4. UPS functions
Normal status |
|
| There is AC input | A | Turn ON the power switch while the beep stop/test switch is pressed. | ||||
| Power switch “OFF” (Status No. 2) | B | Turn OFF the power switch. |
|
| ||||
A | B |
|
|
|
| C Press and hold the beep stop/test switch (for more than 3 seconds). | |||
Setting mode |
|
|
|
| D Press the beep stop/test switch (for less than 3 seconds). | ||||
|
|
|
|
|
|
|
| ||
| Cold start |
|
| OFF | Cold start OFF mode |
|
| ||
| C | *1 |
|
|
|
|
|
| |
ON/OFF setting |
|
| D | D |
|
| |||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
|
| C |
| ON | Cold start ON mode |
|
| ||
| D |
|
|
|
|
|
|
|
|
Output voltage | C | *1 | 200V | Output 200V mode |
|
| |||
| setting |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
|
|
|
|
| D |
|
|
|
|
|
| C |
| 220V | Output 220V mode |
|
| ||
|
|
|
|
|
| ||||
|
|
|
|
| D |
|
|
|
|
|
|
|
| 230V | Output 230V mode | D |
| ||
|
|
|
|
|
| ||||
| D |
|
|
| D |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| 240V | Output 240V mode |
|
| ||
Output voltage | C | *1 |
|
|
|
|
|
| |
| setting |
| 0 minute delay |
|
| ||||
|
| C |
|
|
| D |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| 0.2 minute delay |
|
|
| |
|
|
|
|
|
| D |
|
|
|
|
|
|
|
| 0.5 minute delay |
|
|
| |
|
|
|
|
|
| D |
|
|
|
D | D |
|
|
| 1 minute delay | D |
|
| |
|
|
|
|
|
| D |
|
|
|
|
|
|
|
| 2 minute delay |
|
|
| |
|
|
|
|
|
| D |
|
|
|
|
|
|
|
| 10 minute delay |
|
|
| |
Signal input/output | C |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
| test |
|
| BL | Battery low signal output test |
| |||
|
| C |
|
|
| D |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| TR | Trouble signal output test |
|
| ||
|
|
|
|
|
| D |
|
|
|
|
|
|
| BU | Backup signal output test |
|
| ||
|
|
|
|
|
| D |
|
|
|
|
|
|
| WB | Battery replacement signal output test |
| D | ||
|
|
|
|
|
| D |
|
|
|
|
|
|
| BS | Backup power supply stop signal output test |
|
| ||
|
|
|
|
|
| D |
|
|
|
|
|
|
| Remote | Remote ON/OFF signal output test |
|
|
*1 Displays the current setting value.
50