Baldor TS25, TS45, TS60, TS400, TS80, TS175, TS130, TS35 manual Analog Inputs, Set points Basic Setpoints

Page 36

Analog Inputs Three analog inputs for resistive sensor 0 to 2400 ohms measuring are available on IL controller. Use LiteEdit software to modify configuration.

The Analog inputs values assignment (AI1 = Oil press, AI2 = Water temp, AI3 = Fuel level) is fix. It is possible to configure on each Analog input:

SReading from IL Analog inputs or from Engine Control Unit via CAN bus (J1939)

SSensor characteristics − from the list,

SValue dimension (e.g. psi − bars, °F − °C, % − l)

SNumber of decimal points (0, 1, 2, ...).

Note: Corresponding Analog input terminal is dead when reading is switched to ECU.

All values from ECU shall show ####, but no alarm is displayed when CAN communication is interrupted.

Warning and shut−down limits are adjusted in Engine protection group.

 

Table 4-8 Analog Inputs

 

 

 

AI1 Oil press

 

Oil pressure analog input. Default VDO sensor in range 0 to 145 psi.

AI2 Water temp

 

Water temperature analog input. Default VDO sensor in range 32 to 212°F

 

 

 

AI3 Fuel level

 

Fuel level analog input. Default VDO sensor 0−180R = 0−100%.

Set points

Table 4-9 Basic Setpoints

 

 

EnterPassword

Password is a four−digit number. Password enables change of relevant

 

protected set points Use or keys to set and ENTER key to enter the

 

password.

 

 

ChangePassword

Use or keys to set and ENTER key to change the password.

Gen−set name

User defined name, used for InteliLite identification at remote phone or

 

mobile connection. Gen−set name is max 14 characters long and have to

 

be entered using LiteEdit software.

 

 

Nomin power(3ph)

Nominal power of the generator in three phases connection.

 

Step: 1 kW; Range: 1 − 3000 kW

 

 

Nomin power(1ph)

Nominal power of the generator in single−phase connection.

 

Step: 1 kW; Range: 1 − 3000 kW

 

 

CT Ratio

Gen−set phases current transformers ratio.

 

Step: 1 A; Range: 1 − 5000 A / 5A

 

 

PT ratio

Gen−set potential transformers ratio.

 

Step: 0,1 V / V; Range: 0,1 − 500,0 V / V

 

 

Nominal freq

Nominal generator frequency (usually 50 or 60 Hz )

 

Step: 1Hz; Range: 45 − 65 Hz

 

 

Gear teeth

Number of teeth on the engine gear for the pick−up. Set to zero, if no

 

pick−up is used. Engine speed is counted from the generator frequency.

 

Step: 1; Range: 0 − 500

 

Note: Generator frequency can be used only when generator voltage

 

(min 5V) is present before reaching of the firing speed

 

(Starting RPM) after start.

Nominal RPM

Nominal engine speed. Step: 1RPM; Range: 100 − 4000 RPM.

FLTRESGOTOMAN

DISABLED: Controller stays in AUT mode after Fault reset .

 

ENABLED: Automatic switch from AUT (or TEST) to MAN mode after

 

Fault reset to avoid automatic engine start. This function is active for Shut

 

down protection only.

 

 

DispBackLightTO

Timeout after which the display backlight is switched off.

 

Step: 1 min Range: 0 − 60 min

 

Default value: 0 = the display lights all the time

 

 

Mode IL [ OFF, MAN, AUT ]

Equivalent to Controller mode changes by MODE" or MODEA buttons.

 

Note: Controller Mode change can be separately password protected.

 

 

RS232 mode

Communication protocol switch.

[Standard/Modbus ]

Standard: LiteEdit communication protocol. Modbus: Modbus protocol.

 

Note: For detail description see chapter Modbus protocol.

 

 

Num rings AA

Number of rings prior to open modem connection. Step: 1; Range: 1 − 30

 

Note: NumberRings AA change is not activated immediately. It is activated

 

after controller is switched on or when modem is connected to controller.

