Operation
Table 7 | Alarms, functions, and corrective actions (continued) |
| |||||||
|
|
|
|
|
|
|
|
| |
Actual |
|
|
|
|
|
|
|
| |
Alarm/fault |
|
|
|
|
|
|
|
| |
Name |
|
|
|
|
|
|
|
| |
Displayed |
| Description | Fault |
|
|
|
|
| |
On Front |
| of Alarm/ | Or | Latch | Dial | Freeze | Event Log |
| |
Panel |
| Fault | Alarm | Mask | Mask | Mask | Mask | Meaning and Corrective Action(s) | |
|
|
|
|
|
|
|
| This is a summary event based on the | |
|
|
|
|
|
|
|
| detection of at least one of these faults | |
|
|
|
|
|
|
|
| being active: Battery Overcharge; DC | |
|
|
|
|
|
|
|
| Overvoltage Steady State; DC Overvoltage | |
Rectifier Fail |
| Rectifier Fail | Fault | YES | YES | YES | YES | Transient; DC Undervoltage Steady State; | |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Fuse Fail; Rectifier Drive 1 Fail; Rectifier | |
|
|
|
|
|
|
|
| Drive 2 Fail. All actions are controlled by the | |
|
|
|
|
|
|
|
| causal fault. | |
|
|
|
|
|
|
|
| This is a summary event based on the | |
|
|
|
|
|
|
|
| detection of at least one of the following; | |
Inverter Fail |
| Inverter Fail | Fault | YES | YES | YES | YES | IDC Peak; IGBT Drive Fail; Output | |
| Overvoltage Transfer; Output Undervoltage | ||||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Transfer; Inverter DC Offset. All actions are | |
|
|
|
|
|
|
|
| controlled by the causal faults. | |
|
|
|
|
|
|
|
| An Equipment | |
|
| Overtemp |
|
|
|
|
| has persisted for more than 10 minutes. | |
Ovtemp time- |
|
|
|
|
| The load is transferred to the bypass line | |||
Fault | YES | YES | NO | YES | |||||
out Sd |
| and the UPS module is shut down. Check | |||||||
| Shutdown |
|
|
|
|
| |||
|
|
|
|
|
|
| the air intake, air exhaust, and filters before | ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| attempting to | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| A transfer to Static Bypass was | |
Transfer |
| Transfer Failed | Fault | YES | YES | YES | YES | unsuccessfully attempted and power to the | |
Failed Sd |
| Shutdown | load was lost. Attempt to restart the system. | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| Contact Liebert Global Services. | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Indicates that the unit has transferred to | |
|
|
|
|
|
|
|
| SBS without the knowledge of the UPSC. It | |
Ctrl Fault |
| Controller fault |
|
|
|
|
| occurs when the UPSC’s Watchdog Fail | |
| Fault | YES | YES | NO | YES | line is automatically asserted during a | |||
SBS on |
| SBS on | |||||||
|
|
|
|
|
| UPSC reset. This is a permanent (latched) | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| condition which requires service. Contact | |
|
|
|
|
|
|
|
| Liebert Global Services at once. | |
|
|
|
|
|
|
|
| At least one of the following alarm | |
|
|
|
|
|
|
|
| conditions is present: Inverter Fault, | |
|
|
|
|
|
|
|
| Rectifier Fuse Blown, Reverse Power, Over | |
|
| Hardware |
|
|
|
|
| load Shutdown, logic power supply failure, | |
Hardware Sd | Fault | YES | NO | NO | YES | or inverter output symmetry failure. The | |||
Shutdown | |||||||||
|
|
|
|
|
|
| load automatically transfers to the bypass | ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| line. The UPS module is shut down and | |
|
|
|
|
|
|
|
| isolated. Contact Liebert Global Services at | |
|
|
|
|
|
|
|
| once. Do not attempt to reset the UPS. | |
Opt pwr |
| Option Power |
|
|
|
|
| The Option Power Supply has failed. | |
| Fault | YES | YES | NO | YES | Remote Alarm Status panels may be | |||
supply Fail |
| Supply Fail | |||||||
|
|
|
|
|
| disabled. Contact Liebert Global Service. | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
79