2. Installation and connection

2-4 Checking the operation

After you finish connecting devices to the unit, make sure the backup function operates properly.

Check that the Battery Mode is performed normally according to the following procedure.

(This operation check simulates a power failure by disconnecting the AC input plug from a wall outlet.)

(1)Turn ON the unit's power switch.

The beeper sounds and the current settings are displayed on the LED.

After 5 secounds, the self-diagnostic test is performed in Battery Mode for approximately 10 seconds.

When the self-diagnostic test finishes successfully, switching to AC output from commercial power is per- formed and the the display below is shown.

(If the battery voltage is low, the self-diagnostic test is not performed and the operation starts immediately, using output from commercial power.)

Status indicator

Description

Power switch “ON”

Operating normally

ON

OFF

ON, OFF, or blinking

depending on status

 

 

(2)Bring all the connected devices into operation.

(Including devices connected to the AC outlet of your PC.)

Operate the devices in a way in which abrupt power stop does not damage the connected devices, data, etc.

(3)Under this condition, check the the unit's LED display and beep sound.

Are they in the same status as shown below?

Status indicator

 

Beep

None

Power supply output receptacles

Outputs power (connected devices are powered)

DIP

8

 

7

 

6

 

5

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

3

ON

2

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

バッテリ

ブザー停止/テスト

電源出力

増設

 

 

 

 

 

 

 

 

 

 

-

 

バイパス

バッテリ

 

 

運転

交換

 

 

 

 

 

 

 

 

 

 

 

 

 

If the same as the one shown above: The operation is normal. Proceed to (4).

If not the same as the one shown above: The operation is abnormal. One of the cases described in "4. Dis- play and beeps when there is an equipment failure" of "3-3 Inter- preting a beep and displays" on page 39 must apply.

Take necessary measures and then proceed to (4).

(4)Disconnect the AC input plug of this unit from a wall outlet (commercial power).

The UPS enters Battery Mode.

31

Image 33
Contents BU1002SW/BU3002SW Introduction Internal Battery Start Installation/connection Procedure from installation to operationTable of Contents Safety precautions Keep plastic package bags out of reach of childrenMisuse may cause death or serious injury Provide secure grounding Do not disassemble, repair, or modify the unitDo not pinch or tie the cable of the unit Doing so may compromise the safety of devices If fluid leaks from the unit, do not touch the fluid Do not allow the unit to come in contact with waterPerform replacement on a stable and flat place Do not insert metal objects into the battery connectorsUse a specified battery for replacement Do not disassemble or modify the batteryDo not use a new battery and an old battery at the same time Do not put the battery into fire and do not break itDo not perform a withstand voltage test Rebooting Quitting Battery ModeScheduled operation using the UPS monitoring software This unit uses lead acid batteries2Checking the contents PreparationUnpacking the product Front view Name of each partSide view BU1002SW BU3002SW Rear viewExplanation of symbols used on unit Precautions and notes on installation and connection Installation and connectionDo not install the unit in other than specified orientations Installation and connection Do not perform a withstand voltage test BU1002SW Installation and connectionBU3002SW Casters locked Group control of power supply output Connecting the equipmentOutput on Output OFF Connecting a device to the power supply output BU1002SWNfpa Input plug L6-15P Front view BU3002SW Rated value of output capacity Max kVA/2100W Connecting a device to the power supply output BU3002SWRear panel Input plug L6-20P Front view Turn on the units power switch Checking the operationBring all the connected devices into operation OFF Battery Mode, check the units LED display and beep soundCharging the battery Measuring the initial value of backup timeRecharging the battery Operation Precautions and notes for operationExplanation Start and stop procedures and basic operation Start procedureOperation Turn on the power switch of the UPS Setting switch 1 can be used to turn the beeper ON/OFF. Operation after a power failureOperation during recovery from a power failure Stop procedureConnection capacity/battery level meter Displays and beeps in normal operation Interpreting beeps and displaysDisplay and beep for battery replacement UPS functions Suspending a beepSelf-diagnosis test Changing the setting of the functions Description of the auto battery test functionSetting switch function list UPS functions BS signal reception time corresponds to the setting switch BS signal valid range setting setting switch UPS operation mode settings Settings available for this operation are shown belowSettable items and explanations OFF Settings Cold start How to measure backup time Measuring the backup timeEstimated backup time For Windows Server 2003/XP/Me/2000/Windows NT/Linux/MacBUM100S Checking the battery Maintenance and InspectionLife of battery estimated replacement timing Methods for checking the batteryReplacing the battery Procedure for recycling the battery Battery recyclingDo not hold the connector or cable of the battery pack Tighten the 2 screws Battery replacement is now complete Red tape Tighten 2 screws After replacing the battery during operation Do not put your fingers into the fan Replacing the fanFan replacement procedure Cleaning the UPS CleaningUPS monitoring software Using the UPS monitoring software and contact signalSoftware title RS-232C Connect the UPS to a computerWhen connecting 2 or more computers to the UPS When using UPS Power Manager UPS monitoring software for MacExplanation Install the included UPS service driver on the computer Connector Click Perform UPS service setupStopping the UPS Recycling and Discarding the BatteryCheck Set Click How to set up UPS service set the time to shut down WindowsCheck Set Check Set Contact Signal Contact signalSignal output Low battery level signal output BLRemote ON/OFF Signal Items that can be set using the contact signal cardBU/BL signal reverse output setting Output delay time setting for backup signal output BUContact Signal Connector female DSUB9P Insert/ removal method of contact signal cardContact Signal ratings Remote ON/OFF connectorContact Signal circuit inside the UPS Example of the use of the Contact Signal circuitRemote ON/OFF circuit Precautions and notes for the use of the Contact SignalAdding an SNMP/Web card Using an SNMP/Web cardDescription features SpecificationsSNMP/Web card outline Connecting an additional battery unit Extending the backup timeAdding BUM300S to the BU3002SW Problem Check and remedy TroubleshootingReferences SpecificationsBU3002SW DimensionsRelated products Circuit block diagramK1L-D-06051B