Line Fusing and Wire Size
You must incorporate over current protection for the incoming AC power with the rating shown here.
UL approval for operation with the circuit breakers identified in the table below is pending. At present, fuses shown must be used for installation to meet UL.
| Recommended |
| Fuse |
| Miniature Circuit Breaker | ||
Drive Model | Minimum AC/PE | Fuse Class & Action | Bussman | Ferraz- | Allen Bradley | Square D | |
| Line Wire Gauge | ||||||
| Shawmut | ||||||
|
|
|
|
|
| ||
|
| RK1 | A2D6R | 60124 | |||
EP202 | 16 AWG | RK1 | A2K6R | 6 A, 1 pole | 6 A. 1 pole | ||
|
| ||||||
|
|
|
|
| |||
ISO 1,5 |
|
|
|
|
| ||
CC | ATDR6 | 60158 | |||||
| |||||||
|
| ||||||
|
|
|
|
| 6 A, 2 pole | 6 A, 2 pole | |
|
| CC | ATMR6 | ||||
|
|
|
| ||||
|
|
|
|
|
|
| |
|
| RK1 |
| A2D10R | 60127 | ||
EP204 | 16 AWG | RK1 | A2K10R | 10 A, 1 pole | 10 A, 1 pole | ||
|
| ||||||
|
|
|
|
| |||
ISO 1,5 |
|
|
|
|
| ||
CC | ATDR10 | 60161 | |||||
| |||||||
|
| ||||||
|
|
|
|
| 10 A, 2 pole | 10 A, 2 pole | |
|
| CC | ATMR10 | ||||
|
|
|
| ||||
|
|
|
|
|
|
| |
|
| RK1 |
| A2D15R | 60129 | ||
EP206 | 14 AWG | RK1 | A2K15R | 15 A, 1 pole | 15 A, 1 pole | ||
|
| ||||||
|
|
|
|
| |||
ISO 2,5 |
|
|
|
|
| ||
CC | ATDR15 | 60263 | |||||
| |||||||
|
| ||||||
|
|
|
|
| 15 A, 2 pole | 15 A, 2 pole | |
|
| CC | ATMR15 | ||||
|
|
|
| ||||
|
|
|
|
|
|
|
Use copper conductors only. Conductors must be rated 75°C or higher, preferably 90°C.
The Protective Earth (PE) wire connection is mandatory for human safety and proper operation. This connection must not be fused or interrupted by any means. Failure to follow proper PE wiring can cause death or serious injury.
.
Drive Model | Input Voltage | Frequency | Input Current (Amps RMS) at | Inrush Current | |
(Vac) | (Hz) | Full Drive Output Current | (Amps) | ||
| |||||
EP202 |
|
| 5.0 | 40 (5 ms) | |
|
|
|
|
| |
EP204 | 240 / 1 Ø | 47 - 63 | 8.5 | 65 (5 ms) | |
|
|
|
|
| |
EP206 |
|
| 12.0 | 100 (5 ms) | |
|
|
|
|
|
This inrush current specification assumes the drive has been powered off for at least 8 minutes at 40ºC (104ºF) ambient or 5 minutes at 25ºC (77ºF) ambient. If this amount of time has not elapsed since power off, the inrush current will be higher.