Initial Installation
This section describes the installation of the SNMP Solo adapter when you connect it to the UPS and the network. (Refer to the Configuration section for network communications’ setup.) For configuration, connect the SNMP Solo temporarily to a PC with a terminal emulation package or to a dumb terminal. The following steps guide you in connecting the SNMP Solo to the network and UPS.
1.Install the UPS.
2.Adjust the DIP switches on the SNMP Solo for Configuration. Switch 1 is ON when down; switch 2 is OFF when up.
3.Temporarily, connect the SNMP Solo adapter to a dumb terminal or to a PC with the terminal emulation package.
a)Using the configuration cable, connect the end of the cabled labeled
b)Connect the other end into the SNMP Solo’s serial port.
4.Configure the communications settings.
a)Use the following settings to configure the dumb terminal or PC.
Baud rate ! | 9600 | Flow Control Xon/XOFF |
| ||
Data bits | ! | 8 | Handshaking | ! | None |
Stop bit | ! | 1 | Terminal Type:! | ANSI (VT100) | |
Parity | ! | None | Local Echo | ! | Off |