VTSS Configuration Planning

FICON Data Transfer Rates

The fastest native FICON channels are rated at 200 MB/sec., but actually can achieve a maximum data rate of only 170 MB/sec. under optimum conditions. In actual practice, FI- CON typically operates at 40-60 MB/sec. using the 32 KB block size commonly found in tape workloads.

VCF3 cards support 2 Gb link speeds; actual throughput speed is determined by many factors including block size, microcode level, etc.

FICON Cabling — Short-Wave vs. Long-Wave Connections

Currently, FICON channels send data via fiber-optic cables only; copper-wire cables are not supported. Fiber-optic data communiction cables are either single-mode or multi- mode, as summarized in Table 2-5, and have these characteristics:

Single-mode cables have a smaller core size than multi-mode, typically 8.5 or 9 microns, and use long wavelengths to transmit data over greater distances (up to 10 km; 20 km with an RPQ)1

Multi-mode cables have a larger core size than single-mode cables, typically 50 or 62.5 microns, and use short wavelengths, which limits transmission range to distances less than 500 m (1640 ft.). Multi-mode cables are more economical when long transmission distances are not a requirement.

VCF2 (FICON) cards support both short- and long-wave connections through different SFP connectors, which can be intermixed on individual cards. By default, VCF2 cards ship with long-wave (LX) SFP connectors; an orderable option allows field upgrades to short- wave (SX) connections.

LC Fibre connectors are used on both short- and long-wave SFPs, which requires use of LC-LC or LC-SC cables for all VTSS-to-host connections.

Table 2-5. Single-Mode vs. Multi-Mode FICON Cabling

Mode Type

Core Size

Wavelength

Color

Max. Transmission Distance

Relative Cost

Single-mode

8.5 to 9

 

 

• 10 km (6.2 mi.)

 

Long (LX)

Yellow

• 20 km (12.4 mi.) with RPQ

More

(SM)

microns

 

 

• 100 km (62 mi.) with repeaters

 

 

 

 

 

 

 

 

 

 

 

 

Multi-mode

50 to 62.5

Short (SX)

Orange

• 50 micron: 500 m (1640 ft.)

Less

(MM)

microns

 

 

 

 

• 62.5 micron: 175 m (574 ft.)*

 

Note: * Requires mode-conditioner patch (MCP) cables, used in pairs. Data rates >100 MB/sec. are not supported when MCP cables are used.

1. RPQ is not available with FICON channels rated at 200 MB/sec.

96257

Sun Confidential: Internal Only

2-37

 

Revision A

 

