Site Evaluation – Internal Considerations

Site Power Distribution Systems

The following elements of the site power distribution system should be evaluated when planning an installation of VSM5 system equipment.

System Design

A properly installed power distribution system is required to ensure safe operation of VSM5 system equipment. Power should be supplied from a feeder separate from one used for lighting, air conditioning, and other electrical systems.

Atypical input power configuration, shown in Figure 4-1, is either a five-wire high-voltage or a four-wire low-voltage type, with three-phase service coming from a service entrance or separately derived source, and with overcurrent protection and suitable grounding. A three-phase, five-wire distribution system provides the greatest configuration flexibility, since it allows power to be provided to both three-phase and single-phase equipment.

Figure 4-1. Site Electrical Power Distribution System

Computer Room

Remotely Operated

Power Panel

Power Service Disconnect

Incoming Three-phase Power from service entrance or separately derived system with appropriate over-current protection and suitable ground

Ground Terminal Bar (bonded to enclosure) Same size as neutral

Neutral

 

 

 

 

 

Only valid at

 

 

 

 

 

 

 

 

 

 

service entrance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or separately

 

 

 

 

 

 

 

 

 

 

derived system

 

 

 

 

 

 

 

 

 

 

(transformer)

 

 

 

 

 

Ground

Service Entrance

Ground or Suitable

Building Ground

Note: Bounding of neutral and ground at other points is Illegal.

Ledgend:

Insulated Green Wire Ground

Phase Wires and Neutral

Neutral Bus

Circuit Breakers of

Appropriate Size

Branch Circuits

 

*For loads requiring a

 

neutral attach computer/data

 

120V * processing equipment only

 

Single

208/240V Phase

208/240V

Single

Phase

3-Phase

 

208/240V (4-wire)

Customer Supplied

3-Phase

Receptacles/Connectors-

(5-wire)

in Accordance with

Local Codes

A502_046

96257

Sun Confidential: Internal Only

4-49

 

Revision A

 

