4.UPS functions
●Setting for whether or not to perform battery test (setting switch 3 )
…Factory setting: OFF
| ON |
|
|
|
|
|
|
|
|
|
| DIP | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 | 2 | 3 |
| 4 | 5 | 6 |
| 7 | 8 |
OFF: The battery test is automatically executed once every 4 weeks.
ON: Does not perform the auto battery test.
Use this setting to disable Battery Mode for for the regularly performed auto battery test.
●Auto startup mode setting (setting switch 4 ) … Factory setting: OFF
ON |
|
|
|
|
|
|
|
|
| DIP | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 2 3 4 5 6 7 8
OFF: (Mode A) After UPS stopped, the UPS is automatically started immediately when “ON” is detected for the AC input.
ON: (Mode B) After UPS stopped, the UPS is automatically started in the AC input’s “OFF to ON” timing that is detected.
(Definition of AC input OFF: When AC input is OFF for 1 second or more)
*Setting switch 4 is valid when the auto startup after recovery from power failure setting (setting switch 2) is set to OFF (auto restart is performed).
*This setting mode is valid only after the UPS has been stopped by the contact signal backup stop signal (BS).
*When a cable is connected to the