Briggs & Stratton 12KW Low Battery Voltage, Low Oil Pressure, Engine Fail To Start, Low Frequency

Page 15

Briggs & Stratton Power Products Home Generator

Owners Manual

Low Battery Voltage

This fault is indicated by one blink.This condition occurs if the generator cannot start because the starting battery output power is below that needed to crank the engine. Causes for this problem may be a faulty battery or trickle charger circuit.

To remedy the problem, contact your local service center to check the battery trickle charge output. Remove the

15 Amp fuse and disconnect the battery from the generator. Take the battery to a local battery store for analysis.

Replace the battery after it has been fully recharged, connecting the NEGATIVE cable last. Install the 15 Amp fuse.

Low Oil Pressure

This fault is indicated by two blinks.The unit is equipped with an oil pressure switch (Figure 4) using normally closed contacts that are held open by engine oil pressure during operation. Should oil pressure drop below the 8 psi range, switch contacts close and the engine is shut down.

Engine Fail To Start

This fault is indicated by four blinks.This feature prevents the generator from damaging itself if it continually attempts to start in spite of another problem, such as no fuel supply. Each time the system is directed to start, the unit will crank for 15 seconds, pause for 15 seconds, crank for 15 seconds, pause for 15 seconds, and repeat. If the system does not begin producing electricity after approximately 90 seconds, the unit will stop cranking and the LED will blink.

The most likely cause of this problem is no fuel supply. Check the inside and outside fuel shut off valves to ensure they are fully open. Other causes could be failed spark plug(s), failed engine ignition, or the engine air filter is clogged.You may need to contact your installer for assistance if you can’t remedy these problems.

Low Frequency

This fault is indicated by 5 blinks.This feature protects devices connected to the transfer switch by shutting the generator down if the engine runs slower than the preset limit.

Figure 4 — Low Oil Pressure & High Temp. Switches

 

High

 

Temperature

Oil

Switch

Pressure

 

Switch

 

 

Oil Drain

 

Fitting

To remedy the low oil pressure condition, add the recommended oil to the FULL mark on the dipstick.

If low oil pressure condition still exists, engine will start, then shut down after about 10 seconds and diagnostic LED will flash. In this case, contact an authorized service facility.

Low Voltage (Generator)

This fault is indicated by three blinks.This condition is caused by a restriction in the fuel flow, a broken or disconnected signal lead, a failed alternator winding, the control panel circuit breaker is open, or Home Standby Generator is overloaded.

To remedy the problem, contact your local service center.

This condition is caused by a failed engine governor or by excessive loads on the generator.To remedy the problem, you may need to contact your installer or local service center for assistance.

Engine Overspeed

This fault is indicated by 6 blinks.This feature protects devices connected to the transfer switch by shutting the generator down if the engine happens to run faster than the preset limit.The overspeed fault is detected as follows:

If the generator output frequency runs at 72 Hz for five seconds, the generator will shut down.

If the generator output frequency reaches 75 Hz, the generator will shut down instantly.

This condition is caused by a failed engine governor.To remedy the problem, you should contact your installer or local service center for assistance.

Oil Temperature High

This fault is indicated by seven blinks.The contacts of the temperature switch (Figure 4) are normally open. If the engine oil temperature exceeds approximately 140°C (284°F), the fault is detected and the engine shuts down.

Common causes for this condition include running the unit with all access doors removed, obstructed air inlet or exhaust port, low oil level, or debris in the engine cylinder cooling fins.

To resolve the problem, remove any accumulated debris and obstructions and let the engine cool down. Ensure that the Oil Service door and/or the Control Panel door is installed whenever the unit is running.

15

Image 15
Contents Manual del Propietario Manuel de lUtilisateur Table of Contents Safety Rules Briggs & Stratton Power Products Home Generator Owner Orientation Approved Transfer SwitchesInstallation Assistance IntroductionGenerator Clearances Power Decrease at High Altitude or High TemperatureFuel Factors Generator LocationEssential Circuits Essential Circuit SelectionDevice Running Watts Shipment Contents UnpackingDelivery Inspection Know Your Home Standby Generator LED Know Your System Control PanelAccess Doors To Remove an Access DoorTo Install an Access Door Gaseous Fuel System Battery ConnectionBefore Initial START-UP Engine OilServicing the System Setting Exercise TimerTo perform the Set Exercise procedure Automatic OperationSpecifications Fault Detection SystemGenerator Engine Fail To Start Low Battery VoltageOil Temperature High Low Oil PressureStorage Generator MaintenanceTo Clean the Generator When Calling the FactoryProblem Cause Correction TroubleshootingManual del Propietario Tabla DE ContenidoInstrucciones DE Seguridad PeligroAdvertencia Precaución Asistencia para la instalación IntroducciónOrientación Para EL Propietario Conmutadores de Transferencia AprobadosFactores Relacionados con el Combustible Ubicación del GeneradorDistancias Desde el Generador Circuitos Fundamentales Selección de los Circuitos FundamentalesDispositivo Vatiaje de El Generador Doméstico incluye lo siguiente DesempaqueInspección al Momento de la Entrega Contenido de la CajaConozca SU Generador Doméstico DE Reserva Conozca EL Panel DE Control DEL Sistema Puertas de Acceso Para Retirar una Puerta de AccesoPara Instalar una Puerta de Acceso Sistema de Combustible Gaseoso Antes DEL Arranque InicialConexión de la Batería Aceite de MotorParo del Sistema Configuración del Temporizador de PrácticaOperación Automática Verificación de la Operación AutomáticaEspecificaciones MantenimientoGenerador El Motor no Arranca Baja Tensión de la BateríaBaja Presión de Aceite Baja TensiónAlta Temperatura del Aceite Sobrevelocidad del MotorPara Limpiar el Generador Mantenimiento DEL GeneradorAlmacenamiento Cambio del Aceite del MotorNotas Reparacion DE Averias Manuel dUtilisation Table DES MatièresAvertissement Règles DE SécuritéLe contact de ces pièces risque de causer de graves brûlures Commutateurs de Transfert Approuvés Aide à lInstallationIntroduction Conseils AU PropriétaireEmplacement de la Génératrice Facteurs Relatifs au CombustibleDégagement Autour de la Génératrice Circuits Essentiels Sélection des Circuits EssentielsAppareil Watts Le Groupe Électrogène est Livré avec les Éléments Suivants DéballageVérification de la Livraison Contenu de la BoîteFAMILIARISEZ-VOUS Avec Votre Groupe Électrogène La position normale de fonctionnement est la position Pour Installer une Porte dAccès Portes dAccèsPour Enlever une Porte dAccès Système de Combustible Gazeux Avant LE Démarrage InitialBranchement de la Batterie Huile à MoteurRéglage de la Minuterie du Cycle dExercice Fonctionnement AutomatiqueArrêt du Système Vérification du Fonctionnement AutomatiqueCaractéristiques EntretienGénératrice Le Moteur Ne Démarre Pas Faible Tension de la BatterieFaible Pression dHuile Basse TensionTempérature de lHuile Élevée Emballement du MoteurVidange de lHuile Moteur Entretien DU GénérateurRemisage Pour Nettoyer le GénérateurDépannage