Site Evaluation – Internal Considerations

Floor Loading Specifications and References

Table 4-3. VSM5-VTSS Floor Loading Specifications

 

 

 

 

Basic Floor Load*

 

Maximum Superimposed Floor Load #

730 kg/m2 (149 lbs./ft2)

 

485 kg/m2 (99 lbs./ft2)

Notes:

* Load over footprint surface area (7093.7 cm2/1099.5 in2) of an unpackaged VSM5-VTSS cabinet, with a maxi- mum weight of 445 kg/982 lbs., i.e., a VTSS with 64 array disk drives.

# Assumes minimum Z+Z axis dimension of 185.3 cm/73.0 in. (i.e., cabinet depth 77.1 cm/30.4 in. + front service clearance of 54.1 cm/21.3 in. + rear service clearance of 54.1 cm/21.3 in.), minimum X+X axis dimension of 104.9 cm/41.2 in. (i.e., cabinet width 92.1 cm/36.3 in. + left clearance of 6.4 cm/2.5 in. + right clearance of 6.4 cm/2.5 in.).

Table 4-4. VSM5-VTSS Cabinet Superimposed Floor Loading Example

Total Front + Rear Service Clearance (Z+Z) / 2

Notes:

 

 

Total Left + Right Side Clearance (X+X) / 2

 

 

 

 

 

 

 

 

7.6 cm

61.0 cm

91.4 cm

121.9 cm

152.4 cm

 

(3.0 in.)

(24.0 in.)

(36.0 in.)

(48.0 in.)

(60.0 in.)

 

 

 

 

 

 

55.9 cm

443 kg/m2

340 k.g/m2

308 kg/m2

285 kg/m2

268 kg/m2

(22.0 in)

(91 lb./ft2)

(70 lb/ft2)

(63 lb./ft2)

(58 lb./ft2)

(55 lb./ft2)

96.5 cm

374 kg/m2

295 k.g/m2

270 kg/m2

252 kg/m2

239 kg/m2

(38.0 in)

(77 lb./ft2)

(60 lb/ft2)

(55 lb./ft2)

(52 lb./ft2)

(49 lb./ft2)

116.8 cm

350 kg/m2

279 kg/m2

257 kg/m2

241 kg/m2

229 kg/m2

(46.0 in)

(72 lb./ft2)

(57 lb./ft2)

(53 lb./ft2)

(49 lb./ft2)

(47 lb./ft2)

137.2 cm

331 kg/m2

267 kg/m2

247 kg/m2

232 kg/m2

222 kg/m2

(54.0 in)

(68 lb./ft2)

(55 lb./ft2)

(51 lb./ft2)

(48 lb./ft2)

(45 lb./ft2)

157.5 cm

315 kg/m2

256 kg/m2

238 kg/m2

225 kg/m2

215 kg/m2

(62.0 in)

(64 lb./ft2)

(52 lb./ft2)

(49 lb./ft2)

(46 lb./ft2)

(44 lb./ft2)

See Figure 4-3 on page 4-53for the location and load of each VTSS cabinet support point.

Values assume 15 lb./ft2 (73 kg/m2) superimposed dead load over entire area for raised floor, cables, etc., and 15 lb./ft2 (73 kg/m2) live load for personnel and equipment in clearance areas between units.

Loading of adjacent floor areas must be considered when evaluating overall floor capacity.

To evaluate floor loading for other possible configurations, consult a structural engineer.

96257

Sun Confidential: Internal Only

4-53

 

Revision A

 