Image 37
Contents StorageTek Page Virtual Tape Storage Subsystem Vtss Disclaimer of Warranties and Limitation of Liability Export Destination Control StatementProprietary Information Statement Revision a SeptemberSAP Revision History / Summary of ChangesContents Implementation Planning Site Readiness Planning 96257 Sun Confidential Internal Only Vii Revision a96257 Sun Confidential Internal Only Viii Revision a Figures Tables Class 1 Laser Product Notice Warranty NoticeCabling Notice Hazardous Materials Handling Product Safety StandardsStandards Conformance Electromagnetic CompatibilityPage Definitions Internal Code License StatementSafety Precautions Safety / Fiber Optic / ESD PrecautionsStrictly Comply With Caution and Warning Messages Electrostatic Discharge PrecautionsProtect Your Eyes Fiber Optic Component Handling PrecautionsAbout This Guide Optimizing Content For Electronic ViewingProduct Overview Intended AudienceNotational and Typographic Conventions Alert MessagesExamples Description of Convention Reference Documents Where to Find Additional InformationVSM Engineering Website SE Support Tools ColophonSystem Assurance Process Flow Planning and Implementation OverviewCreating Planning Teams Planning / Readiness / Implementation Timelines Page Configuration Planning Overview Configuration PlanningKey High-Level Activities Key Sub-Tasks Key Participants VSM Quick Tool Tool Selection Screen Defining Customer RequirementsVSM Sizer Tool VSM Sizer ToolMVC Sizer Tool MVC Sizer ToolMVC Migration Tool MVC Migration ToolCDS Sizer Tool CDS Sizer ToolVSM5-VTSS Physical Characteristics Vtss Configuration PlanningVSM5-VTSS Physical Characteristics VSM5-VTSS Environmental RequirementsVSM5-VTSS Model Numbers / Configurations / Capacities Model Numbers / Configurations / CapacitiesAdditional Prerequisites for Ficon RTDs Prerequisites for Ficon ConnectivityNative Ficon Attachment Options Native Ficon AttachmentFicon Cabling Short-Wave vs. Long-Wave Connections Ficon Data Transfer RatesSingle-Mode vs. Multi-Mode Ficon Cabling Ficon Channel Card Configuration 4 VCF Cards VCF3 Ficon Card Configuration ExamplesFicon Channel Card Configuration 6 VCF Cards Fibre Channel Cables Available Lengths Fibre Channel Cables Available LengthsDescription / Length Part Number DC Power Supply Voltage Ripple Specifications AC Source Power Specifications and ConnectorsVSM5-VTSS AC Source Power Specifications and Connectors VSM5-VTSS DC Power Supply Voltage RipplePower Requirements Implementation Planning Overview Implementation PlanningPage Site Readiness Planning Overview Site Readiness PlanningSite Evaluation Internal Considerations Site Evaluation External ConsiderationsTransfering Equipment Point-to-Point Structural Dimensions and ObstructionsEmergency Power Control Data Center SafetySite Electrical Power Distribution System Site Power Distribution SystemsSource Power Voltage Range Frequency Range Hz Source Power Requirements for VSM5 EquipmentHvac Requirements Electrostatic DischargeFloor Construction Requirements Environmental Requirements and HazardsFloor Loading Requirements Site Evaluation Internal Considerations VSM5-VTSS Floor Loading SpecificationsVSM5-VTSS Cabinet Superimposed Floor Loading Example Raised Flooring Horizontal Force Chart VSM5-VTSS Cabinet Weight Distribution and Leveler LocationsPhysical Space Requirements VSM5-VTSS Cabinet Dimensions for Physical Space PlanningPage Specifications and Additional Information Motherboard and FRU Interconnections Side Motherboard and FRU Interconnections Side Figure A-3. VSM5-VTSS Power Safety Grounding Diagram Side Power Safety Grounding Diagram SideFigure A-4. VSM5-VTSS Power Safety Grounding Diagram Side Figure A-5. VSM5-VTSS Power System Diagram Power System DiagramFigure A-6. VSM5-VTSS Data Paths and Interfaces Data Paths and InterfacesVShell Command Reference Fiber Optic Cable SpecificationsTable A-1. Fiber Optic Cable Specifications Table A-2. VShell Command ReferenceFigure A-7. Sample Iocp Gen for Ficon Configuration Sample Iocp Gen for Ficon ConfigurationSequential Device Parameters Numbers Virtual Tape Drive Mapping and Host AddressingTable A-4. VSM5-VTSS FRU Identifiers FRU IdentifiersISP1 Hex Decimal Unit.Tray.Slot Logic Motherboard and CardsCard Cage Impellers Hex Decimal Unit.Tray.Slot Logic Power Supply FansPhysical Array Disk Drive Tray Hex Decimal Unit.Tray.Slot Physical Array Disk Drive Tray DA.5.DRV0 Figure A-8. Array Drive Module States and Relationships Array Drive Module Status DescriptionsMedia Acceptance Test MAT Partition Table A-5. Array Drive Module Status DescriptionsSpares Partition Unavailable PartitionPage Ficon Channel Extension Guidelines Definition of Terms Understand Channel Extension Performance Limitations General Channel Extension ConsiderationsInteroperability Testing Placement of Extension EquipmentFicon Topologies Channel Director/Switch Extender Ficon Channel Extension Sample ConfigurationsTape Silo HostFigure B-4. VTSS-to-RTD Channel Extension Direct Attachment McData/CNT Channel Extension Interoperability McData/CNT Channel Extension InteroperabilityISL Failover Is Supported Only in Shuttle Mode Cisco Systems Channel Extension Interoperability Page Glossary Sun Confidential Internal Only 96257 Revision a 96257 Sun Confidential Internal Only Revision a Data compression. See compression 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Functional device. See functional volume Technology with ISO 96257 Sun Confidential Internal Only Revision a MLC. Machine-Level Control Part number Service Delivery Platform SDP. a Sun StorageTek 96257 Sun Confidential Internal Only Revision a Sun Confidential Internal Only 96257 Revision a Forms and Reference Notes Host System Configuration Information Customer Personnel Contacts Sun StorageTek / QSP Personnel Contacts Planning Worksheet 1 Planning Worksheet 2 Planning Worksheet 3 Planning Worksheet 4 Planning Worksheet 5 Software Information Hardware Information Tape Devices Hardware Information Switches / Routers Hardware Information SDP and Modem Devices Account Account Account Account Account Page Headquarters