Image 49
Contents StorageTek Page Virtual Tape Storage Subsystem Vtss Disclaimer of Warranties and Limitation of Liability Export Destination Control StatementProprietary Information Statement Revision a SeptemberSAP Revision History / Summary of ChangesContents Implementation Planning Site Readiness Planning 96257 Sun Confidential Internal Only Vii Revision a96257 Sun Confidential Internal Only Viii Revision a Figures Tables Class 1 Laser Product Notice Warranty NoticeCabling Notice Hazardous Materials Handling Product Safety StandardsStandards Conformance Electromagnetic CompatibilityPage Definitions Internal Code License StatementSafety Precautions Safety / Fiber Optic / ESD PrecautionsStrictly Comply With Caution and Warning Messages Electrostatic Discharge PrecautionsProtect Your Eyes Fiber Optic Component Handling PrecautionsAbout This Guide Optimizing Content For Electronic ViewingProduct Overview Intended AudienceNotational and Typographic Conventions Alert MessagesExamples Description of Convention Reference Documents Where to Find Additional InformationVSM Engineering Website SE Support Tools ColophonSystem Assurance Process Flow Planning and Implementation OverviewCreating Planning Teams Planning / Readiness / Implementation Timelines Page Configuration Planning Overview Configuration PlanningKey High-Level Activities Key Sub-Tasks Key Participants VSM Quick Tool Tool Selection Screen Defining Customer RequirementsVSM Sizer Tool VSM Sizer ToolMVC Sizer Tool MVC Sizer ToolMVC Migration Tool MVC Migration ToolCDS Sizer Tool CDS Sizer ToolVSM5-VTSS Physical Characteristics Vtss Configuration PlanningVSM5-VTSS Physical Characteristics VSM5-VTSS Environmental RequirementsVSM5-VTSS Model Numbers / Configurations / Capacities Model Numbers / Configurations / CapacitiesAdditional Prerequisites for Ficon RTDs Prerequisites for Ficon ConnectivityNative Ficon Attachment Options Native Ficon AttachmentFicon Cabling Short-Wave vs. Long-Wave Connections Ficon Data Transfer RatesSingle-Mode vs. Multi-Mode Ficon Cabling Ficon Channel Card Configuration 4 VCF Cards VCF3 Ficon Card Configuration ExamplesFicon Channel Card Configuration 6 VCF Cards Fibre Channel Cables Available Lengths Fibre Channel Cables Available LengthsDescription / Length Part Number DC Power Supply Voltage Ripple Specifications AC Source Power Specifications and ConnectorsVSM5-VTSS AC Source Power Specifications and Connectors VSM5-VTSS DC Power Supply Voltage RipplePower Requirements Implementation Planning Overview Implementation PlanningPage Site Readiness Planning Overview Site Readiness PlanningSite Evaluation Internal Considerations Site Evaluation External ConsiderationsTransfering Equipment Point-to-Point Structural Dimensions and ObstructionsEmergency Power Control Data Center SafetySite Electrical Power Distribution System Site Power Distribution SystemsSource Power Voltage Range Frequency Range Hz Source Power Requirements for VSM5 EquipmentHvac Requirements Electrostatic DischargeFloor Construction Requirements Environmental Requirements and HazardsFloor Loading Requirements Site Evaluation Internal Considerations VSM5-VTSS Floor Loading SpecificationsVSM5-VTSS Cabinet Superimposed Floor Loading Example Raised Flooring Horizontal Force Chart VSM5-VTSS Cabinet Weight Distribution and Leveler LocationsPhysical Space Requirements VSM5-VTSS Cabinet Dimensions for Physical Space PlanningPage Specifications and Additional Information Motherboard and FRU Interconnections Side Motherboard and FRU Interconnections Side Figure A-3. VSM5-VTSS Power Safety Grounding Diagram Side Power Safety Grounding Diagram SideFigure A-4. VSM5-VTSS Power Safety Grounding Diagram Side Figure A-5. VSM5-VTSS Power System Diagram Power System DiagramFigure A-6. VSM5-VTSS Data Paths and Interfaces Data Paths and InterfacesVShell Command Reference Fiber Optic Cable SpecificationsTable A-1. Fiber Optic Cable Specifications Table A-2. VShell Command ReferenceFigure A-7. Sample Iocp Gen for Ficon Configuration Sample Iocp Gen for Ficon ConfigurationSequential Device Parameters Numbers Virtual Tape Drive Mapping and Host AddressingTable A-4. VSM5-VTSS FRU Identifiers FRU IdentifiersISP1 Hex Decimal Unit.Tray.Slot Logic Motherboard and CardsCard Cage Impellers Hex Decimal Unit.Tray.Slot Logic Power Supply FansPhysical Array Disk Drive Tray Hex Decimal Unit.Tray.Slot Physical Array Disk Drive Tray DA.5.DRV0 Figure A-8. Array Drive Module States and Relationships Array Drive Module Status DescriptionsMedia Acceptance Test MAT Partition Table A-5. Array Drive Module Status DescriptionsSpares Partition Unavailable PartitionPage Ficon Channel Extension Guidelines Definition of Terms Understand Channel Extension Performance Limitations General Channel Extension ConsiderationsInteroperability Testing Placement of Extension EquipmentFicon Topologies Channel Director/Switch Extender Ficon Channel Extension Sample ConfigurationsTape Silo HostFigure B-4. VTSS-to-RTD Channel Extension Direct Attachment McData/CNT Channel Extension Interoperability McData/CNT Channel Extension InteroperabilityISL Failover Is Supported Only in Shuttle Mode Cisco Systems Channel Extension Interoperability Page Glossary Sun Confidential Internal Only 96257 Revision a 96257 Sun Confidential Internal Only Revision a Data compression. See compression 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Functional device. See functional volume Technology with ISO 96257 Sun Confidential Internal Only Revision a MLC. Machine-Level Control Part number Service Delivery Platform SDP. a Sun StorageTek 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Forms and Reference Notes Host System Configuration Information Customer Personnel Contacts Sun StorageTek / QSP Personnel Contacts Planning Worksheet 1 Planning Worksheet 2 Planning Worksheet 3 Planning Worksheet 4 Planning Worksheet 5 Software Information Hardware Information Tape Devices Hardware Information Switches / Routers Hardware Information SDP and Modem Devices Account Account Account Account Account Page Headquarters