Liebert 30-130kVA manual This is a summary event based on

Page 87

Operation

Table 7

Alarms, functions, and corrective actions (continued)

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

 

 

 

 

 

 

 

Displayed

 

Description

Fault

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

This is a summary event based on the

 

 

 

 

 

 

 

 

detection of at least one of these faults

 

 

 

 

 

 

 

 

being active: Battery Overcharge; DC

 

 

 

 

 

 

 

 

Overvoltage Steady State; DC Overvoltage

Rectifier Fail

 

Rectifier Fail

Fault

YES

YES

YES

YES

Transient; DC Undervoltage Steady State;

 

 

 

 

 

 

 

 

Delta-Wye Current Imbalance; Rectifier

 

 

 

 

 

 

 

 

Fuse Fail; Rectifier Drive 1 Fail; Rectifier

 

 

 

 

 

 

 

 

Drive 2 Fail. All actions are controlled by the

 

 

 

 

 

 

 

 

causal fault.

 

 

 

 

 

 

 

 

This is a summary event based on the

 

 

 

 

 

 

 

 

detection of at least one of the following;

Inverter Fail

 

Inverter Fail

Fault

YES

YES

YES

YES

IDC Peak; IGBT Drive Fail; Output

 

Overvoltage Transfer; Output Undervoltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer; Inverter DC Offset. All actions are

 

 

 

 

 

 

 

 

controlled by the causal faults.

 

 

 

 

 

 

 

 

An Equipment Over-temperature condition

 

 

Overtemp

 

 

 

 

 

has persisted for more than 10 minutes.

Ovtemp time-

 

 

 

 

 

The load is transferred to the bypass line

Time-out

Fault

YES

YES

NO

YES

out Sd

 

and the UPS module is shut down. Check

 

Shutdown

 

 

 

 

 

 

 

 

 

 

 

 

the air intake, air exhaust, and filters before

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

attempting to start-up the UPS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A transfer to Static Bypass was

Transfer

 

Transfer Failed

Fault

YES

YES

YES

YES

unsuccessfully attempted and power to the

Failed Sd

 

Shutdown

load was lost. Attempt to restart the system.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact Liebert Global Services.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicates that the unit has transferred to

 

 

 

 

 

 

 

 

SBS without the knowledge of the UPSC. It

Ctrl Fault

 

Controller fault

 

 

 

 

 

occurs when the UPSC’s Watchdog Fail

 

Fault

YES

YES

NO

YES

line is automatically asserted during a

SBS on

 

SBS on

 

 

 

 

 

 

UPSC reset. This is a permanent (latched)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condition which requires service. Contact

 

 

 

 

 

 

 

 

Liebert Global Services at once.

 

 

 

 

 

 

 

 

At least one of the following alarm

 

 

 

 

 

 

 

 

conditions is present: Inverter Fault,

 

 

 

 

 

 

 

 

Rectifier Fuse Blown, Reverse Power, Over

 

 

Hardware

 

 

 

 

 

load Shutdown, logic power supply failure,

Hardware Sd

Fault

YES

NO

NO

YES

or inverter output symmetry failure. The

Shutdown

 

 

 

 

 

 

 

load automatically transfers to the bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

line. The UPS module is shut down and

 

 

 

 

 

 

 

 

isolated. Contact Liebert Global Services at

 

 

 

 

 

 

 

 

once. Do not attempt to reset the UPS.

Opt pwr

 

Option Power

 

 

 

 

 

The Option Power Supply has failed.

 

Fault

YES

YES

NO

YES

Remote Alarm Status panels may be

supply Fail

 

Supply Fail

 

 

 

 

 

 

disabled. Contact Liebert Global Service.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

