Briggs & Stratton 01894-1 manual Operating Generator, Starting the Engine, Jump Start Procedure

Page 9

OPERATION

OPERATING THE

GENERATOR

Starting the Engine

IMPORTANT: Always unplug the battery float charger before starting the generator.

Disconnect all electrical loads from the generator. Follow start instruction steps in numerical order:

1.Make sure unit is on a level surface.

IMPORTANT: Failure to start and operate unit on a level surface will cause the unit not to start or shut down during operation.

2.Follow start instructions given in engine operator’s manual and turn start switch on generator to “Start” position (Figure 5).

Figure 5 — Starter Switch

To prolong the life of starter components, DO NOT hold starter switch in “Start” position for more than 15 seconds, and pause for 1 minute.

NOTE: If engine starts but fails to run, or if unit shuts down during operation, make sure unit is on a level surface and check for proper oil level in crankcase.This unit may be equipped with a low oil protection device. See engine operator’s manual.

WARNING

Running engines produce heat.Temperature of muffler and nearby areas can reach or exceed 150°F (65°C).

Severe burns can occur on contact.

Exhaust heat/gases can ignite combustibles, structures or damage fuel tank causing a fire.

DO NOT touch hot surfaces and avoid hot exhaust gases.

Allow equipment to cool before touching.

Keep at least 5 ft. (152 cm) clearance on all sides of generator including overhead.

Code of Federal Regulation (CFR) Title 36 Parks, Forests, and Public Property require equipment powered by an internal combustion engine to have a spark arrester, maintained in effective working order, complying to USDA Forest service standard 5100-1C or later revision. In the State of California a spark arrester is required under section 4442 of the California Public resources code. Other states may have similar laws.

Jump Start Procedure

If the generator’s starting battery fails, use the following instructions to jump start your generator.You can jump start the generator using any 12 Volt automotive or utility style storage battery.

1.Unscrew the fuse holder and remove the generator’s 10 Amp in-line fuse (Figure 6).Verify the fuse is good or replace with a known good fuse. Reinstall fuse in the fuse holder.

Figure 6 — In-Line Fuse

2.Slide the red rubber boot off the generator’s battery terminal and push it onto the red wire, thus uncovering the POSITIVE battery terminal.

9

Image 9
Contents 01894-1 7000W Table of Contents Safety RulesEquipment Description When Starting Equipment When Adding or Draining FuelWhen Operating Equipment When Transporting or Repairing EquipmentWhen Testing for Engine Spark When Adjusting or Making Repairs to Your GeneratorVolt AC, 20 Amp Duplex Receptacles May be Know Your Generator120/240 Volt AC, 30 Amp Locking Receptacle May 120/240 Volt AC, 30 AmpAssembly Unpacking the GeneratorAttach Handle When Adding Fuel Remove Cover on Start SwitchBefore Starting the Engine Add Engine OilConnecting to a Building’s Electrical System Using the GeneratorSystem Ground Generator LocationJump Start Procedure Operating GeneratorStarting the Engine Charging a Battery Connecting Electrical LoadsStopping the Engine Do not Overload GENERATOR. See Don’t Overload GeneratorCold Weather Operation How to Use the Battery ChargerCreating a Permanent Cold Weather Shelter Creating a Temporary Cold Weather Shelter120/240 Volt AC, 30 Amp, Locking Receptacle ReceptaclesVolt AC, 20 Amp, Duplex Receptacle Volt DC, 10 Amp ReceptacleDON’T Overload Generator Power ManagementCapacity ExampleSpecifications General Maintenance RecommendationsEngine Maintenance Storage Problem Cause Correction TroubleshootingPage Limited Warranty Table DES Matières Symboles de Danger et MoyensDescription DE L Équipement Règles DE SécuritéLors DU Démarrage DE Léquipement Lors DE Lajout OU DE LA Vidange DU CarburantLorsque Léquipement Fonctionne Lorsque Vous Transportez OU Réparez LéquipementLors DE Tests Dallumage DU Moteur Lorsque Vous Réglez OU Réparez Votre GénérateurConnaissez Votre Générateur Assemblage Enlever le génératrice de la boiteFixer la poignée Ajoutez de lhuile à moteur Avant LE Démarrage DU MoteurAjoutez de lessence Enlevez le couvercle de linterrupteur de démarrageUtilisation DE LA Génératrice Emplacement de la GénératriceMise à la terre du système Branchement au système électrique dun édificeUtilisation DU Générateur Démarrage du MoteurProcédure de démarrage à laide dune batterie dappoint Arrêt du Moteur Branchement des Charges ÉlectriquesRecharge d’une Batterie Placez linterrupteur de démarrage à la position StopComment Utiliser le Chargeur de Batterie Fonctionnement PAR Temps FroidCréation d’un abri temporaire Création d’un abri permanentVent Prise à Verrouillage de 120/240 Volts c.a., 30 Ampères Prises DE CourantVolts c.a., 20 Ampères Prise de Courant Double Prise de 10 Ampères, 12 Volts c.cCapacité NE PAS Surcharger GénérateurGestion de la Consommation ExempleRecommandations Générales D’ENTRETIEN SpécificationsEntretien du Moteur Remisage Remarques Dépannage Garantie Limitée Période DE GarantieDescripción DEL Equipo Tabla DE ContenidosReglas DE Seguridad AdvertenciaCuando Añada Combustible O Vacíe EL Depósito PeligroCuando Ponga EN Funcionamiento EL Equipo Cuando Opere EL EquipoPrecaución Cuando Ajuste O Haga Reparaciones a SU GeneradorCuando Pruebe LA Bujía DEL Motor Placa de Características Conozca SU GeneradorAceite Llena la Tapa Agrega aceite al motor aquí Culatazo el Principio Usó para comenzar motorMontaje Desembalaje del GeneradorFije el Asa Agregar Aceite al Motor Antes DE Darle Arranque AL MotorAgregue Combustible Quite la Cubierta en el Interruptor del ArranqueTierra del Sistema USO DEL GeneradorUbicación del Generador Conexión al Sistema Eléctrico de un EdificioOperando EL Generador Encienda el MotorProcedimiento de Arranque en Puente Parado Del Motor Conexion De Cargas ElectricasCarga de la Bateria No Sobrecargue GENERADOR. Vea No Sobrecargue GeneradorOperación Durante UN Clima FríoCómo al Uso el Corcel de Batería Figura 42 Refugio Frío Permanente del Tiempo 120/240 Voltios AC, 30 Amperios, Receptáculo de Seguridad Receptáculos PrecauciónVolt AC, 20 Amperios, Receptáculos Dobles Tomacorrientes de 12 Voltios DCCapacidad No Sobrecargue GeneradorControl de la Energía EjemploEspecificaciones Recomendaciones Generales DE MantenimientoMantenimiento del Motor Almacenamiento Diagnositicos DE Averías Problemo Causa AccionNotas Notas Uso comercial Uso del consumidor