Omron BU1002SW, BU3002SW Provide secure grounding, Do not disassemble, repair, or modify the unit

Page 7

Safety precautions

Caution (for installation and connection)

When an abnormality (unusual sound or smell) occurs, turn OFF the unit's power switch and disconnect the AC input plug from the wall outlet. Install the unit soon after the AC input plug is disconnected from the wall outlet.

When performing maintenance on the connected devices, follow the above instructions to ensure safety.

Do not connect devices such as dryers, some solenoid valves, etc. , which have a half-wave rectifier that allows only half-cycle AC power to flow through.

Overcurrent may damage the UPS.

Connect the BU1002SW to a wall outlet (commercial power) with a capacity of 7.4A or more, and connect the B3002SW to a wall outlet (commercial power) with a capacity of 16A or more.

Otherwise, the power cord may be heated.

When equipment with the maximum output capacity is connected, a maximum current of 7.4A (BU1002SW) or 16A (BU3002SW) flows.

Provide secure grounding.

After checking the plug shape of the wall outlet, directly connect the AC input plug of the unit to it. A failure or leak that occurs when the unit is not properly grounded may result in electric shock.

Do not disassemble, repair, or modify the unit.

Doing so may cause an electric shock or a fire.

Do not install the unit in other than specified orientations.

Dropping or toppling the unit may cause injury.

If you install the unit in an orientation other than specified, the unit cannot be protected from a battery fluid leakage.

Do not use the unit where the maximum temperature exceeds 40°C.

The battery becomes weak rapidly, which may cause a fire.

Doing so may cause a failure or malfunction of the unit.

Do not exceed the ranges specified for environmental conditions during use/storage.

Do not install or store the unit in the places listed below.

Do not store in places where the humidity is lower than 20% or higher than 90%.

Do not use in places where the humidity is lower than 25% or higher than 85%.

Do not use in closed spaces such as cabinets without clearance, or in places where flam- mable or corrosive gases are present, places subject to vibration or shock, or outdoors.

Installation or storing the unit in such a place may cause a fire.

Do not connect equipment that exceeds the output capacity of the unit. You can use a 200V plug strip to connect additional devices, but do not connect devices that exceed the current capacity of the plug strip.

The current protection of the unit may operate, which may stop the output.

The wiring of the plug strip heats up, which may cause a fire.

Do not pinch or tie the cable of the unit.

Doing so may cause the cable to be damaged or heated, which may cause an electric shock or a fire.

If the cable is damaged, stop using the unit and have the cable repaired. For repair, contact us; ____

5

Image 7
Contents BU1002SW/BU3002SW Introduction Internal Battery Start Installation/connection Procedure from installation to operationTable of Contents Keep plastic package bags out of reach of children Safety precautionsMisuse may cause death or serious injury Do not disassemble, repair, or modify the unit Provide secure groundingDo not pinch or tie the cable of the unit Doing so may compromise the safety of devices If fluid leaks from the unit, do not touch the fluid Do not allow the unit to come in contact with waterDo not disassemble or modify the battery Do not insert metal objects into the battery connectorsPerform replacement on a stable and flat place Use a specified battery for replacementDo not use a new battery and an old battery at the same time Do not put the battery into fire and do not break itDo not perform a withstand voltage test This unit uses lead acid batteries Quitting Battery ModeRebooting Scheduled operation using the UPS monitoring softwarePreparation 2Checking the contentsUnpacking the product Front view Name of each partSide view BU1002SW BU3002SW Rear viewExplanation of symbols used on unit Precautions and notes on installation and connection Installation and connectionDo not install the unit in other than specified orientations Installation and connection Do not perform a withstand voltage test BU1002SW Installation and connectionBU3002SW Casters locked Group control of power supply output Connecting the equipmentOutput on Output OFF Connecting a device to the power supply output BU1002SWNfpa Input plug L6-15P Front view BU3002SW Rated value of output capacity Max kVA/2100W Connecting a device to the power supply output BU3002SWRear panel Input plug L6-20P Front view Checking the operation Turn on the units power switchBring all the connected devices into operation OFF Battery Mode, check the units LED display and beep soundMeasuring the initial value of backup time Charging the batteryRecharging the battery Operation Precautions and notes for operationExplanation Start procedure Start and stop procedures and basic operationOperation Turn on the power switch of the UPS Setting switch 1 can be used to turn the beeper ON/OFF. Operation after a power failureStop procedure Operation during recovery from a power failureConnection capacity/battery level meter Displays and beeps in normal operation Interpreting beeps and displaysDisplay and beep for battery replacement Suspending a beep UPS functionsSelf-diagnosis test Changing the setting of the functions Description of the auto battery test functionSetting switch function list UPS functions BS signal reception time corresponds to the setting switch BS signal valid range setting setting switch Settings available for this operation are shown below UPS operation mode settingsSettable items and explanations OFF Settings Cold start For Windows Server 2003/XP/Me/2000/Windows NT/Linux/Mac Measuring the backup timeHow to measure backup time Estimated backup timeBUM100S Methods for checking the battery Maintenance and InspectionChecking the battery Life of battery estimated replacement timingReplacing the battery Procedure for recycling the battery Battery recyclingDo not hold the connector or cable of the battery pack Tighten the 2 screws Battery replacement is now complete Red tape Tighten 2 screws After replacing the battery during operation Do not put your fingers into the fan Replacing the fanFan replacement procedure Cleaning the UPS CleaningUPS monitoring software Using the UPS monitoring software and contact signalSoftware title RS-232C Connect the UPS to a computerWhen connecting 2 or more computers to the UPS When using UPS Power Manager UPS monitoring software for MacExplanation Install the included UPS service driver on the computer Connector Click Perform UPS service setupStopping the UPS Recycling and Discarding the BatteryCheck Set Click How to set up UPS service set the time to shut down WindowsCheck Set Check Set Low battery level signal output BL Contact signalContact Signal Signal outputRemote ON/OFF Signal Items that can be set using the contact signal cardBU/BL signal reverse output setting Output delay time setting for backup signal output BUContact Signal Connector female DSUB9P Insert/ removal method of contact signal cardExample of the use of the Contact Signal circuit Remote ON/OFF connectorContact Signal ratings Contact Signal circuit inside the UPSRemote ON/OFF circuit Precautions and notes for the use of the Contact SignalAdding an SNMP/Web card Using an SNMP/Web cardSpecifications Description featuresSNMP/Web card outline Connecting an additional battery unit Extending the backup timeAdding BUM300S to the BU3002SW Problem Check and remedy TroubleshootingReferences SpecificationsBU3002SW DimensionsRelated products Circuit block diagramK1L-D-06051B