Briggs & Stratton 01894-1 manual Using the Generator, System Ground, Generator Location

Page 8

OPERATION

USING THE GENERATOR

System Ground

The generator has a system ground that connects the generator frame components to the ground terminals on the AC output receptacles.The system ground is connected to the AC neutral wire (the neutral is bonded to the generator frame).

Special Requirements

There may be Federal or State Occupational Safety and Health Administration (OSHA) regulations, local codes, or ordinances that apply to the intended use of the generator. Please consult a qualified electrician, electrical inspector, or the local agency having jurisdiction.

In some areas, generators are required to be registered with local utility companies.

If the generator is used at a construction site, there may be additional regulations which must be observed.

Connecting to a Building’s Electrical System

Connections for standby power to a building’s electrical system must be made by a qualified electrician.The connection must isolate the generator power from utility power, and must comply with all applicable laws and electrical codes.

WARNING

Generator produces powerful voltage.

Failure to isolate generator from power utility can result in death or injury to electric utility workers due to backfeed of electrical energy.

When using generator for backup power, notify utility company. Use approved transfer equipment to isolate generator from electric utility.

Use a ground fault circuit interrupter (GFCI) in any damp or highly conductive area, such as metal decking or steel work.

DO NOT touch bare wires or receptacles.

DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.

DO NOT operate generator in the rain or wet weather.

DO NOT handle generator or electrical cords while standing in water, while barefoot, or while hands or feet are wet.

DO NOT allow unqualified persons or children to operate or service generator.

Generator Location

Generator Clearance

WARNING

Exhaust heat/gases can ignite combustibles, structures or damage fuel tank causing a fire.

Keep at least 5 ft. (152 cm) clearance on all sides of generator including overhead.

Place generator in a well ventilated area, which will allow for removal of deadly exhaust gas. DO NOT place generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area (Figure 4). Prevailing winds and air currents should be taken into consideration when positioning generator.

Using a generator indoors WILL KILL YOU IN MINUTES.

Exhaust contains carbon monoxide, a poison gas you cannot see or smell.

NEVER use in the home ONLY use outdoors and

or in partly enclosed far from open windows, areas such as garages. doors, and vents.

Figure 4 — Generator Clearance

Exhaust Port

8

Image 8
Contents 01894-1 7000W Equipment Description Table of ContentsSafety Rules When Adding or Draining Fuel When Starting EquipmentWhen Operating Equipment When Transporting or Repairing EquipmentWhen Adjusting or Making Repairs to Your Generator When Testing for Engine SparkKnow Your Generator Volt AC, 20 Amp Duplex Receptacles May be120/240 Volt AC, 30 Amp Locking Receptacle May 120/240 Volt AC, 30 AmpAttach Handle AssemblyUnpacking the Generator Remove Cover on Start Switch When Adding FuelBefore Starting the Engine Add Engine OilUsing the Generator Connecting to a Building’s Electrical SystemSystem Ground Generator LocationStarting the Engine Jump Start ProcedureOperating Generator Connecting Electrical Loads Charging a BatteryStopping the Engine Do not Overload GENERATOR. See Don’t Overload GeneratorHow to Use the Battery Charger Cold Weather OperationCreating a Temporary Cold Weather Shelter Creating a Permanent Cold Weather ShelterReceptacles 120/240 Volt AC, 30 Amp, Locking ReceptacleVolt AC, 20 Amp, Duplex Receptacle Volt DC, 10 Amp ReceptaclePower Management DON’T Overload GeneratorCapacity ExampleEngine Maintenance SpecificationsGeneral Maintenance Recommendations Storage Troubleshooting Problem Cause CorrectionPage Limited Warranty Symboles de Danger et Moyens Table DES MatièresDescription DE L Équipement Règles DE SécuritéLors DE Lajout OU DE LA Vidange DU Carburant Lors DU Démarrage DE LéquipementLorsque Léquipement Fonctionne Lorsque Vous Transportez OU Réparez LéquipementLorsque Vous Réglez OU Réparez Votre Générateur Lors DE Tests Dallumage DU MoteurConnaissez Votre Générateur Fixer la poignée AssemblageEnlever le génératrice de la boite Avant LE Démarrage DU Moteur Ajoutez de lhuile à moteurAjoutez de lessence Enlevez le couvercle de linterrupteur de démarrageEmplacement de la Génératrice Utilisation DE LA GénératriceMise à la terre du système Branchement au système électrique dun édificeProcédure de démarrage à laide dune batterie dappoint Utilisation DU GénérateurDémarrage du Moteur Branchement des Charges Électriques Arrêt du MoteurRecharge d’une Batterie Placez linterrupteur de démarrage à la position StopFonctionnement PAR Temps Froid Comment Utiliser le Chargeur de BatterieVent Création d’un abri temporaireCréation d’un abri permanent Prises DE Courant Prise à Verrouillage de 120/240 Volts c.a., 30 AmpèresVolts c.a., 20 Ampères Prise de Courant Double Prise de 10 Ampères, 12 Volts c.cNE PAS Surcharger Générateur CapacitéGestion de la Consommation ExempleEntretien du Moteur Recommandations Générales D’ENTRETIENSpécifications Remisage Remarques Dépannage Période DE Garantie Garantie LimitéeTabla DE Contenidos Descripción DEL EquipoReglas DE Seguridad AdvertenciaPeligro Cuando Añada Combustible O Vacíe EL DepósitoCuando Ponga EN Funcionamiento EL Equipo Cuando Opere EL EquipoCuando Pruebe LA Bujía DEL Motor PrecauciónCuando Ajuste O Haga Reparaciones a SU Generador Conozca SU Generador Placa de CaracterísticasAceite Llena la Tapa Agrega aceite al motor aquí Culatazo el Principio Usó para comenzar motorFije el Asa MontajeDesembalaje del Generador Antes DE Darle Arranque AL Motor Agregar Aceite al MotorAgregue Combustible Quite la Cubierta en el Interruptor del ArranqueUSO DEL Generador Tierra del SistemaUbicación del Generador Conexión al Sistema Eléctrico de un EdificioProcedimiento de Arranque en Puente Operando EL GeneradorEncienda el Motor Conexion De Cargas Electricas Parado Del MotorCarga de la Bateria No Sobrecargue GENERADOR. Vea No Sobrecargue GeneradorCómo al Uso el Corcel de Batería Operación Durante UNClima Frío Figura 42 Refugio Frío Permanente del Tiempo Receptáculos Precaución 120/240 Voltios AC, 30 Amperios, Receptáculo de SeguridadVolt AC, 20 Amperios, Receptáculos Dobles Tomacorrientes de 12 Voltios DCNo Sobrecargue Generador CapacidadControl de la Energía EjemploMantenimiento del Motor EspecificacionesRecomendaciones Generales DE Mantenimiento Almacenamiento Problemo Causa Accion Diagnositicos DE AveríasNotas Notas Uso del consumidor Uso comercial