79

Image 87
Contents Npower UPS Page Table of Contents Communication Interfaces MaintenanceFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Versatility Safety PrecautionsFactory Backup and Service Assistance ReliabilityRecharge Input Power FailureModes Of Operation Normal Load On UPSMimic Display CHGSYS. Status Options Operator ControlsBattery System General Component DescriptionUPS Module Detailed Component Descriptions Controls HardwareFirmware Operation Input Power FactorBattery Charging Circuit Rectifier/ChargerOperation After End-of-discharge Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitStatic Switch Backfeed Protection Nonlinear Load CharacteristicsUnbalanced Load Characteristics Static Bypass SwitchTransfer and Retransfer Conditions Operation Operation Navigation Buttons Operator Control PanelRotary switch Rotary SwitchPrev Cancel Save & Exit ConfigurationUser Settings Security Access and PasswordsMenu Tree Display Screens and ProceduresSecondary Screens Primary ScreensMimic Display Screen Main Menu ScreenDischg FaultsFaults / Alarms RectSYS. Status Mimic DisplayTemps DEG C Inlet AIR Outlet AIR Heat Sinks DC BUS / Battery StatusInput Status FreqFreq .9 HZ 213 214 Phase Diff Bypass Input StatusOutput Load Status EXI T Active Faults and AlarmsFaults and Alarms User ShutdownNext System RatingsManual Startup Second ScenarioAuto Startup Skip Abort Input Modify Current Limit Target and Ramp ValuesModify DC BUS SET Point Target and Ramp Values ServExternal maintenance bypass switch, dual-input UPS SIB External Maintenance BypassExternal maintenance bypass switch, single-input UPS External Maintenance Bypass Switch Configurations Multiple Battery CabinetsShutdown User ShutdownStatus Reports Status ReportsSystem Status History LOG Clear History Logs Clear Event LOGEvent LOG TotalEvent Log Output History LOG02 / 10 OUT-V IN-V Load FreqInput of / UF SBS Line Trap SBS LoadExit Configuration ScreensPrev DC BUS VoltsInput Frequency Output FrequencyCurrent Date System SettingsCancel Save & Exit System SettingsTime Next PREV. Cancel Save & ExitCurrent Time Order NumberOutput Transformer Bypass WIND. no Enter PasswordSingle / Dual Input DualOptions 10% Passive Filter SettingsOptions Active Filter LBS Generator Auto RestartPrev Exit Pulse Rectifier Battery GND Fault Green MachineAlternate Power Pole FAN no Line Drop CompensationCommunication Options Auto DialNext Exit Auto Dial YES Auto Dial OUT Pager Pager Support ConfigurationPager Enabled Pager Number Pager PIN Modem Health CheckPREV. Cancel Next PREV. Cancel 10 % Passive Filter Settings Factory SettingsNext Cancel Freeze Alarm MaskLatching DialSave & Exit Cancel Alarm / Fault NameAlarm / Fault Name Battery Fuse Fail Alarm / Fault Name F EAuto Dial Customer Alarm InterfaceCustomer Alarm Interface Programmable Output Relay Board #Remote LED Board # Relay Assignments STD SET User DefinedSTD SET UP Down ADD Remove Clear Exit Prog Relay #Manual Transfer Navigating ProtocolBattery Test Battery ManagementAuto Test MIN MAX Weeks Battery CycleBattery Duration Battery EqualizerStop Start Enabled DisabledAuto ManualEqualize Time Period Battery Temp Compensation ChargeTemperature Battery Temperature Compensation ChargeBattery Cycle Monitor Battery Temp CompensationBattery Cycle Monitor Summary Clear BCMClear Summary YES / no Seconds Discharge Cycles SummaryTime Down BATT. EOD Lower SET Point BATT. EOD Upper SET Point Battery Time Low WarningBattery Supplement BATT. Time LOW WarningAuto Restart Auto Restart Trigger Condition Alarm NotificationsSystem Status Monitoring System StatusSign OFF Date 10/30/02 System StatusSign OFF Date 10/30/01 Next Prev Save & ExitAccumulated # of Brown Outs Accumulated Backup HoursAccumulated Operating Hours on UPS Accumulated Operating Hours on BypassFaults Faults, Alarms, StatusDescription L Latching...D Dial Alarm / Fault Name F E DelayOn Battery Input Contact #1 UP DownSummary Alarms, functions, and corrective actions Alarm MessagesContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Status Communication Interfaces1 RS-232 Port Local Reporting Terminal Worldwide ReportingAuto-Dial Dial Out Pager Requesting InformationSiteScan Remote Alarm Status PanelSetting Up External Communication Devices Load on BypassOK to Transfer Momentary Overloads Input Power Failure Load on BatteryAutomatic Re-transfers to UPS Automatic OperationsOverloads Automatic Transfers to BypassAutomatic Module Off Line Maintenance Air Filters Routine MaintenanceBattery Maintenance Record LogBattery Safety Precautions Torque Requirements Battery voltage recordRecommended Test Equipment Reporting a ProblemDetecting Trouble Corrective ActionsMaintenance 101 Maintenance 102 Page Ne t