Trailer Setup See Figure 4-1for component identification. Carefully read all instructions before starting.

1.Locate a suitable, level location. Also be sure there are no overhead wires or obstructions.

The trailer is balanced so the majority of the weight rests on the tow bar (Jack).

If on a minor incline, the safest way to position the tailer is to have the tow bar facing down the incline (front of the trailer lower than the rear of the trailer).

2.Install tire chocks if used. These prevent the trailer from moving when parked.

3.Disconnect the safety chains and the trailer light connector from the tow vehicle.

4.Pull the pin on the front jack and rotate the jack 90 degrees to the vertical position. Lock the jack in the vertical position using the pin to secure it.

5.Move the Coupler Handle to the vertical position to release the ball hitch.

OR

Release the Pintle hook.

6.Use the jack to raise the trailer coupler from the ball hitch of the tow vehicle.

7.The tow vehicle can now be moved away from the trailer.

8.Use the jack to level the trailer for operation.

Voltage Selection

WARNING: High voltage is present whenever the engine is running. Electrical shock can cause serious or fatal injury. Always stop engine before connecting or disconnecting power cords or external devices.

WARNING: High voltage is present whenever engine is running. Electrical shock can cause serious or fatal injury. Never operate electrical equipment while standing in water, on wet ground or with wet hands, feet or shoes or while barefoot.

Hard Wire Load Terminal Block, shown in Figure 3-5.

1.Ensure the generator is off.

2.Place voltage select switch in the correct position 208/120, 240/120 or 480/277VAC. Refer to Table 4-2for voltages available in each position. To ensure the switch position is not accidently changed, it should be padlocked as shown in Figure 4-3.

Figure 4-3

Insert padlock through the hole in the handle. This activates an internal mechanism that prevents handle rotation.

3.Carefully inspect all Individual load cables for broken insulation or other signs of damage. Never use a damaged cable. Replace it before usage.

4.L1, L2, L3, Neutral and Ground cables must be brought into load block compartment through access hole in base of enclosure.

5.Ensure that wires are properly connected and connections are secure.

6.Use disconnect at the load to turn off the load. Do not start engine with load switched “on”. Allow engine to come up to speed and warm up before load is switched on.

Note: When the generator is running, opening load block door will cause load disconnect to trip.

7.Observe the output voltage indicator and set the Voltage Adjust (Figure 4-5) for proper voltage.

8.If left unattended, lock all doors to prevent tampering or injury.

MN2417

Operation 4-5

Image 27
Contents Tier 2/3 Towable Generators Trailer and Skid Mounted California Proposition 65 Warning Table of Contents Ii Table of Contents MN2417 Read This Manual Thoroughly Section Product Safety InformationPrecaution Statements Used In This Manual PropertyOperation Statements On next MN2417 Product Safety Information Operation Statements Burn Statements Installation Statements Installation Statements Maintenance Statements Product Safety Information MN2417 Labor Parts Limited WarrantyGeneral Information MN2417 Section Receiving & Installation Generator Mounting Skid Installation Hot Exhaust GassesFuel Connections Standby Power Ratings Prime Power RatingsProtection Receptacle Panel Single Phase Single Phase ConnectionsGeneral Wiring Considerations Three Phase ConnectionsTransfer Switch Considerations Battery Charger ConsiderationsFrame Ground Connection Battery Installation Recommended Engine Oil and Battery Type Oil & Battery RecommendationsPost Installation Checks Post Installation Checks Towing the Generator Selecting the Proper Towing EquipmentTow Vehicle Tow Hitch Capacity Towing Heavy Trailer Loads Trailer Component Identification Lug Nut Tightening Specifications Page Receptacle Panel Load Connections, see Figure Three/Single Phase OperationOperator Control Panel Components Voltage Reconnect and AdjustmentManual Start Procedure Manual Stop ProcedureAuto Start Procedure Digital Engine Controller Description EM0046A21 MRS17 Alarm & Warning ConditionsMeasurement Menu OFF ModeMAN Mode AUT ModeAdjustment Menu Alarm ListECU Alarm List Sensor fail FLS see Table Shut down SD see TablePossible Warnings Inputs and Outputs Binary InputsBinary outputs Set points Basic Setpoints Analog Inputs10 Engine Setpoints Stabil Time11 Engine Protect Setpoints 10Engine Setpoints12 Generator Protect Setpoints 14 IOM/PTM Module Setpoints 13 Sensor Spec Setpoints+ D+ Jdic Engine GeneralTroubleshooting Guide Problems and SolutionsLoad too large for unit 1Troubleshooting GuideTroubleshooting and Maintenance MN2417 Part number Appendix a Wiring DiagramsFigure A-1 TS25 Connection Diagram Figure A-2 TS25 Connection Diagram Figure A-3 TS25 Connection Diagram Figure A-4 TS25 Connection Diagram Figure A-5 TS25 Connection Diagram Figure A-6 TS25 Connection Diagram Figure A-7 TS35 Connection Diagram Figure A-8 TS35 Connection Diagram Figure A-9 TS35 Connection Diagram Figure A-10 TS35 Connection Diagram Figure A-11 TS35 Connection Diagram Figure A-12 TS35 Connection Diagram Figure A-13 TS35 Power Connection Diagram Figure A-14 TS60 Connection Diagram Figure A-15 TS60 Connection Diagram Figure A-16 TS60 Connection Diagram Figure A-17 TS60 Connection Diagram Figure A-18 TS60 Connection Diagram Figure A-19 TS60 Connection Diagram Figure A-20 TS60 Connection Diagram Figure A-21 TS80 Connection Diagram Figure A-22 TS80 Connection Diagram Figure A-23 TS80 Connection Diagram Figure A-24 TS80 Connection Diagram Figure A-25 TS80 Connection Diagram Figure A-26 TS80 Connection Diagram Figure A-27 TS80 Connection Diagram Figure A-28 TS80 Connection Diagram Figure A-29 TS80 Connection Diagram Figure A-30 TS80 Connection Diagram Figure A-31 TS400 Connection Diagram Figure A-32 TS400 Connection Diagram Figure A-33 TS400 Connection Diagram Figure A-34 TS400 Connection Diagram Figure A-35 TS400 Connection Diagram Figure A-36 TS400 Connection Diagram Figure A-37 TS400 Connection Diagram Figure A-38 TS400 Connection Diagram Figure A-39 TS400 Connection Diagram Baldor District Offices Baldor Electric Company