Final Installation

Now that you have completed Configuration you are ready to connect the SNMP Solo to your UPS and to the network. Follow these steps to complete the installation:

1.Turn DIP switch 1 on the SNMP Solo from the DOWN (ON) position to the UP (OFF) position.

2.Disconnect the configuration cable from the SNMP Solo adapter and the terminal or PC. Store this cable for future use.

3.Disconnect the SNMP Solo from the power supply.

4.Locate the cable labled “73743”. This is the UPS interface cable. Place the SNMP Solo close enough to the UPS so the UPS interface cable can connect the SNMP Solo’s serial port and the UPS’s serial port.

5.Connect the labelled end of the UPS interface cable to the SNMP Solo’s serial port. Connect the other end to the UPS’s serial port.

6.Connect the SNMP Solo to the Ethernet cable—either UTP or BNC.

7.Reconnect the SNMP Solo to the power supply.

Verify the SNMP Solo Operation

After you complete all configuration settings and connect the SNMP Solo to the network, check the LINK status.

LED Status After Power Up

At first, green and red LEDs do not light.

Green LED begins to pulse randomly, showing network activity.

Five to ten seconds after power up, the red LED flashes rapidly; this indicates that the SNMP Solo is determining which UPS model is connected to your system.

After SNMP Solo determines your UPS model, the red LED turns off.

The red LED pulses once whenever the SNMP

Solo detects a communication failure.

Final Installation

23

Image 29
Contents Snmp Solo Limited Warranty FCC Compliance Governing LawConventions Used In This Guide TrademarksTable of Contents Appendix Introduction Snmp Solo FeaturesExample Network With Snmp Solo Snmp Solo Package Snmp Solo Package ContentsStatus LEDs Two 3.5 Diskettes Configuration CablePower Supply UPS Interface Cable System Requirements System Requirements Initial Installation Initial Installation Hardware adapter prior to configuring the device ConfigurationIP address Set IP And Gateway Addresses And MIB System GroupTripp Lite Configuration Access Controls Set Access ControlsSet Trap Receivers Trap Receivers Additional Setup Screen Additional Setup ScreenDisplay Settings To Save and Exit Reset Configuration to DefaultTelnet options TelNet OptionsExit Without Saving Upload FirmwareVerify the Snmp Solo Operation Final InstallationEstablish Network Communications General Network Management Stations Configuring the NMSPoll the Device OIDs From the Test Connectivity box Add Snmp Solo Object to the Management Map SunConnect SunNet ManagerPoll the Device OIDs Reference AppendixCommunities IP AddressesClass Value of First Network ID Host ID Number Subnetting and Subnet MasksRouting and Filtering GatewaysAgent GlossaryOID Plugged into their respective ports TroubleshootingComputer System Placing a Technical Support Call773 Technical SupportReference Worksheet