4. UPS functions

BS signal valid range setting (setting switch 7 ) Factory setting: OFF

 

ON

 

 

 

 

 

 

 

 

 

 

DIP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

4

5

6

 

7

8

OFF: The BS signal is always valid (receivable).

The unit’s “power output ” can be stopped by inputting a “ON” backup power supply stop signal (BS) that continues for 10 seconds or more.

ON: The BS signal is valid (receivable) only when in Battery Mode. (The signal is not received when in Commercial Power Mode.)

The unit’s “power output ” can be stopped by inputting a “ON” backup power supply stop signal (BS) that continues for 0.01 (10 ms) seconds or more.

Use this setting in commercial operation when you do not want to stop operations when a backup power supply stop signal (BS) is received.

•Auto startup operation when power is restored

Auto startup when power is restored is associated with setting switch 2.

However, the unit does not start up when the BS signal is ON.

●BS signal valid range setting (setting switch 7 )

ON

AC inputOFF

Commercial Power Mode

Operationg Mode

Battery Mode

BS signal

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 sec

 

 

 

 

 

 

 

10 sec

 

Power supply output

ON

 

 

 

 

*1

 

 

*1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Setting switch OFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

0.01 sec

 

 

 

 

 

 

 

 

 

 

 

 

Power supply output

ON

 

 

 

 

 

 

 

*1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Setting switch ON)

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1: Operation when setting switch 2 is OFF (auto startup is performed). When it is ON (auto startup is not performed) auto startup is not performed.

46

Image 48
Contents BU1002SW/BU3002SW Introduction Internal Battery Procedure from installation to operation Start Installation/connectionTable of Contents Safety precautions Keep plastic package bags out of reach of childrenMisuse may cause death or serious injury Provide secure grounding Do not disassemble, repair, or modify the unitDo not pinch or tie the cable of the unit Doing so may compromise the safety of devices Do not allow the unit to come in contact with water If fluid leaks from the unit, do not touch the fluidDo not insert metal objects into the battery connectors Perform replacement on a stable and flat placeUse a specified battery for replacement Do not disassemble or modify the batteryDo not put the battery into fire and do not break it Do not use a new battery and an old battery at the same timeDo not perform a withstand voltage test Quitting Battery Mode RebootingScheduled operation using the UPS monitoring software This unit uses lead acid batteries2Checking the contents PreparationUnpacking the product Name of each part Front viewSide view Rear view BU1002SW BU3002SWExplanation of symbols used on unit Installation and connection Precautions and notes on installation and connectionDo not install the unit in other than specified orientations Installation and connection Do not perform a withstand voltage test Installation and connection BU1002SWBU3002SW Casters locked Connecting the equipment Group control of power supply outputConnecting a device to the power supply output BU1002SW Output on Output OFFNfpa Input plug L6-15P Front view Connecting a device to the power supply output BU3002SW BU3002SW Rated value of output capacity Max kVA/2100WRear panel Input plug L6-20P Front view Turn on the units power switch Checking the operationBring all the connected devices into operation Battery Mode, check the units LED display and beep sound OFFCharging the battery Measuring the initial value of backup timeRecharging the battery Precautions and notes for operation OperationExplanation Start and stop procedures and basic operation Start procedureOperation Turn on the power switch of the UPS Operation after a power failure Setting switch 1 can be used to turn the beeper ON/OFF.Operation during recovery from a power failure Stop procedureConnection capacity/battery level meter Interpreting beeps and displays Displays and beeps in normal operationDisplay and beep for battery replacement UPS functions Suspending a beepSelf-diagnosis test Description of the auto battery test function Changing the setting of the functionsSetting switch function list UPS functions BS signal reception time corresponds to the setting switch BS signal valid range setting setting switch UPS operation mode settings Settings available for this operation are shown belowSettable items and explanations OFF Settings Cold start Measuring the backup time How to measure backup timeEstimated backup time For Windows Server 2003/XP/Me/2000/Windows NT/Linux/MacBUM100S Maintenance and Inspection Checking the batteryLife of battery estimated replacement timing Methods for checking the batteryReplacing the battery Battery recycling Procedure for recycling the batteryDo not hold the connector or cable of the battery pack Tighten the 2 screws Battery replacement is now complete Red tape Tighten 2 screws After replacing the battery during operation Replacing the fan Do not put your fingers into the fanFan replacement procedure Cleaning Cleaning the UPSUsing the UPS monitoring software and contact signal UPS monitoring softwareSoftware title Connect the UPS to a computer RS-232CWhen using UPS Power Manager UPS monitoring software for Mac When connecting 2 or more computers to the UPSExplanation Install the included UPS service driver on the computer Connector Perform UPS service setup ClickRecycling and Discarding the Battery Stopping the UPSHow to set up UPS service set the time to shut down Windows Check Set ClickCheck Set Check Set Contact signal Contact SignalSignal output Low battery level signal output BLItems that can be set using the contact signal card Remote ON/OFF SignalOutput delay time setting for backup signal output BU BU/BL signal reverse output settingInsert/ removal method of contact signal card Contact Signal Connector female DSUB9PRemote ON/OFF connector Contact Signal ratingsContact Signal circuit inside the UPS Example of the use of the Contact Signal circuitPrecautions and notes for the use of the Contact Signal Remote ON/OFF circuitUsing an SNMP/Web card Adding an SNMP/Web cardDescription features SpecificationsSNMP/Web card outline Extending the backup time Connecting an additional battery unitAdding BUM300S to the BU3002SW Troubleshooting Problem Check and remedySpecifications ReferencesDimensions BU3002SWCircuit block diagram Related productsK1L-D-06051B