Sun Microsystems 96257 manual Electrostatic Discharge Precautions

Page 16

Strictly Comply With Caution and Warning Messages

To prevent injury and equipment damage, comply with all caution and warning messages in this document. Also employ any and all other precautions which you deem necessary for safe operation of equipment in your specific operating environment.

Carefully Follow Procedural Steps

Always complete procedural steps in listed order. Performing steps out of order can ex- pose you to potentially hazardous or lethal conditions.

Protect Yourself From Moving Parts

Restrict loose clothing and long hair to avoid becoming entangled in moving parts such as fans, impellers, and blowers.

Promptly Reinstall Covers and Doors

After completing service procedures, promptly reinstall cabinet covers, and close and lock cabinet doors to maintain proper cabinet airflow, prevent overheating, and restrict accessi- bility to energized FRUs.

Miscellaneous Safety Precautions

To prevent tipovers, never tilt a cabinet beyond a 15-degree angle (e.g., when ascending or descending ramps). Use caution when working near open floor tiles. Use good house- keeping practices to avoid fire hazards and to reduce the potential for mishaps.

Electrostatic Discharge Precautions

Electrostatic discharge (ESD)-sensitive components must always be handled under pro- tected conditions, and ESD-preventive equipment must be used when servicing equip- ment. Employees who handles ESD-sensitive parts must be aware of the damage that ESD can cause, and must take the following precautions to prevent it.

Use ESD-Preventive Equipment

Always use Field Service Grounding Kit P/N 4711 when installing or servicing Sun equip- ment. Always use a conductive wrist strap and antistatic work mat, and ensure those are grounded to a jack or unpainted metal on the cabinet frame when working.

Regularly Check and Clean ESD-Preventive Equipment

Regularly (at least monthly during frequent use) verify the resistance of wrist-strap grounding cords to be between 0.8M ohm (Ω) and 1.2M ohm (Ω), and work mat cords to be less than 1.2M ohm (Ω); replace damaged cords or any that do not meet these specifi- cations. Regularly (at least monthly during frequent use) clean antistatic work mats; ACL Conductive Cleaner is preferred for this purpose since it leaves no residue, but isopropyl alcohol or a mild detergent and water solution can also be used.

Remove Conductive Personal Items

Before beginning service procedures inside a cabinet, remove all conductive metal ob- jects from your person including rings, watches, necklaces, and badge chains.

Handle ESD-Sensitive Components Carefully

Keep circuit cards, ASICs, and other ESD-sensitive components away from ESD sources and extraneous electrical currents. Keep parts in ESD-protective packaging until installa- tion, and store removed ESD-sensitive parts in protective packaging.

96257

Sun Confidential: Internal Only

xvi

 

Revision A

 

