Baldor TS400, TS45, TS60, TS80, TS175, TS130, TS35, TS250 manual Generator Protect Setpoints

Page 39

 

Table 4-12 Generator Protect Setpoints

 

 

 

Overload

 

Threshold for generator overload (in % of Nominal power)

 

 

Step: 1% of Nominal power; Range: 0 − 200%

 

 

 

Overload Wrn

 

Threshold for generator overload warning (in % of Nominal power)

 

 

Step: 1% of Nominal power; Range: 0 − 200%

 

 

 

Overload del

 

Delay for generator overload alarm. Step: 0.1s; Range: 0 − 60.0 s

Ishort

 

Shutdown occurs when short circuit limit Ishort limit is reached.

 

 

Step: 1 % of Nominal current; Range: 100 − 500 %

 

 

 

2Inom del

 

IDMT curve shape selection. 2Inom del is Reaction time of IDMT

 

 

protection for 200% overcurrent Igen = 2* Nominal current.

 

 

Step: 0,1 s; Range: 0,1 − 20 s

 

 

IDMT is “very inverse” generator over current protection. Reaction time is

 

 

not constant but depends on generator over current level according

 

 

following formula. Reaction time is limited up to 900 sec = 15 minutes.

 

 

IDMT protection is not active for Reaction time values longer than 15

 

 

minutes.

 

 

2lnom del * Nomin current

 

 

Reaction Time + lgen * Nomin current

Curr unbal

 

Threshold for generator current asymmetry (unbalance).

 

 

Step: 1% of Nominal current; Range: 1 − 100% of Nominal current

 

 

 

Curr unbal del

 

Delay for generator current assymetry. Step: 0.1 s; Range: 0 − 60.0 s

Gen >V

 

Shutdown level for generator overvoltage. All three phases are checked.

 

 

Maximum out of three is used.

 

 

Step: 1% of Nominal voltage; Range: Gen >V Wrn −200%

 

 

 

Gen >V Wrn

 

Warning level for generator overvoltage. All three phases are checked.

 

 

Maximum out of three is used.

 

 

Step: 1% of Nominal voltage; Range: Gen <V Wrn − Gen >V

 

 

 

Gen <V Wrn

 

Warning level for generator under voltage. All three phases are checked.

 

 

Minimum out of three is used.

 

 

Step: 1% of Nominal voltage; Range: Gen <V − Gen >V Wrn

Gen <V

 

Shutdown level for generator under voltage. All three phases are checked.

 

 

Minimum out of three is used.

 

 

Step: 1% of Nominal voltage; Range: 0% − Gen <V Wrn

 

 

 

Gen V del

 

Delay for generator under voltage and over voltage alarm

 

 

Step: 0.1s; Range: 0 − 60 s

 

 

 

Volt unbal

 

Threshold for generator voltage unbalance alarm.

 

 

Step: 1% of Nominal voltage; Range: 0 − 100% of Nominal voltage

 

 

 

Volt unbal del

 

Delay for generator voltage unbalance alarm.

 

 

Step: 0.1s; Range: 0 − 60.0 s

 

 

 

Gen >f

 

Shutdown level for generator over frequency.

 

 

Step: 0.1% of Nominal frequency; Range: Gen > Wrn − 200.0%

 

 

 

Gen >f Wrn

 

Warning level for generator over frequency.

 

 

Step: 0.1% of Nominal frequency; Range: Gen <f Wrn − Gen >V

 

 

 

Gen <f

 

Shutdown level for generator under frequency.

 

 

Step: 0.1% of Nominal frequency; Range: 0.0 − Gen <f Wrn

 

 

 

Gen <f Wrn

 

Warning level for generator under frequency.

 

 

Step: 0.1% of Nominal frequency; Range: Gen <f − Gen >f Wrn

 

 

 

Gen f del

 

Delay for generator under frequency and over frequency alarm.

