Baldor TS80, TS25, TS45, TS60, TS400, TS175, TS130 Sensor Spec Setpoints, 14 IOM/PTM Module Setpoints

Page 40

 

Table 4-13 Sensor Spec Setpoints

 

 

 

Calibr AI1,AI2, AI3

 

Calibrating constant to adjust the measured value of IL analog inputs.

 

 

Physical dimension of calibrating constant is corresponding to Analog

 

 

input. Step: 1; Range: −1000 to +1000

 

 

 

AnOut−kW/20mA

 

Conversion coefficient from gen−set power to iG−IOM or PTM analog

 

 

output. Step: 1; Range: 1 to 32000

 

Table 4-14 IOM/PTM Module Setpoints

 

 

 

AnlInIOM1 lev1

 

The level for IOM ANALOG INPUT 1 alarm detection.

 

 

Step: 1; Range: −100 to +10000

 

 

 

AnlInIOM1 lev2

 

The level for IOM ANALOG INPUT 1 alarm detection.

 

 

Step: 1; Range: −100 to+10000

 

 

 

AnlInIOM1 del

 

Delay for IOM ANALOG INPUT 1 alarm. Step: 1 s; Range: 0 − 180 s

AnlInIOM2 lev1

 

The level for IOM ANALOG INPUT 2 alarm detection.

 

 

Step: 1; Range: −100 to +10000

 

 

 

AnlInIOM2 lev2

 

The level for IOM ANALOG INPUT 2 alarm detection.

 

 

Step: 1; Range: −100 to +10000

 

 

 

AnlInIOM2 del

 

Delay for IOM ANALOG INPUT 2 alarm. Step: 1 s; Range: 0 − 180 s

AnlInIOM3 lev1

 

The level for IOM ANALOG INPUT 3 alarm detection.

 

 

Step: 1; Range: −100 to +10000

 

 

 

AnlInIOM3 lev2

 

The level for IOM ANALOG INPUT 3 alarm detection.

 

 

Step: 1; Range: −100 to +10000

 

 

 

AnlInIOM3 del

 

Delay for IOM ANALOG INPUT 3 alarm.

 

 

Step: 1 s; Range: 0 − 180 s

 

 

 

AnlInIOM4 lev1

 

The level for IOM ANALOG INPUT 4 alarm detection.

 

 

Step: 1; Range: −100 to +10000

 

 

 

AnlInIOM4 lev2

 

The level for IOM ANALOG INPUT 4 alarm detection.

 

 

Step: 1; Range: −100 to +10000

 

 

 

AnlInIOM4 del

 

Delay for IOM ANALOG INPUT 4 alarm. Step: 1 s; Range: 0 − 180 s

 

 

The protection of IOM/PTM inputs is activated by over crossing the limits.

 

 

 

Calibr AInIOM 1..4

 

Calibrating constant to adjust the measured value of IOM/PTM analog

 

 

inputs. Physical dimension of calibrating constant is corresponding to

 

 

Analog input. Step: 1; Range: −1000 to +1000

4-18 Operation

MN2417

Image 40
Contents Tier 2/3 Towable Generators Trailer and Skid Mounted California Proposition 65 Warning Table of Contents Ii Table of Contents MN2417 Section Product Safety Information Read This Manual ThoroughlyProperty Precaution Statements Used In This ManualOperation Statements On next MN2417 Product Safety Information Operation Statements Burn Statements Installation Statements Installation Statements Maintenance Statements Product Safety Information MN2417 Limited Warranty Labor PartsGeneral Information MN2417 Section Receiving & Installation Generator Mounting Skid Hot Exhaust Gasses InstallationFuel Connections Prime Power Ratings Standby Power RatingsProtection Single Phase Connections Receptacle Panel Single PhaseThree Phase Connections Transfer Switch ConsiderationsBattery Charger Considerations General Wiring ConsiderationsFrame Ground Connection Battery Installation Oil & Battery Recommendations Recommended Engine Oil and Battery TypePost Installation Checks Post Installation Checks Selecting the Proper Towing Equipment Towing the GeneratorTow Vehicle Tow Hitch Capacity Towing Heavy Trailer Loads Trailer Component Identification Lug Nut Tightening Specifications Page Three/Single Phase Operation Receptacle Panel Load Connections, see FigureVoltage Reconnect and Adjustment Operator Control Panel ComponentsManual Stop Procedure Manual Start ProcedureAuto Start Procedure Alarm & Warning Conditions Digital Engine Controller Description EM0046A21 MRS17OFF Mode MAN ModeAUT Mode Measurement MenuAlarm List Adjustment MenuECU Alarm List Shut down SD see Table Sensor fail FLS see TablePossible Warnings Binary Inputs Inputs and OutputsBinary outputs Analog Inputs Set points Basic Setpoints Stabil Time 10 Engine Setpoints10Engine Setpoints 11 Engine Protect Setpoints12 Generator Protect Setpoints 13 Sensor Spec Setpoints 14 IOM/PTM Module Setpoints+ D+ Jdic General EngineProblems and Solutions Troubleshooting Guide1Troubleshooting Guide Load too large for unitTroubleshooting and Maintenance MN2417 Appendix a Wiring Diagrams Part numberFigure A-1 TS25 Connection Diagram Figure A-2 TS25 Connection Diagram Figure A-3 TS25 Connection Diagram Figure A-4 TS25 Connection Diagram Figure A-5 TS25 Connection Diagram Figure A-6 TS25 Connection Diagram Figure A-7 TS35 Connection Diagram Figure A-8 TS35 Connection Diagram Figure A-9 TS35 Connection Diagram Figure A-10 TS35 Connection Diagram Figure A-11 TS35 Connection Diagram Figure A-12 TS35 Connection Diagram Figure A-13 TS35 Power Connection Diagram Figure A-14 TS60 Connection Diagram Figure A-15 TS60 Connection Diagram Figure A-16 TS60 Connection Diagram Figure A-17 TS60 Connection Diagram Figure A-18 TS60 Connection Diagram Figure A-19 TS60 Connection Diagram Figure A-20 TS60 Connection Diagram Figure A-21 TS80 Connection Diagram Figure A-22 TS80 Connection Diagram Figure A-23 TS80 Connection Diagram Figure A-24 TS80 Connection Diagram Figure A-25 TS80 Connection Diagram Figure A-26 TS80 Connection Diagram Figure A-27 TS80 Connection Diagram Figure A-28 TS80 Connection Diagram Figure A-29 TS80 Connection Diagram Figure A-30 TS80 Connection Diagram Figure A-31 TS400 Connection Diagram Figure A-32 TS400 Connection Diagram Figure A-33 TS400 Connection Diagram Figure A-34 TS400 Connection Diagram Figure A-35 TS400 Connection Diagram Figure A-36 TS400 Connection Diagram Figure A-37 TS400 Connection Diagram Figure A-38 TS400 Connection Diagram Figure A-39 TS400 Connection Diagram Baldor District Offices Baldor Electric Company