Figure 4-5 Operator Control Panel Components
Volts
Analog display of generator output voltage in RMS volts.
AMPS
Analog display of generator output current in RMS amps.
HERTZ
Analog display of generator RPM which relates to the output frequency in Hertz.
Battery
Displays the voltage of the engine starting battery.
Water Temp
Displays the temperature of the engine coolant.
Oil Press
Displays engine oil pressure.
Horn A Horn (annunciator or buzzer) sounds an alarm when operator attention is needed.
Shore Power Inlet Connect an extension cord that has an appropriate rating from utility power to this outlet. To power onboard battery charger, block heater, etc.
1
OFF 2
Amps Switch switch (On−Off ) Selects what is displayed on AC Amperes meter.
Off − No AC Ampere display.
1 − Phase 1 current display.
2 − Phase 2 current display.
3 − Phase 3 current display.
Voltage Select Switch switch
Selects 208/120, 240/120 or 480/277VAC.
− | + | Voltage Adjust | |
Increase or Decrease the Generator output | |||
|
|
voltage.
Panel Lights)
Lamps to illuminate the operator panel.
PANEL LIGHTS
15
BREAKER
or
2 Pole
or
1 Pole
Breaker Circuit Breakers provides protection on some units. To reset a breaker, simply press the center button when tripped or move handle to f" then back to
Note: Some features are optional and may not be installed on your system.
Panel Lights switch (On−Off )
ON | OFF | Turns on the panel lights. |
| ||
| FUSE |
|
|
| Fuse Fuses provides protection on some units. |
|
| (Do not remove while generator is running). |
Auto Start Connection for external two wire starting from transfer switch or other controller. Strip the insulation from the remote start wires. Simply press while inserting the wire then release to secure the connection.
Voltage Reconnect and Adjustment
The digital engine controller runs software called voltage auto−detect. Every time the engine is started and after the timer in the Engine Params: Stabil Time has elapsed, the nominal voltage will be detected and locked in. Various set points in the engine controller are then calculated as a percentage of this nominal voltage. For example: The over−voltage set point is set to 110%.
This means that when the unit is providing 208V, the over−voltage set point will lock in at 229V. When the unit is operating in 480V the over−voltage set point will lock in at 528V.
Example: To change the voltage from 208V nominal to 240V nominal, the voltage adjustment must be made before the controller locks in the nominal voltage.
1.Set the Voltage Select Switch to 240/120V position.
2.Start the engine.
3.Immediately adjust the Voltage Adjust for 240VAC nominal before the 20 second timer expires.
4.The new 240V nominal voltage is now locked in.
This procedure must be performed whenever the nominal voltage is changed.
MN2417 | Operation |