Site Evaluation – Internal Considerations

Transfering Equipment Point-to-Point

Site conditions must be verified to ensure all VSM5 system equipment can be safely trans- ported between the delivery dock, staging area, and data center without encountering di- mensional restrictions, obstructions, or safety hazards, or exceeding rated capacities of lifting and loading equipment, flooring, or other infrastructure. Conditions that must to be verified are described below.

Structural Dimensions and Obstructions

Dimensions of elevators, doors, hallways, etc. must be sufficient to allow unimpeded tran- sit of VSM5-VTSS cabinets (in shipping containers, where appropriate) from the delivery dock to the data center installation location. See “VSM5-VTSS Physical Characteristics” on page 2-33for VTSS cabinet-dimension details.

Elevator Lifting Capacities

Any elevators that will be used to transfer VSM5-VTSS cabinets must have a certified load rating of at least 1000 kg (2200 lbs.). This provides adequate capacity to lift the heaviest packaged, fully-popuated VTSS cabinet (roughly 480 kg/1056 lbs. with 64 array drives), a pallet jack (allow 100 kg/220 lbs.), and two persons (allow 200 kg/440 lbs.). See “VSM5- VTSS Physical Characteristics” on page 2-33for additional cabinet-weight details.

Floor-Load Ratings

Solid floors, raised floors, and ramps located along the transfer path for VSM5-VTSS cab- inets must be able to withstand concentrated and rolling loads generated by the weight of a populated cabinet, equipment used to lift a cabinet (e.g., a pallet jack), and personnel who are moving the cabinet from point to point.

Raised floor panels located along a transfer path must be able to resist a concentrated load of 454 kg (1000 lbs.) and a rolling load of 181 kg (400 lbs.) anywhere on the panel, with a maximum deflection of 2 mm (0.08 in.). Raised floor pedestals must be able to re- sist an axial load of 2268 kg (5000 lbs.). See “Floor Loading Requirements” on page 4-52for additional floor-loading details.

When being moved from one location to another, a VSM5-VTSS cabinet generates rough- ly twice the floor load as in a static state. Using 19 mm (0.75 in.) plywood along a transfer path reduces the rolling load produced by a cabinet.

Ramp Inclines

To prevent VSM5-VTSS cabinets from tipping on ramps while being moved from point to point, the site engineer or facilities manager must verify the incline angle of all ramps in the transfer path. Inclines cannot exceed 10 degrees (176 mm/m; 2.12 in./ft.).

96257

Sun Confidential: Internal Only

4-47

 

Revision A

 

