NOTE: In some areas you may need to acquire electrical permits for installing the Home Standby Generator, building permits for installing gas lines, and permits for noise allowances.Your installer should check your local codes AND obtain the permits before installing the system.

Fuel Factors

An important consideration affecting the entire installation is the type of fuel used by your Home Standby Generator. The system was factory tested and adjusted using natural gas as a fuel. Liquid propane (LP) may also be used as a fuel (see the Installation Manual).

Although there are specific factors that are inherent to each of these fuels, your location and the duration of possible utility interruptions should guide your selection of fuel type. For urban installations, Natural Gas (if available) should be your fuel of choice. For remote installations, a Liquefied Petroleum (LP) tank might better meet your needs.

For proper engine function, the following fuel guidelines are recommended:

Use clean, dry fuel, free of moisture or any particulate material. Using fuels outside the following recommended values may cause performance problems.

Generator Location

The actual physical location of your HSG has a direct affect on:

1.The amount of plumbing required to fuel your generator.

2.The amount of wiring required to control and connect your generator.

NOTE: Specific location guidelines are discussed in the Installation Manual. Acquaint yourself with that information and confer with your installer. Be sure to ask how your site might affect installation costs and compliance with local codes and standards.

Generator Clearances

The generator enclosure must be a minimum of 3 ft.

(92 cm) from combustible material. Leave at least 3 ft.

(92 cm) all around the enclosure for access to the inside of the enclosure.

The unit’s exhaust port must be at least 5 ft. (152 cm) from any building opening (window, door, vent etc.), and the exhaust must not be able to accumulate in any occupied area (Figure 1).

In engines set up to run on propane (LP) gas, commercial grade HD5 propane with a minimum fuel energy of 2500 BTUs/ft3 with maximum propylene content of 5% and butane and heavier gas content of 2.5% and minimum propane content of 90%.

WARNING

Propane and Natural Gas is extremely flammable and explosive.

Fire or explosion can cause severe burns or death.

The Home Standby Generator is equipped with an automatic safety gas “fuel shut-off” valve.

DO NOT operate the equipment if the “fuel shut-off” valve is missing or inoperative.

Power Decrease at High Altitude or High Temperature

Air density is less at high altitudes, resulting in less available engine power. Specifically, engine power will decrease 3.5% for each 1,000 feet (300 meters) above sea level and 1% for each 10° F (5.6°C) above 77°F (25°C). Make sure you and your installer consider these factors when determining total generator load.

Figure 1 — Home Standby Generator Clearances

Exhaust

 

Port

Exhaust port must be

 

 

5 ft (152 cm) minimum

 

distance from building

 

openings

6

Image 6
Contents Manual del Propietario Manuel de lUtilisateur Table of Contents Safety Rules Briggs & Stratton Power Products Home Generator Introduction Approved Transfer SwitchesInstallation Assistance Owner OrientationGenerator Location Power Decrease at High Altitude or High TemperatureFuel Factors Generator ClearancesEssential Circuits Essential Circuit SelectionDevice Running Watts Shipment Contents UnpackingDelivery Inspection Know Your Home Standby Generator Know Your System Control Panel LEDAccess Doors To Remove an Access DoorTo Install an Access Door Engine Oil Battery ConnectionBefore Initial START-UP Gaseous Fuel SystemAutomatic Operation Setting Exercise TimerTo perform the Set Exercise procedure Servicing the SystemSpecifications Fault Detection SystemGenerator Low Oil Pressure Low Battery VoltageOil Temperature High Engine Fail To StartWhen Calling the Factory Generator MaintenanceTo Clean the Generator StorageTroubleshooting Problem Cause CorrectionTabla DE Contenido Manual del PropietarioInstrucciones DE Seguridad PeligroAdvertencia Precaución Conmutadores de Transferencia Aprobados IntroducciónOrientación Para EL Propietario Asistencia para la instalaciónFactores Relacionados con el Combustible Ubicación del GeneradorDistancias Desde el Generador Circuitos Fundamentales Selección de los Circuitos FundamentalesDispositivo Vatiaje de Contenido de la Caja DesempaqueInspección al Momento de la Entrega El Generador Doméstico incluye lo siguienteConozca SU Generador Doméstico DE Reserva Conozca EL Panel DE Control DEL Sistema Puertas de Acceso Para Retirar una Puerta de AccesoPara Instalar una Puerta de Acceso Aceite de Motor Antes DEL Arranque InicialConexión de la Batería Sistema de Combustible GaseosoVerificación de la Operación Automática Configuración del Temporizador de PrácticaOperación Automática Paro del SistemaEspecificaciones MantenimientoGenerador Baja Tensión Baja Tensión de la BateríaBaja Presión de Aceite El Motor no ArrancaSobrevelocidad del Motor Alta Temperatura del AceiteCambio del Aceite del Motor Mantenimiento DEL GeneradorAlmacenamiento Para Limpiar el GeneradorNotas Reparacion DE Averias Table DES Matières Manuel dUtilisationRègles DE Sécurité AvertissementLe contact de ces pièces risque de causer de graves brûlures Conseils AU Propriétaire Aide à lInstallationIntroduction Commutateurs de Transfert ApprouvésEmplacement de la Génératrice Facteurs Relatifs au CombustibleDégagement Autour de la Génératrice Circuits Essentiels Sélection des Circuits EssentielsAppareil Watts Contenu de la Boîte DéballageVérification de la Livraison Le Groupe Électrogène est Livré avec les Éléments SuivantsFAMILIARISEZ-VOUS Avec Votre Groupe Électrogène La position normale de fonctionnement est la position Pour Installer une Porte dAccès Portes dAccèsPour Enlever une Porte dAccès Huile à Moteur Avant LE Démarrage InitialBranchement de la Batterie Système de Combustible GazeuxVérification du Fonctionnement Automatique Fonctionnement AutomatiqueArrêt du Système Réglage de la Minuterie du Cycle dExerciceCaractéristiques EntretienGénératrice Basse Tension Faible Tension de la BatterieFaible Pression dHuile Le Moteur Ne Démarre PasEmballement du Moteur Température de lHuile ÉlevéePour Nettoyer le Générateur Entretien DU GénérateurRemisage Vidange de lHuile MoteurDépannage