| Table | |
|
|
|
Start RPM |
| “Firing” speed when iL controller stops cranking (starter goes OFF). |
|
| Step: 1% of nominal RPM; Range: 5 − 50 % |
|
|
|
Starting POil |
| When reached controller stops cranking (starter goes OFF). |
|
| Step: 0,1 psi; Range: −100 − 10000 |
|
| Note: There are three conditions for stop cranking: Starting RPM, |
|
| StartingPOil and D+ (when enabled). Starter goes off when any |
|
| of these conditions is valid. |
|
|
|
Prestart time |
| Time of closing of the PRE−START output prior to the engine start. |
|
| Set to zero if you want to leave the output PRE−START open. |
|
| Step: 1s; Range: 0 − 600 s |
|
|
|
MaxCrank time |
| Maximum time limit of cranking. Step: 1s; Range: 1 − 60 s |
CrnkFail pause |
| Pause between crank attempts. Step: 1s; Range: 5 − 60 s |
Crank attemps |
| Max number of crank attempts. Step: 1; Range: 1 − 10 |
Idle time |
| Idle time delay starts when RPM exceeds Start RPM . Start fail is detected |
|
| when during Idle state RPM decreases below 2. |
|
| During the Idle time timer running the binary output IDLE/NOMINAL is |
|
| opened, when it elapses the IDLE/NOMINAL output closes. |
|
| Binary output IDLE/NOMINAL opens during Cooling period again. |
|
| Step: 1 s; Range: 0 − 600 s |
|
| Note: If the IDLE function not supported on the governor, set the Idle time |
|
| nevertheless to minimum 5s to avoid Underspeed possibly |
|
| caused by instability of the engine short after start. |
|
|
|
GCB CloseDelay |
| GCB can be closed earliest GCB CloseDelay after Stabil time when all |
|
| electric values are in overunder voltage and over−under frequency limits. |
|
| Step: 1 s; Range: 0 − 300 s |
|
|
|
Stabil time |
| Generator Nominal voltage is detected during genset start after starter is |
|
| switched off and Idle time elapses. Electric generator protections are |
|
| active since detection. Step: 1 s; Range: 0 − 300 s |
|
|
|
MinStpValvTime |
| Binary output Stop solenoid closes when stop sequence begins and |
|
| closes at least for MinStpValvTime. Example MinStpValvTime = 20 sec. |
|
| a) When engine stops (RPM=0) in 10 seconds, Binary output Stop |
|
| solenoid still stays closed for 10 sec. |
|
| b) When engine stops in 30 seconds, Binary output Stop solenoid opens |
|
| 10 seconds after RPM=0 and Vg =0 and Oil pressure = 0. Those 10 sec is |
|
| fix time for safe stop. Step: 1s; Range: 0 − 180 s |
|
| Note: Stop of engine is detected when all following conditions are met: |
|
| RPM =0, Oil pressure < StartingPOil and Generator voltage < 10 VAC. |
|
| Stop fail is detected when is difference between those conditions, e.g |
|
| RPM=O and Generator voltage > 10V. |
RPM
Start RPM | RPM |
| |
| RPM = 2 |
Idle Function
B O S tarter
| B O IDLE /RA T E D |
|
|
|
|
|
|
|
| ||
| Idle tim e | M in stab tim e |
|
|
| ||||||
Electric protections | |||||||||||
|
|
| Start Fail |
|
|
|
|
| activ e | ||
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Stabil Time
MN2417 | Operation |