Omron BU1002SW, BU3002SW specifications BS signal reception time corresponds to the setting switch

Page 47

4. UPS functions

(1)When BS signal is used to stop the UPS after a power failure occurs

(1)-1.

*1 ON

AC input

 

OFF

BS signal

ON

 

 

OFF

Power output

ON

(Setting switch 4 OFF:

OFF

Mode A)

Power output

ON

(Setting switch 4 ON:

 

Mode B)

OFF

(2) When BS signal is used to shut down the UPS when AC input is ON

 

ON

 

1 sec

AC input

OFF

*1

 

 

 

 

 

 

ON

 

 

BS signal

OFF

 

 

 

 

 

Power output

ON

 

 

(Setting switch 4 OFF:

OFF

 

 

Mode A)

 

 

Power output

ON

 

 

(Setting switch 4 ON:

OFF

 

 

Mode B)

 

 

Starts up when BS signal turns OFF

Starts up when AC input turns from OFF to ON

* 1: BS signal reception time corresponds to the setting switch 7.

45

Image 47
Contents BU1002SW/BU3002SW Introduction Internal Battery Start Installation/connection Procedure from installation to operationTable of Contents Misuse may cause death or serious injury Safety precautionsKeep plastic package bags out of reach of children Do not pinch or tie the cable of the unit Provide secure groundingDo not disassemble, repair, or modify the unit Doing so may compromise the safety of devices If fluid leaks from the unit, do not touch the fluid Do not allow the unit to come in contact with waterDo not disassemble or modify the battery Do not insert metal objects into the battery connectorsPerform replacement on a stable and flat place Use a specified battery for replacementDo not use a new battery and an old battery at the same time Do not put the battery into fire and do not break itDo not perform a withstand voltage test This unit uses lead acid batteries Quitting Battery ModeRebooting Scheduled operation using the UPS monitoring softwareUnpacking the product 2Checking the contentsPreparation Front view Name of each partSide view BU1002SW BU3002SW Rear viewExplanation of symbols used on unit Precautions and notes on installation and connection Installation and connectionDo not install the unit in other than specified orientations Installation and connection Do not perform a withstand voltage test BU1002SW Installation and connectionBU3002SW Casters locked Group control of power supply output Connecting the equipmentOutput on Output OFF Connecting a device to the power supply output BU1002SWNfpa Input plug L6-15P Front view BU3002SW Rated value of output capacity Max kVA/2100W Connecting a device to the power supply output BU3002SWRear panel Input plug L6-20P Front view Bring all the connected devices into operation Turn on the units power switchChecking the operation OFF Battery Mode, check the units LED display and beep soundRecharging the battery Charging the batteryMeasuring the initial value of backup time Operation Precautions and notes for operationExplanation Operation Turn on the power switch of the UPS Start and stop procedures and basic operationStart procedure Setting switch 1 can be used to turn the beeper ON/OFF. Operation after a power failureConnection capacity/battery level meter Operation during recovery from a power failureStop procedure Displays and beeps in normal operation Interpreting beeps and displaysDisplay and beep for battery replacement Self-diagnosis test UPS functionsSuspending a beep Changing the setting of the functions Description of the auto battery test functionSetting switch function list UPS functions BS signal reception time corresponds to the setting switch BS signal valid range setting setting switch Settable items and explanations UPS operation mode settingsSettings available for this operation are shown below OFF Settings Cold start For Windows Server 2003/XP/Me/2000/Windows NT/Linux/Mac Measuring the backup timeHow to measure backup time Estimated backup timeBUM100S Methods for checking the battery Maintenance and InspectionChecking the battery Life of battery estimated replacement timingReplacing the battery Procedure for recycling the battery Battery recyclingDo not hold the connector or cable of the battery pack Tighten the 2 screws Battery replacement is now complete Red tape Tighten 2 screws After replacing the battery during operation Do not put your fingers into the fan Replacing the fanFan replacement procedure Cleaning the UPS CleaningUPS monitoring software Using the UPS monitoring software and contact signalSoftware title RS-232C Connect the UPS to a computerWhen connecting 2 or more computers to the UPS When using UPS Power Manager UPS monitoring software for MacExplanation Install the included UPS service driver on the computer Connector Click Perform UPS service setupStopping the UPS Recycling and Discarding the BatteryCheck Set Click How to set up UPS service set the time to shut down WindowsCheck Set Check Set Low battery level signal output BL Contact signalContact Signal Signal outputRemote ON/OFF Signal Items that can be set using the contact signal cardBU/BL signal reverse output setting Output delay time setting for backup signal output BUContact Signal Connector female DSUB9P Insert/ removal method of contact signal cardExample of the use of the Contact Signal circuit Remote ON/OFF connectorContact Signal ratings Contact Signal circuit inside the UPSRemote ON/OFF circuit Precautions and notes for the use of the Contact SignalAdding an SNMP/Web card Using an SNMP/Web cardSNMP/Web card outline Description featuresSpecifications Connecting an additional battery unit Extending the backup timeAdding BUM300S to the BU3002SW Problem Check and remedy TroubleshootingReferences SpecificationsBU3002SW DimensionsRelated products Circuit block diagramK1L-D-06051B