Image 16
Contents StorageTek Page Virtual Tape Storage Subsystem Vtss Export Destination Control Statement Disclaimer of Warranties and Limitation of LiabilityProprietary Information Statement Revision a SeptemberRevision History / Summary of Changes SAPContents 96257 Sun Confidential Internal Only Vii Revision a Implementation Planning Site Readiness Planning96257 Sun Confidential Internal Only Viii Revision a Figures Tables Class 1 Laser Product Notice Warranty NoticeCabling Notice Product Safety Standards Hazardous Materials HandlingStandards Conformance Electromagnetic CompatibilityPage Internal Code License Statement DefinitionsSafety / Fiber Optic / ESD Precautions Safety PrecautionsElectrostatic Discharge Precautions Strictly Comply With Caution and Warning MessagesFiber Optic Component Handling Precautions Protect Your EyesOptimizing Content For Electronic Viewing About This GuideProduct Overview Intended AudienceNotational and Typographic Conventions Alert MessagesExamples Description of Convention Where to Find Additional Information Reference DocumentsVSM Engineering Website Colophon SE Support ToolsPlanning and Implementation Overview System Assurance Process FlowCreating Planning Teams Planning / Readiness / Implementation Timelines Page Configuration Planning Overview Configuration PlanningKey High-Level Activities Key Sub-Tasks Key Participants Defining Customer Requirements VSM Quick Tool Tool Selection ScreenVSM Sizer Tool VSM Sizer ToolMVC Sizer Tool MVC Sizer ToolMVC Migration Tool MVC Migration ToolCDS Sizer Tool CDS Sizer ToolVtss Configuration Planning VSM5-VTSS Physical CharacteristicsVSM5-VTSS Physical Characteristics VSM5-VTSS Environmental RequirementsModel Numbers / Configurations / Capacities VSM5-VTSS Model Numbers / Configurations / CapacitiesPrerequisites for Ficon Connectivity Additional Prerequisites for Ficon RTDsNative Ficon Attachment Native Ficon Attachment OptionsFicon Cabling Short-Wave vs. Long-Wave Connections Ficon Data Transfer RatesSingle-Mode vs. Multi-Mode Ficon Cabling VCF3 Ficon Card Configuration Examples Ficon Channel Card Configuration 4 VCF CardsFicon Channel Card Configuration 6 VCF Cards Fibre Channel Cables Available Lengths Fibre Channel Cables Available LengthsDescription / Length Part Number AC Source Power Specifications and Connectors DC Power Supply Voltage Ripple SpecificationsVSM5-VTSS AC Source Power Specifications and Connectors VSM5-VTSS DC Power Supply Voltage RipplePower Requirements Implementation Planning Implementation Planning OverviewPage Site Readiness Planning Site Readiness Planning OverviewSite Evaluation External Considerations Site Evaluation Internal ConsiderationsStructural Dimensions and Obstructions Transfering Equipment Point-to-PointData Center Safety Emergency Power ControlSite Power Distribution Systems Site Electrical Power Distribution SystemSource Power Requirements for VSM5 Equipment Source Power Voltage Range Frequency Range HzElectrostatic Discharge Hvac RequirementsFloor Construction Requirements Environmental Requirements and HazardsFloor Loading Requirements Site Evaluation Internal Considerations VSM5-VTSS Floor Loading SpecificationsVSM5-VTSS Cabinet Superimposed Floor Loading Example VSM5-VTSS Cabinet Weight Distribution and Leveler Locations Raised Flooring Horizontal Force ChartVSM5-VTSS Cabinet Dimensions for Physical Space Planning Physical Space RequirementsPage Specifications and Additional Information Motherboard and FRU Interconnections Side Motherboard and FRU Interconnections Side Power Safety Grounding Diagram Side Figure A-3. VSM5-VTSS Power Safety Grounding Diagram SideFigure A-4. VSM5-VTSS Power Safety Grounding Diagram Side Power System Diagram Figure A-5. VSM5-VTSS Power System DiagramData Paths and Interfaces Figure A-6. VSM5-VTSS Data Paths and InterfacesFiber Optic Cable Specifications VShell Command ReferenceTable A-1. Fiber Optic Cable Specifications Table A-2. VShell Command ReferenceSample Iocp Gen for Ficon Configuration Figure A-7. Sample Iocp Gen for Ficon ConfigurationVirtual Tape Drive Mapping and Host Addressing Sequential Device Parameters NumbersFRU Identifiers Table A-4. VSM5-VTSS FRU IdentifiersHex Decimal Unit.Tray.Slot Logic Motherboard and Cards ISP1Card Cage Impellers Hex Decimal Unit.Tray.Slot Logic Power Supply FansPhysical Array Disk Drive Tray Hex Decimal Unit.Tray.Slot Physical Array Disk Drive Tray DA.5.DRV0 Array Drive Module Status Descriptions Figure A-8. Array Drive Module States and RelationshipsTable A-5. Array Drive Module Status Descriptions Media Acceptance Test MAT PartitionSpares Partition Unavailable PartitionPage Ficon Channel Extension Guidelines Definition of Terms General Channel Extension Considerations Understand Channel Extension Performance LimitationsInteroperability Testing Placement of Extension EquipmentFicon Topologies Ficon Channel Extension Sample Configurations Channel Director/Switch ExtenderTape Silo HostFigure B-4. VTSS-to-RTD Channel Extension Direct Attachment McData/CNT Channel Extension Interoperability McData/CNT Channel Extension InteroperabilityISL Failover Is Supported Only in Shuttle Mode Cisco Systems Channel Extension Interoperability Page Glossary Sun Confidential Internal Only 96257 Revision a 96257 Sun Confidential Internal Only Revision a Data compression. See compression 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Functional device. See functional volume Technology with ISO 96257 Sun Confidential Internal Only Revision a MLC. Machine-Level Control Part number Service Delivery Platform SDP. a Sun StorageTek 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Forms and Reference Notes Host System Configuration Information Customer Personnel Contacts Sun StorageTek / QSP Personnel Contacts Planning Worksheet 1 Planning Worksheet 2 Planning Worksheet 3 Planning Worksheet 4 Planning Worksheet 5 Software Information Hardware Information Tape Devices Hardware Information Switches / Routers Hardware Information SDP and Modem Devices Account Account Account Account Account Page Headquarters