Operation

3.1.1Operator Control Panel

The Operator Control Panel enables the operator to perform the following tasks:

Obtain a quick indication of operational status:

Is the critical bus OK?

Is the UPS system OK?

Is the battery available?

Is the bypass line available?

Monitor the power flow through the UPS system and monitor all meter readings:

Is the critical load being supplied power from the UPS system or bypass?

Are input, battery, and output voltage, frequency, and current readings at nominal levels?

How much battery time is still available during an outage?

Is the battery recharging after discharge?

Execute operational procedures:

Perform critical bus transfer/retransfer between the UPS and the bypass line.

Start-up and shutdown the UPS.

Shutdown the system instantly in the event of an emergency.

Access status reports and history files:

Obtain a complete listing of the present status of the UPS including input, output, and bat- tery voltage, frequency, and current readings, and any alarms that may be present.

Review a complete history report of all events leading up to and immediately after a fault con- dition.

Examine an archive listing of all alarm conditions that have occurred over a period of time.

Make adjustments to programmable parameters (access limited by Security Access function):

Set the date and the time functions.

Change the auto-dial phone number and the modem options.

Select the number of auto-retransfer attempts.

Make adjustments to the UPS output voltage before performing a manual load transfer.

3.1.2Navigation Buttons

The Navigation Buttons are located below the Display Screen.

Figure 4 Navigation buttons

MAIN MENU

 

 

MANUAL TRANSFER

 

 

 

 

BATTERY MANAGEMENT

STARTUP / SHUTDOWN

STATUS REPORTS

 

CONFIGURATION

 

SELECT

UP

DOWN

ALARM

RESET

ALARM SILENCE

ESCAPE

16

Image 24
Contents Npower UPS Page Table of Contents Maintenance Communication InterfacesFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Safety Precautions Factory Backup and Service AssistanceReliability VersatilityInput Power Failure Modes Of OperationNormal Load On UPS RechargeMimic Display CHGSYS. Status Operator Controls OptionsBattery System General Component DescriptionUPS Module Detailed Component Descriptions Controls HardwareFirmware Input Power Factor Battery Charging CircuitRectifier/Charger OperationBattery Disconnect Battery Charge Current LimitingBattery Equalize Charge Circuit Operation After End-of-dischargeNonlinear Load Characteristics Unbalanced Load CharacteristicsStatic Bypass Switch Static Switch Backfeed ProtectionTransfer and Retransfer Conditions Operation Operation Operator Control Panel Navigation ButtonsRotary Switch Rotary switchConfiguration User SettingsSecurity Access and Passwords Prev Cancel Save & ExitDisplay Screens and Procedures Menu TreePrimary Screens Secondary ScreensMain Menu Screen Mimic Display ScreenFaults Faults / AlarmsRect DischgMimic Display SYS. StatusDC BUS / Battery Status Input StatusFreq Temps DEG C Inlet AIR Outlet AIR Heat SinksFreq .9 HZ 213 214 Phase Diff Bypass Input StatusOutput Load Status Active Faults and Alarms Faults and AlarmsUser Shutdown EXI TSystem Ratings NextManual Startup Second ScenarioAuto Startup Input Modify Current Limit Target and Ramp Values Modify DC BUS SET Point Target and Ramp ValuesServ Skip AbortSIB External Maintenance Bypass External maintenance bypass switch, dual-input UPSExternal maintenance bypass switch, single-input UPS Multiple Battery Cabinets External Maintenance Bypass Switch ConfigurationsUser Shutdown ShutdownStatus Reports System StatusHistory LOG Clear History Logs Clear Event LOG Status ReportsEvent LOG TotalEvent Log History LOG 02 / 10OUT-V IN-V Load Freq OutputSBS Line Trap SBS Load Input of / UFConfiguration Screens ExitDC BUS Volts Input FrequencyOutput Frequency PrevSystem Settings Cancel Save & ExitSystem Settings Current DateNext PREV. Cancel Save & Exit Current TimeOrder Number TimeEnter Password Single / Dual InputDual Output Transformer Bypass WIND. no10% Passive Filter Settings OptionsActive Filter LBS Generator Auto Restart OptionsPulse Rectifier Battery GND Fault Green Machine Alternate Power Pole FAN noLine Drop Compensation Prev ExitCommunication Options Auto DialNext Exit Pager Support Configuration Pager Enabled Pager Number Pager PINModem Health Check Auto Dial YES Auto Dial OUT PagerPREV. Cancel Next PREV. Cancel 10 % Passive Filter Settings Factory SettingsNext Cancel Alarm Mask LatchingDial FreezeAlarm / Fault Name Alarm / Fault Name Battery Fuse FailAlarm / Fault Name F E Save & Exit CancelCustomer Alarm Interface Auto DialCustomer Alarm Interface Programmable Output Relay Board #Remote LED Board # Relay Assignments STD SET User DefinedSTD SET Prog Relay # UP Down ADD Remove Clear ExitNavigating Protocol Manual TransferBattery Management Battery TestAuto Test Battery Cycle Battery DurationBattery Equalizer MIN MAX WeeksEnabled Disabled AutoManual Stop StartBattery Temp Compensation Charge TemperatureBattery Temperature Compensation Charge Equalize Time PeriodBattery Temp Compensation Battery Cycle MonitorBattery Cycle Monitor Summary Clear BCMClear Summary YES / no Seconds Discharge Cycles SummaryTime Down Battery Time Low Warning BATT. EOD Lower SET Point BATT. EOD Upper SET PointBattery Supplement BATT. Time LOW WarningAuto Restart Alarm Notifications Auto Restart Trigger ConditionSystem Status System Status MonitoringSystem Status Sign OFF Date 10/30/01Next Prev Save & Exit Sign OFF Date 10/30/02Accumulated Backup Hours Accumulated Operating Hours on UPSAccumulated Operating Hours on Bypass Accumulated # of Brown OutsFaults, Alarms, Status FaultsAlarm / Fault Name F E Delay On Battery Input Contact #1UP Down Description L Latching...D DialSummary Alarm Messages Alarms, functions, and corrective actionsContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Communication Interfaces Status1 RS-232 Port Local Reporting Terminal Worldwide ReportingAuto-Dial Requesting Information Dial Out PagerRemote Alarm Status Panel SiteScanSetting Up External Communication Devices Load on BypassOK to Transfer Input Power Failure Load on Battery Momentary OverloadsAutomatic Operations OverloadsAutomatic Transfers to Bypass Automatic Re-transfers to UPSAutomatic Module Off Line Maintenance Routine Maintenance Battery MaintenanceRecord Log Air FiltersBattery Safety Precautions Battery voltage record Torque RequirementsReporting a Problem Detecting TroubleCorrective Actions Recommended Test EquipmentMaintenance 101 Maintenance 102 Page Ne t