Image 53
Contents StorageTek Page Virtual Tape Storage Subsystem Vtss Disclaimer of Warranties and Limitation of Liability Export Destination Control StatementProprietary Information Statement Revision a SeptemberSAP Revision History / Summary of ChangesContents Implementation Planning Site Readiness Planning 96257 Sun Confidential Internal Only Vii Revision a96257 Sun Confidential Internal Only Viii Revision a Figures Tables Cabling Notice Warranty NoticeClass 1 Laser Product Notice Hazardous Materials Handling Product Safety StandardsStandards Conformance Electromagnetic CompatibilityPage Definitions Internal Code License StatementSafety Precautions Safety / Fiber Optic / ESD PrecautionsStrictly Comply With Caution and Warning Messages Electrostatic Discharge PrecautionsProtect Your Eyes Fiber Optic Component Handling PrecautionsAbout This Guide Optimizing Content For Electronic ViewingProduct Overview Intended AudienceExamples Description of Convention Alert MessagesNotational and Typographic Conventions Reference Documents Where to Find Additional InformationVSM Engineering Website SE Support Tools ColophonSystem Assurance Process Flow Planning and Implementation OverviewCreating Planning Teams Planning / Readiness / Implementation Timelines Page Key High-Level Activities Key Sub-Tasks Key Participants Configuration PlanningConfiguration Planning Overview VSM Quick Tool Tool Selection Screen Defining Customer RequirementsVSM Sizer Tool VSM Sizer ToolMVC Sizer Tool MVC Sizer ToolMVC Migration Tool MVC Migration ToolCDS Sizer Tool CDS Sizer ToolVSM5-VTSS Physical Characteristics Vtss Configuration PlanningVSM5-VTSS Physical Characteristics VSM5-VTSS Environmental RequirementsVSM5-VTSS Model Numbers / Configurations / Capacities Model Numbers / Configurations / CapacitiesAdditional Prerequisites for Ficon RTDs Prerequisites for Ficon ConnectivityNative Ficon Attachment Options Native Ficon AttachmentSingle-Mode vs. Multi-Mode Ficon Cabling Ficon Data Transfer RatesFicon Cabling Short-Wave vs. Long-Wave Connections Ficon Channel Card Configuration 4 VCF Cards VCF3 Ficon Card Configuration ExamplesFicon Channel Card Configuration 6 VCF Cards Description / Length Part Number Fibre Channel Cables Available LengthsFibre Channel Cables Available Lengths DC Power Supply Voltage Ripple Specifications AC Source Power Specifications and ConnectorsVSM5-VTSS AC Source Power Specifications and Connectors VSM5-VTSS DC Power Supply Voltage RipplePower Requirements Implementation Planning Overview Implementation PlanningPage Site Readiness Planning Overview Site Readiness PlanningSite Evaluation Internal Considerations Site Evaluation External ConsiderationsTransfering Equipment Point-to-Point Structural Dimensions and ObstructionsEmergency Power Control Data Center SafetySite Electrical Power Distribution System Site Power Distribution SystemsSource Power Voltage Range Frequency Range Hz Source Power Requirements for VSM5 EquipmentHvac Requirements Electrostatic DischargeFloor Loading Requirements Environmental Requirements and HazardsFloor Construction Requirements VSM5-VTSS Cabinet Superimposed Floor Loading Example VSM5-VTSS Floor Loading SpecificationsSite Evaluation Internal Considerations Raised Flooring Horizontal Force Chart VSM5-VTSS Cabinet Weight Distribution and Leveler LocationsPhysical Space Requirements VSM5-VTSS Cabinet Dimensions for Physical Space PlanningPage Specifications and Additional Information Motherboard and FRU Interconnections Side Motherboard and FRU Interconnections Side Figure A-3. VSM5-VTSS Power Safety Grounding Diagram Side Power Safety Grounding Diagram SideFigure A-4. VSM5-VTSS Power Safety Grounding Diagram Side Figure A-5. VSM5-VTSS Power System Diagram Power System DiagramFigure A-6. VSM5-VTSS Data Paths and Interfaces Data Paths and InterfacesVShell Command Reference Fiber Optic Cable SpecificationsTable A-1. Fiber Optic Cable Specifications Table A-2. VShell Command ReferenceFigure A-7. Sample Iocp Gen for Ficon Configuration Sample Iocp Gen for Ficon ConfigurationSequential Device Parameters Numbers Virtual Tape Drive Mapping and Host AddressingTable A-4. VSM5-VTSS FRU Identifiers FRU IdentifiersISP1 Hex Decimal Unit.Tray.Slot Logic Motherboard and CardsPhysical Array Disk Drive Tray Hex Decimal Unit.Tray.Slot Logic Power Supply FansCard Cage Impellers Hex Decimal Unit.Tray.Slot Physical Array Disk Drive Tray DA.5.DRV0 Figure A-8. Array Drive Module States and Relationships Array Drive Module Status DescriptionsMedia Acceptance Test MAT Partition Table A-5. Array Drive Module Status DescriptionsSpares Partition Unavailable PartitionPage Ficon Channel Extension Guidelines Definition of Terms Understand Channel Extension Performance Limitations General Channel Extension ConsiderationsFicon Topologies Placement of Extension EquipmentInteroperability Testing Channel Director/Switch Extender Ficon Channel Extension Sample ConfigurationsTape Silo HostFigure B-4. VTSS-to-RTD Channel Extension Direct Attachment McData/CNT Channel Extension Interoperability McData/CNT Channel Extension InteroperabilityISL Failover Is Supported Only in Shuttle Mode Cisco Systems Channel Extension Interoperability Page Glossary Sun Confidential Internal Only 96257 Revision a 96257 Sun Confidential Internal Only Revision a Data compression. See compression 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Functional device. See functional volume Technology with ISO 96257 Sun Confidential Internal Only Revision a MLC. Machine-Level Control Part number Service Delivery Platform SDP. a Sun StorageTek 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Forms and Reference Notes Host System Configuration Information Customer Personnel Contacts Sun StorageTek / QSP Personnel Contacts Planning Worksheet 1 Planning Worksheet 2 Planning Worksheet 3 Planning Worksheet 4 Planning Worksheet 5 Software Information Hardware Information Tape Devices Hardware Information Switches / Routers Hardware Information SDP and Modem Devices Account Account Account Account Account Page Headquarters