4-14 Operation

MN2417

Image 36
Contents Tier 2/3 Towable Generators Trailer and Skid Mounted California Proposition 65 Warning Table of Contents Ii Table of Contents MN2417 Section Product Safety Information Read This Manual ThoroughlyPrecaution Statements Used In This Manual PropertyOperation Statements On next MN2417 Product Safety Information Operation Statements Burn Statements Installation Statements Installation Statements Maintenance Statements Product Safety Information MN2417 Limited Warranty Labor PartsGeneral Information MN2417 Section Receiving & Installation Generator Mounting Skid Installation Hot Exhaust GassesFuel Connections Standby Power Ratings Prime Power RatingsProtection Single Phase Connections Receptacle Panel Single PhaseThree Phase Connections Transfer Switch ConsiderationsBattery Charger Considerations General Wiring ConsiderationsFrame Ground Connection Battery Installation Recommended Engine Oil and Battery Type Oil & Battery RecommendationsPost Installation Checks Post Installation Checks Towing the Generator Selecting the Proper Towing EquipmentTow Vehicle Tow Hitch Capacity Towing Heavy Trailer Loads Trailer Component Identification Lug Nut Tightening Specifications Page Three/Single Phase Operation Receptacle Panel Load Connections, see FigureVoltage Reconnect and Adjustment Operator Control Panel ComponentsManual Start Procedure Manual Stop ProcedureAuto Start Procedure Alarm & Warning Conditions Digital Engine Controller Description EM0046A21 MRS17OFF Mode MAN ModeAUT Mode Measurement MenuAdjustment Menu Alarm ListECU Alarm List Sensor fail FLS see Table Shut down SD see TablePossible Warnings Inputs and Outputs Binary InputsBinary outputs Analog Inputs Set points Basic SetpointsStabil Time 10 Engine Setpoints10Engine Setpoints 11 Engine Protect Setpoints12 Generator Protect Setpoints 13 Sensor Spec Setpoints 14 IOM/PTM Module Setpoints+ D+ Jdic General EngineProblems and Solutions Troubleshooting Guide1Troubleshooting Guide Load too large for unitTroubleshooting and Maintenance MN2417 Appendix a Wiring Diagrams Part numberFigure A-1 TS25 Connection Diagram Figure A-2 TS25 Connection Diagram Figure A-3 TS25 Connection Diagram Figure A-4 TS25 Connection Diagram Figure A-5 TS25 Connection Diagram Figure A-6 TS25 Connection Diagram Figure A-7 TS35 Connection Diagram Figure A-8 TS35 Connection Diagram Figure A-9 TS35 Connection Diagram Figure A-10 TS35 Connection Diagram Figure A-11 TS35 Connection Diagram Figure A-12 TS35 Connection Diagram Figure A-13 TS35 Power Connection Diagram Figure A-14 TS60 Connection Diagram Figure A-15 TS60 Connection Diagram Figure A-16 TS60 Connection Diagram Figure A-17 TS60 Connection Diagram Figure A-18 TS60 Connection Diagram Figure A-19 TS60 Connection Diagram Figure A-20 TS60 Connection Diagram Figure A-21 TS80 Connection Diagram Figure A-22 TS80 Connection Diagram Figure A-23 TS80 Connection Diagram Figure A-24 TS80 Connection Diagram Figure A-25 TS80 Connection Diagram Figure A-26 TS80 Connection Diagram Figure A-27 TS80 Connection Diagram Figure A-28 TS80 Connection Diagram Figure A-29 TS80 Connection Diagram Figure A-30 TS80 Connection Diagram Figure A-31 TS400 Connection Diagram Figure A-32 TS400 Connection Diagram Figure A-33 TS400 Connection Diagram Figure A-34 TS400 Connection Diagram Figure A-35 TS400 Connection Diagram Figure A-36 TS400 Connection Diagram Figure A-37 TS400 Connection Diagram Figure A-38 TS400 Connection Diagram Figure A-39 TS400 Connection Diagram Baldor District Offices Baldor Electric Company