 

 

Step: 0.1s; Range: 0 − 60.0 s

MN2417

Operation 4-17

Image 39
Contents Tier 2/3 Towable Generators Trailer and Skid Mounted California Proposition 65 Warning Table of Contents Ii Table of Contents MN2417 Read This Manual Thoroughly Section Product Safety InformationPrecaution Statements Used In This Manual PropertyOperation Statements On next MN2417 Product Safety Information Operation Statements Burn Statements Installation Statements Installation Statements Maintenance Statements Product Safety Information MN2417 Labor Parts Limited WarrantyGeneral Information MN2417 Section Receiving & Installation Generator Mounting Skid Installation Hot Exhaust GassesFuel Connections Standby Power Ratings Prime Power RatingsProtection Receptacle Panel Single Phase Single Phase ConnectionsGeneral Wiring Considerations Three Phase ConnectionsTransfer Switch Considerations Battery Charger ConsiderationsFrame Ground Connection Battery Installation Recommended Engine Oil and Battery Type Oil & Battery RecommendationsPost Installation Checks Post Installation Checks Towing the Generator Selecting the Proper Towing EquipmentTow Vehicle Tow Hitch Capacity Towing Heavy Trailer Loads Trailer Component Identification Lug Nut Tightening Specifications Page Receptacle Panel Load Connections, see Figure Three/Single Phase OperationOperator Control Panel Components Voltage Reconnect and AdjustmentManual Start Procedure Manual Stop ProcedureAuto Start Procedure Digital Engine Controller Description EM0046A21 MRS17 Alarm & Warning ConditionsMeasurement Menu OFF ModeMAN Mode AUT ModeAdjustment Menu Alarm ListECU Alarm List Sensor fail FLS see Table Shut down SD see TablePossible Warnings Inputs and Outputs Binary InputsBinary outputs Set points Basic Setpoints Analog Inputs10 Engine Setpoints Stabil Time11 Engine Protect Setpoints 10Engine Setpoints12 Generator Protect Setpoints 14 IOM/PTM Module Setpoints 13 Sensor Spec Setpoints+ D+ Jdic Engine GeneralTroubleshooting Guide Problems and SolutionsLoad too large for unit 1Troubleshooting GuideTroubleshooting and Maintenance MN2417 Part number Appendix a Wiring DiagramsFigure A-1 TS25 Connection Diagram Figure A-2 TS25 Connection Diagram Figure A-3 TS25 Connection Diagram Figure A-4 TS25 Connection Diagram Figure A-5 TS25 Connection Diagram Figure A-6 TS25 Connection Diagram Figure A-7 TS35 Connection Diagram Figure A-8 TS35 Connection Diagram Figure A-9 TS35 Connection Diagram Figure A-10 TS35 Connection Diagram Figure A-11 TS35 Connection Diagram Figure A-12 TS35 Connection Diagram Figure A-13 TS35 Power Connection Diagram Figure A-14 TS60 Connection Diagram Figure A-15 TS60 Connection Diagram Figure A-16 TS60 Connection Diagram Figure A-17 TS60 Connection Diagram Figure A-18 TS60 Connection Diagram Figure A-19 TS60 Connection Diagram Figure A-20 TS60 Connection Diagram Figure A-21 TS80 Connection Diagram Figure A-22 TS80 Connection Diagram Figure A-23 TS80 Connection Diagram Figure A-24 TS80 Connection Diagram Figure A-25 TS80 Connection Diagram Figure A-26 TS80 Connection Diagram Figure A-27 TS80 Connection Diagram Figure A-28 TS80 Connection Diagram Figure A-29 TS80 Connection Diagram Figure A-30 TS80 Connection Diagram Figure A-31 TS400 Connection Diagram Figure A-32 TS400 Connection Diagram Figure A-33 TS400 Connection Diagram Figure A-34 TS400 Connection Diagram Figure A-35 TS400 Connection Diagram Figure A-36 TS400 Connection Diagram Figure A-37 TS400 Connection Diagram Figure A-38 TS400 Connection Diagram Figure A-39 TS400 Connection Diagram Baldor District Offices Baldor Electric Company