump Assembly Fuel Filter Support Appendix 3 Exploded Views and Parts Lists HOUSING, Timing Gear 3114 Water Pump Assembly Appendix 4 Notes Appendix 4 Notes Federal and California Emissions Control Warranty Statement Your Warranty Rights and ObligationsManufacturers Warranty Coverage Parts CoveredObtaining Warranty Service Obligations and Rights of the Manufacturer and OwnerLimitations Generac Power SYSTEMS, INC