INSTALLATION

General Location Guidelines

Install the unit outdoors ONLY.

Place the unit in a prepared location that is flat and has provisions for water drainage.

Install the unit in a location where sump pump discharge, rain gutter down spouts, roof run-off, landscape irrigation, or water sprinklers will not flood the unit or spray the enclosure and enter any air inlet our outlet openings.

Install the unit where the location of any services such as phone, electrical, fuel, air conditioning, irrigation, including covered, concealed and underground services will not be affected or obstructed.

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, you may need to construct a windbreak to protect the unit.

Install the generator as close as possible to the Transfer Switch to reduce the length of wiring and conduit.

Install the generator as close as possible to the fuel supply to reduce length of pipes.

IMPORTANT: Laws or local codes may regulate the distance to the fuel supply.

The Home Generator System is shipped already attached to its mounting pad. Unless mandated by local code, a concrete slab is not required.

If mandated by local code, construct a concrete slab at least 3 inches thick and 6 inches longer and wider than the unit.

Attach unit to slab with 1/4” diameter (minimum) masonry anchor bolts long enough to retain the unit.

Fuel and Electrical Inlet Dimensions

Figure 2, below, depicts the location of the fuel piping connector. Also shown is the recommended location for punching holes for attaching the power conduit.

Lifting the Generator

The generator weighs more than 530 pounds. Proper tools, equipment and qualified personnel should be used in all phases of handling and moving the generator.

WARNING

Hazardous Voltage

Contact with power lines can cause electric shock or burn.

Lifting Hazard / Heavy Object

Can cause muscle strain or back injury.

If lifting or hoisting equipment is used, DO NOT contact any power lines.

DO NOT lift or move generator without assistance.

Use lifting pipes as described in the section “Lifting the Generator” in installation manual.

The unit may shift on the lifting pipes during movement, which can cause injury.

DO NOT lift unit by roof as damage to generator will occur.

Figure 2 — Generator Fuel and Conduit Attachment Locations, Oil Fill Side of Unit

Recommended

 

Conduit Attachment

 

Area

 

Fuel Piping

 

Connector

3/4” NPT

 

 

7

Image 7 Contents
12000 Customer Responsibilities Table of ContentsInstaller Responsibilities Equipment Description Engine exhaust from this product contains Important Safety Rules Hazard Symbols and Meanings Do not dispose of battery in a fireSafety Rules Installing the 15A fuse could cause the engine to start Installation NPT Fuel and Electrical Inlet DimensionsLifting the Generator General Location GuidelinesPort Access DoorsTo Open an Access Door To lift InsertDo not light a cigarette or smoke To Close an Access DoorTemporary Manometer Installed 10ft 15ft 20ft 30ft 40ft Fuel ConsumptionFuel Pipe Sizing 10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ftWiring for the 10 Pole Connector Wiring for the 2 Pole ConnectorSystem Connections Grounding the Generator Fault Detection SystemTo install the remote LED panel Generator AC Connection SystemEngine Oil Battery ConnectionBefore Initial START-UP System Control PanelFuel Supply System Servicing the BatteryTo configure the fuel system for LP use Fuel System SelectionFor a 15kW Home Generator System Engine AdjustmentInstall 15 Amp fuse in control panel Initial START-UP no LoadGovernor Installation Inspection Setting Exercise TimerAutomatic Operation Sequence Physical Properties Propane Natural Gas Fuel Comparison ChartWithdrawal Rate 32F 20F 10F 30F 40F Responsabilidades DEL Cliente Dimensiones de la Entrada para ElectricidadTabla DE Contenido Descripción DEL EquipoGases Tóxicos AdvertenciaSímbolos de Peligro y Significados ExplosiónLos generadores producen un voltaje muy poderoso Aviso PrecauciónInstala el fusible se puede producir el arranque del motor Contenido de la Caja InstalaciónPrecauciones al Momento del Desempaque Inspección al Momento de la EntregaElevación del Generador Dimensiones de la Entrada para Electricidad y CombustiblePautas Generales para la Ubicación del Generador Para abrir una puerta de acceso Puertas de AccesoPara cerrar una puerta de acceso Sistema DE Combustible Gaseoso Figura 21 Manómetro Instalado Transitoriamente Gas Natural peso específico = Dimensiones de la Cañería de CombustibleConsumo de Combustible Gas Natural Vapor de PLCableado para toma bipolar Conexiones DE SistemaToma de 10 polos Contactos de fallo Sistema de Detección de Fallas Sistema de Conexión de c.a. del GeneradorConexión a Tierra del Generador Interconexiones del Circuito de ControlAceite de Motor Antes DEL Arranque Inicial DEL MotorPanel de Control del Sistema Conexión de la BateríaServicio la Batería Para configurar el sistema de combustible para uso de LPSelección DEL Sistema DE Combustible Sistema de Suministro de CombustibleQuite el tapón de la entrada LP de la válvula en T Arranque Inicial SIN CargaAjuste del Motor Para sistema de generador de doméstico de 15kWTornillo de Ajuste Del ReguladorInspección Posterior a LA Instalación Configuración DEL Temporizador DE PrácticaTemporizador de enfriamiento del motor Propiedades físicas Propano Gas natural Cuadro de Comparación de CombustiblesTasa de consumo 32F 20F 10F 30F 40F Responsabilités DE Lacheteur Responsabilités DE LinstallateurTable DES Matières Description DE LéquipementManuel dUtilisation Symboles de Danger et MoyensAvertissement ExplosionNE touchez PAS les fils dénudés ou les boîtiers Avis Installation Soulèvement de la Génératrice Directives Générales Concernant lEmplacementPour ouvrir une porte d’accès Portes dAccèsPour fermer une porte d’accès Il faudrait inclure une sortie pour manomètre Manomètre Temporaire InstalléGaz Naturel densité = 0,65 Consommation de CombustibleGrosseur du Tuyau de Combustible Gas Naturel Vapeur PLPrise à dix pôles Contacts de défaillance Connexions DE SystèmeBranchement de la prise à deux pôles Branchement de la prise à dix pôlesNeutre De Puissance Interconnexions du Circuit de CommandeMise à la Masse de la Génératrice Système de Détection des PannesHuile à Moteur Tableau de Commande du SystèmeAvant LE Démarrage Initial DU Moteur Branchement de la BatteriePour la groupe électrogène résidentiel de 12kW Sélection DU Système DE CombustibleSystème dAlimentation en Combustible Entretien de la BatterieRéglez l’interrupteur de système de la génératrice sur on Démarrage Initial Sans ChargePour la groupe électrogène résidentiel de 15kW Raccordez le conduit d’essence à l’entrée LP . Soupape en TRéglage du Moteur Minuterie de Refroidissement du Moteur Vérification InstallationCapteur de Prise en Charge de la Tension de Service Réglage DE LA Minuterie DE Cycle DexerciceRemarques Propriétés physiques Propane Gaz naturel Charte de Comparaison des Combustibles