Baldor TS250, TS45, TS60, TS400, TS80, TS175, TS130 Inputs and Outputs, Binary Inputs, Binary outputs

Page 35

Inputs and Outputs

Any Binary input or output can be configured to any controller terminal Inputs are BI1 − BI6, Outputs are BO1 − BO6) or changed to different function by LiteEdit software.

There is fixed 1 sec delay when any binary input is configured as protection.

 

Table 4-6 Binary Inputs

 

 

 

 

 

 

Alarm

 

 

Alarm type Warning or Shut down

 

 

 

 

Alarm active All the time, or Engine running only

 

 

 

 

 

 

Rem start/stop

 

 

External request for engine run. AUT mode only.

 

Emergency stop

 

 

If the input is opened, shut down is immediately activated. Input is

 

 

 

 

inverted (normally closed).

 

 

 

 

 

 

Rem start/stop

 

 

External request for engine run. AUT mode only.

 

Table 4-7 Binary outputs

 

 

 

 

 

 

Starter (relay output)

 

 

The closed relay energizes the starter motor.

 

 

 

 

The relay opens if:

 

 

 

 

S The firing speed is reached or

 

 

 

 

S Maximum time of cranking is exceeded or

 

 

 

 

S Request to stop occurs

 

 

 

 

 

 

Fuel solenoid (relay output)

 

 

Closed output opens the fuel solenoid and enables the engine start.

 

 

 

 

The output opens if:

 

 

 

 

Emergency stop occurs or

 

 

 

 

Cooled gen−set is stopped or

 

 

 

 

In pause between repeated starts

 

 

 

 

 

 

Prestart

 

 

Output is closed prior to the engine start (Prestart) and opens when

 

 

 

 

START RPM speed is reached.

 

 

 

 

During repeated crank attempts the output is closed too.

 

 

 

 

The output could be used for pre−glow, pre−heat or prelubrication.

 

 

 

 

 

 

Common Sd

 

 

Output closes when any shut−down alarm appears.

 

 

 

 

The output opens, if alarm is not active and FAULT RESET is pressed.

 

 

 

 

Used for shunt trip.

 

MN2417

Operation 4-13

Image 35
Contents Tier 2/3 Towable Generators Trailer and Skid Mounted California Proposition 65 Warning Table of Contents Ii Table of Contents MN2417 Read This Manual Thoroughly Section Product Safety InformationOperation Statements Precaution Statements Used In This ManualProperty On next MN2417 Product Safety Information Operation Statements Burn Statements Installation Statements Installation Statements Maintenance Statements Product Safety Information MN2417 Labor Parts Limited WarrantyGeneral Information MN2417 Section Receiving & Installation Generator Mounting Skid Fuel Connections InstallationHot Exhaust Gasses Protection Standby Power RatingsPrime Power Ratings Receptacle Panel Single Phase Single Phase ConnectionsGeneral Wiring Considerations Three Phase ConnectionsTransfer Switch Considerations Battery Charger ConsiderationsFrame Ground Connection Battery Installation Post Installation Checks Recommended Engine Oil and Battery TypeOil & Battery Recommendations Post Installation Checks Tow Vehicle Tow Hitch Capacity Towing the GeneratorSelecting the Proper Towing Equipment Towing Heavy Trailer Loads Trailer Component Identification Lug Nut Tightening Specifications Page Receptacle Panel Load Connections, see Figure Three/Single Phase OperationOperator Control Panel Components Voltage Reconnect and AdjustmentAuto Start Procedure Manual Start ProcedureManual Stop Procedure Digital Engine Controller Description EM0046A21 MRS17 Alarm & Warning Conditions Measurement Menu OFF Mode MAN Mode AUT ModeECU Alarm List Adjustment MenuAlarm List Possible Warnings Sensor fail FLS see TableShut down SD see Table Binary outputs Inputs and OutputsBinary Inputs Set points Basic Setpoints Analog Inputs10 Engine Setpoints Stabil Time11 Engine Protect Setpoints 10Engine Setpoints12 Generator Protect Setpoints 14 IOM/PTM Module Setpoints 13 Sensor Spec Setpoints+ D+ Jdic Engine GeneralTroubleshooting Guide Problems and SolutionsLoad too large for unit 1Troubleshooting GuideTroubleshooting and Maintenance MN2417 Part number Appendix a Wiring DiagramsFigure A-1 TS25 Connection Diagram Figure A-2 TS25 Connection Diagram Figure A-3 TS25 Connection Diagram Figure A-4 TS25 Connection Diagram Figure A-5 TS25 Connection Diagram Figure A-6 TS25 Connection Diagram Figure A-7 TS35 Connection Diagram Figure A-8 TS35 Connection Diagram Figure A-9 TS35 Connection Diagram Figure A-10 TS35 Connection Diagram Figure A-11 TS35 Connection Diagram Figure A-12 TS35 Connection Diagram Figure A-13 TS35 Power Connection Diagram Figure A-14 TS60 Connection Diagram Figure A-15 TS60 Connection Diagram Figure A-16 TS60 Connection Diagram Figure A-17 TS60 Connection Diagram Figure A-18 TS60 Connection Diagram Figure A-19 TS60 Connection Diagram Figure A-20 TS60 Connection Diagram Figure A-21 TS80 Connection Diagram Figure A-22 TS80 Connection Diagram Figure A-23 TS80 Connection Diagram Figure A-24 TS80 Connection Diagram Figure A-25 TS80 Connection Diagram Figure A-26 TS80 Connection Diagram Figure A-27 TS80 Connection Diagram Figure A-28 TS80 Connection Diagram Figure A-29 TS80 Connection Diagram Figure A-30 TS80 Connection Diagram Figure A-31 TS400 Connection Diagram Figure A-32 TS400 Connection Diagram Figure A-33 TS400 Connection Diagram Figure A-34 TS400 Connection Diagram Figure A-35 TS400 Connection Diagram Figure A-36 TS400 Connection Diagram Figure A-37 TS400 Connection Diagram Figure A-38 TS400 Connection Diagram Figure A-39 TS400 Connection Diagram Baldor District Offices Baldor Electric Company