Image 47
Contents StorageTek Page Virtual Tape Storage Subsystem Vtss Revision a September Export Destination Control StatementDisclaimer of Warranties and Limitation of Liability Proprietary Information StatementSAP Revision History / Summary of ChangesContents Implementation Planning Site Readiness Planning 96257 Sun Confidential Internal Only Vii Revision a96257 Sun Confidential Internal Only Viii Revision a Figures Tables Cabling Notice Warranty NoticeClass 1 Laser Product Notice Electromagnetic Compatibility Product Safety StandardsHazardous Materials Handling Standards ConformancePage Definitions Internal Code License StatementSafety Precautions Safety / Fiber Optic / ESD PrecautionsStrictly Comply With Caution and Warning Messages Electrostatic Discharge PrecautionsProtect Your Eyes Fiber Optic Component Handling PrecautionsIntended Audience Optimizing Content For Electronic ViewingAbout This Guide Product OverviewExamples Description of Convention Alert MessagesNotational and Typographic Conventions Reference Documents Where to Find Additional InformationVSM Engineering Website SE Support Tools ColophonSystem Assurance Process Flow Planning and Implementation OverviewCreating Planning Teams Planning / Readiness / Implementation Timelines Page Key High-Level Activities Key Sub-Tasks Key Participants Configuration PlanningConfiguration Planning Overview VSM Quick Tool Tool Selection Screen Defining Customer RequirementsVSM Sizer Tool VSM Sizer ToolMVC Sizer Tool MVC Sizer ToolMVC Migration Tool MVC Migration ToolCDS Sizer Tool CDS Sizer ToolVSM5-VTSS Environmental Requirements Vtss Configuration PlanningVSM5-VTSS Physical Characteristics VSM5-VTSS Physical CharacteristicsVSM5-VTSS Model Numbers / Configurations / Capacities Model Numbers / Configurations / CapacitiesAdditional Prerequisites for Ficon RTDs Prerequisites for Ficon ConnectivityNative Ficon Attachment Options Native Ficon AttachmentSingle-Mode vs. Multi-Mode Ficon Cabling Ficon Data Transfer RatesFicon Cabling Short-Wave vs. Long-Wave Connections Ficon Channel Card Configuration 4 VCF Cards VCF3 Ficon Card Configuration ExamplesFicon Channel Card Configuration 6 VCF Cards Description / Length Part Number Fibre Channel Cables Available LengthsFibre Channel Cables Available Lengths VSM5-VTSS DC Power Supply Voltage Ripple AC Source Power Specifications and ConnectorsDC Power Supply Voltage Ripple Specifications VSM5-VTSS AC Source Power Specifications and ConnectorsPower Requirements Implementation Planning Overview Implementation PlanningPage Site Readiness Planning Overview Site Readiness PlanningSite Evaluation Internal Considerations Site Evaluation External ConsiderationsTransfering Equipment Point-to-Point Structural Dimensions and ObstructionsEmergency Power Control Data Center SafetySite Electrical Power Distribution System Site Power Distribution SystemsSource Power Voltage Range Frequency Range Hz Source Power Requirements for VSM5 EquipmentHvac Requirements Electrostatic DischargeFloor Loading Requirements Environmental Requirements and HazardsFloor Construction Requirements VSM5-VTSS Cabinet Superimposed Floor Loading Example VSM5-VTSS Floor Loading SpecificationsSite Evaluation Internal Considerations Raised Flooring Horizontal Force Chart VSM5-VTSS Cabinet Weight Distribution and Leveler LocationsPhysical Space Requirements VSM5-VTSS Cabinet Dimensions for Physical Space PlanningPage Specifications and Additional Information Motherboard and FRU Interconnections Side Motherboard and FRU Interconnections Side Figure A-3. VSM5-VTSS Power Safety Grounding Diagram Side Power Safety Grounding Diagram SideFigure A-4. VSM5-VTSS Power Safety Grounding Diagram Side Figure A-5. VSM5-VTSS Power System Diagram Power System DiagramFigure A-6. VSM5-VTSS Data Paths and Interfaces Data Paths and InterfacesTable A-2. VShell Command Reference Fiber Optic Cable SpecificationsVShell Command Reference Table A-1. Fiber Optic Cable SpecificationsFigure A-7. Sample Iocp Gen for Ficon Configuration Sample Iocp Gen for Ficon ConfigurationSequential Device Parameters Numbers Virtual Tape Drive Mapping and Host AddressingTable A-4. VSM5-VTSS FRU Identifiers FRU IdentifiersISP1 Hex Decimal Unit.Tray.Slot Logic Motherboard and CardsPhysical Array Disk Drive Tray Hex Decimal Unit.Tray.Slot Logic Power Supply FansCard Cage Impellers Hex Decimal Unit.Tray.Slot Physical Array Disk Drive Tray DA.5.DRV0 Figure A-8. Array Drive Module States and Relationships Array Drive Module Status DescriptionsUnavailable Partition Table A-5. Array Drive Module Status DescriptionsMedia Acceptance Test MAT Partition Spares PartitionPage Ficon Channel Extension Guidelines Definition of Terms Understand Channel Extension Performance Limitations General Channel Extension ConsiderationsFicon Topologies Placement of Extension EquipmentInteroperability Testing Host Ficon Channel Extension Sample ConfigurationsChannel Director/Switch Extender Tape SiloFigure B-4. VTSS-to-RTD Channel Extension Direct Attachment McData/CNT Channel Extension Interoperability McData/CNT Channel Extension InteroperabilityISL Failover Is Supported Only in Shuttle Mode Cisco Systems Channel Extension Interoperability Page Glossary Sun Confidential Internal Only 96257 Revision a 96257 Sun Confidential Internal Only Revision a Data compression. See compression 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Functional device. See functional volume Technology with ISO 96257 Sun Confidential Internal Only Revision a MLC. Machine-Level Control Part number Service Delivery Platform SDP. a Sun StorageTek 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Forms and Reference Notes Host System Configuration Information Customer Personnel Contacts Sun StorageTek / QSP Personnel Contacts Planning Worksheet 1 Planning Worksheet 2 Planning Worksheet 3 Planning Worksheet 4 Planning Worksheet 5 Software Information Hardware Information Tape Devices Hardware Information Switches / Routers Hardware Information SDP and Modem Devices Account Account Account Account Account Page Headquarters