Omron BU3002SW, BU1002SW Replacing the battery, Perform replacement on a stable and flat place

Page 56

6.Maintenance and inspection

3.Guidelines for how often to check the battery (measure the backup time)

Ambient temperature

Check once every 6 months

Check once a month

20°C

For the first 3 years after purchase

When 3 or more years have passed since purchase

 

 

 

30°C

For the first 1.5 years after purchase

When 1.5 or more years have passed since purchase

 

 

 

*The battery deteriorates even if it is stored. The higher the temperature is, the shorter the life becomes.

6-2 Replacing the battery

The battery can be replaced while the unit is stopped (power supply output stopped).

Caution

When the unit is used in compliance with UL standards or CE marking, do not replace the battery while in operation (while power is being output). Replacing the battery while in operation does not comply with UL standards or CE marking. Make sure to stop the operation of the unit before replacing the battery.

*When replacing the battery, stop the connected devices, turn OFF the power switch of the UPS, and disconnect the AC input plug from the wall.

*If an input power supply error such as a power failure occurs when replacing the battery while in opera- tion, backup cannot be performed and output stops.

*Do not replace the battery during backup operation. Output will stop.

Caution (for battery replacement)

Perform replacement on a stable and flat place.

Handle the battery carefully so that you do not drop it.

Not doing so could cause injury or burns due to liquid (acid) leakage.

Use a specified battery for replacement.

Not doing so may cause a fire.

Product model: BP100XS (Replacement battery pack for BU1002SW)

BP150XS: Two required (Replacement battery pack for BU3002SW)

Do not replace the battery in a place where there is flammable gas.

Spark may occur when connecting the battery, which may cause an explosion or fire.

If fluid (dilute sulfuric acid) leaks from the battery, do not touch the fluid.

Doing so may cause blindness or burns.

If it contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.

Do not disassemble or modify the battery.

Doing so could cause dilute sulfuric acid leak, which could cause blindness and burns.

Do not drop the battery and do not expose it to strong impact.

Dilute sulfuric acid may leak.

Do not short the battery with metal objects.

Doing so could cause an electric shock, fire or burn.

Some electrical energy still remains inside the spent battery.

54

Image 56
Contents BU1002SW/BU3002SW Introduction Internal Battery Procedure from installation to operation Start Installation/connectionTable of Contents Misuse may cause death or serious injury Safety precautionsKeep plastic package bags out of reach of children Do not pinch or tie the cable of the unit Provide secure groundingDo not disassemble, repair, or modify the unit Doing so may compromise the safety of devices Do not allow the unit to come in contact with water If fluid leaks from the unit, do not touch the fluidDo not insert metal objects into the battery connectors Perform replacement on a stable and flat placeUse a specified battery for replacement Do not disassemble or modify the batteryDo not put the battery into fire and do not break it Do not use a new battery and an old battery at the same timeDo not perform a withstand voltage test Quitting Battery Mode RebootingScheduled operation using the UPS monitoring software This unit uses lead acid batteriesUnpacking the product 2Checking the contentsPreparation Name of each part Front viewSide view Rear view BU1002SW BU3002SWExplanation of symbols used on unit Installation and connection Precautions and notes on installation and connectionDo not install the unit in other than specified orientations Installation and connection Do not perform a withstand voltage test Installation and connection BU1002SWBU3002SW Casters locked Connecting the equipment Group control of power supply outputConnecting a device to the power supply output BU1002SW Output on Output OFFNfpa Input plug L6-15P Front view Connecting a device to the power supply output BU3002SW BU3002SW Rated value of output capacity Max kVA/2100WRear panel Input plug L6-20P Front view Bring all the connected devices into operation Turn on the units power switchChecking the operation Battery Mode, check the units LED display and beep sound OFFRecharging the battery Charging the batteryMeasuring the initial value of backup time Precautions and notes for operation OperationExplanation Operation Turn on the power switch of the UPS Start and stop procedures and basic operationStart procedure Operation after a power failure Setting switch 1 can be used to turn the beeper ON/OFF.Connection capacity/battery level meter Operation during recovery from a power failureStop procedure Interpreting beeps and displays Displays and beeps in normal operationDisplay and beep for battery replacement Self-diagnosis test UPS functionsSuspending a beep Description of the auto battery test function Changing the setting of the functionsSetting switch function list UPS functions BS signal reception time corresponds to the setting switch BS signal valid range setting setting switch Settable items and explanations UPS operation mode settingsSettings available for this operation are shown below OFF Settings Cold start Measuring the backup time How to measure backup timeEstimated backup time For Windows Server 2003/XP/Me/2000/Windows NT/Linux/MacBUM100S Maintenance and Inspection Checking the batteryLife of battery estimated replacement timing Methods for checking the batteryReplacing the battery Battery recycling Procedure for recycling the batteryDo not hold the connector or cable of the battery pack Tighten the 2 screws Battery replacement is now complete Red tape Tighten 2 screws After replacing the battery during operation Replacing the fan Do not put your fingers into the fanFan replacement procedure Cleaning Cleaning the UPSUsing the UPS monitoring software and contact signal UPS monitoring softwareSoftware title Connect the UPS to a computer RS-232CWhen using UPS Power Manager UPS monitoring software for Mac When connecting 2 or more computers to the UPSExplanation Install the included UPS service driver on the computer Connector Perform UPS service setup ClickRecycling and Discarding the Battery Stopping the UPSHow to set up UPS service set the time to shut down Windows Check Set ClickCheck Set Check Set Contact signal Contact SignalSignal output Low battery level signal output BLItems that can be set using the contact signal card Remote ON/OFF SignalOutput delay time setting for backup signal output BU BU/BL signal reverse output settingInsert/ removal method of contact signal card Contact Signal Connector female DSUB9PRemote ON/OFF connector Contact Signal ratingsContact Signal circuit inside the UPS Example of the use of the Contact Signal circuitPrecautions and notes for the use of the Contact Signal Remote ON/OFF circuitUsing an SNMP/Web card Adding an SNMP/Web cardSNMP/Web card outline Description featuresSpecifications Extending the backup time Connecting an additional battery unitAdding BUM300S to the BU3002SW Troubleshooting Problem Check and remedySpecifications ReferencesDimensions BU3002SWCircuit block diagram Related productsK1L-D-06051B