Omron BU3002SW, BU1002SW Connecting the equipment, Group control of power supply output

Page 26

2. Installation and connection

2-3 Connecting the equipment

Caution

Do not connect devices with rated voltage of 200 to 240 VAC or higher.

The rated output voltage of this device is 200 to 240 VAC.

Overcurrent may damage the connected devices.

When in use, make sure the output terminal block cover is attached. Do not turn ON the power switch when it is detached.

Voltage is applied to the output terminal block when the power switch is ON, which can result in electric shock.

<Example of connection 1 >

BU1002SW

PC

To power supply output receptacle

BU3002SW

PC

To power supply output receptacle

<Example of connection 2 >

Connected device (1)

Connected device (2)

To the terminal block for output

Connected device (1)

Connected device (2)

To the terminal block for output

Group control of power supply output

This function can be used with the UPS monitoring software included with the UPS. The output receptacles of the BU1002SW are separated into 3 groups: A, B, and C.

1.Power supply output group A

Output begins at the same time as startup.

2.Power supply output group B, C

The output start times for power supply output group B and C are independent of power supply output group A, so they can be delayed or set to precede the output stop time.

The output start/stop time control funtion is available when using the included “PowerAct Pro” UPS monitoring software, “UPS Power Manager” or “SNMP/Web card”.

Output ON/OFF can be controlled with the included UPS monitoring software while the BU1002SW is operating.

The delay settings and ON/OFF control described here can be performed independently for power

supply output group B and power supply output group C.

This function can be used to set the startup order of servers, peripheral devices, etc. The output receptacles can also be forcibly turned ON/OFF remotely.

24

Image 26
Contents BU1002SW/BU3002SW Introduction Internal Battery Procedure from installation to operation Start Installation/connectionTable of Contents Misuse may cause death or serious injury Safety precautionsKeep plastic package bags out of reach of children Do not pinch or tie the cable of the unit Provide secure groundingDo not disassemble, repair, or modify the unit Doing so may compromise the safety of devices Do not allow the unit to come in contact with water If fluid leaks from the unit, do not touch the fluidUse a specified battery for replacement Do not insert metal objects into the battery connectorsPerform replacement on a stable and flat place Do not disassemble or modify the batteryDo not put the battery into fire and do not break it Do not use a new battery and an old battery at the same timeDo not perform a withstand voltage test Scheduled operation using the UPS monitoring software Quitting Battery ModeRebooting This unit uses lead acid batteriesUnpacking the product 2Checking the contentsPreparation Name of each part Front viewSide view Rear view BU1002SW BU3002SWExplanation of symbols used on unit Installation and connection Precautions and notes on installation and connectionDo not install the unit in other than specified orientations Installation and connection Do not perform a withstand voltage test Installation and connection BU1002SWBU3002SW Casters locked Connecting the equipment Group control of power supply outputConnecting a device to the power supply output BU1002SW Output on Output OFFNfpa Input plug L6-15P Front view Connecting a device to the power supply output BU3002SW BU3002SW Rated value of output capacity Max kVA/2100WRear panel Input plug L6-20P Front view Bring all the connected devices into operation Turn on the units power switchChecking the operation Battery Mode, check the units LED display and beep sound OFFRecharging the battery Charging the batteryMeasuring the initial value of backup time Precautions and notes for operation OperationExplanation Operation Turn on the power switch of the UPS Start and stop procedures and basic operationStart procedure Operation after a power failure Setting switch 1 can be used to turn the beeper ON/OFF.Connection capacity/battery level meter Operation during recovery from a power failureStop procedure Interpreting beeps and displays Displays and beeps in normal operationDisplay and beep for battery replacement Self-diagnosis test UPS functionsSuspending a beep Description of the auto battery test function Changing the setting of the functionsSetting switch function list UPS functions BS signal reception time corresponds to the setting switch BS signal valid range setting setting switch Settable items and explanations UPS operation mode settingsSettings available for this operation are shown below OFF Settings Cold start Estimated backup time Measuring the backup timeHow to measure backup time For Windows Server 2003/XP/Me/2000/Windows NT/Linux/MacBUM100S Life of battery estimated replacement timing Maintenance and InspectionChecking the battery Methods for checking the batteryReplacing the battery Battery recycling Procedure for recycling the batteryDo not hold the connector or cable of the battery pack Tighten the 2 screws Battery replacement is now complete Red tape Tighten 2 screws After replacing the battery during operation Replacing the fan Do not put your fingers into the fanFan replacement procedure Cleaning Cleaning the UPSUsing the UPS monitoring software and contact signal UPS monitoring softwareSoftware title Connect the UPS to a computer RS-232CWhen using UPS Power Manager UPS monitoring software for Mac When connecting 2 or more computers to the UPSExplanation Install the included UPS service driver on the computer Connector Perform UPS service setup ClickRecycling and Discarding the Battery Stopping the UPSHow to set up UPS service set the time to shut down Windows Check Set ClickCheck Set Check Set Signal output Contact signalContact Signal Low battery level signal output BLItems that can be set using the contact signal card Remote ON/OFF SignalOutput delay time setting for backup signal output BU BU/BL signal reverse output settingInsert/ removal method of contact signal card Contact Signal Connector female DSUB9PContact Signal circuit inside the UPS Remote ON/OFF connectorContact Signal ratings Example of the use of the Contact Signal circuitPrecautions and notes for the use of the Contact Signal Remote ON/OFF circuitUsing an SNMP/Web card Adding an SNMP/Web cardSNMP/Web card outline Description featuresSpecifications Extending the backup time Connecting an additional battery unitAdding BUM300S to the BU3002SW Troubleshooting Problem Check and remedySpecifications ReferencesDimensions BU3002SWCircuit block diagram Related productsK1L-D-06051B