Operation

3.3.2Startup

There are two start up scenarios which can be followed depending on whether there is already power supplied to the UPS and the UPS is on Bypass, or there is no power to the UPS. Follow the appropri- ate instructions.

First Scenario

Power is not supplied to the UPS (Upstream breakers are open). Locate the Rotary Switch located on the inside of the cabinet on the lower right side as you face the cabinet. Turn the Rotary Switch to the Normal position. For a Single Input unit close the upstream breaker so that power is applied to the UPS. For Dual Input units close both the Input and Bypass line breakers so that power is applied to the Input of the UPS and the Bypass line. At this time, power will be applied to the load through the internal static bypass.

Figure 21 System ratings screen

SYSTEM RATINGS

KVA

40

SYSTEM POWER FACTOR

0.8

INPUT VOLTS

480

OUTPUT VOLTS

208

BYPASS VOLTS

480

NEXT

EXIT

As soon as power is applied, you will see the SYSTEM RATINGS screen (Figure 21). These are the ratings of the unit that were programmed in at the factory. Using the arrow keys highlight SAVE & EXIT and push the SELECT button. This will advance you to the USER SETTINGS screen. The USER SETTINGS have been pre-set at the factory. However, they may be customized for your site. See 3.3.5 - Configuration Screens for detail information on configuration screens. You can change these configurations at any time. Use the arrow keys to move the cursor to SAVE & EXIT and push SELECT. This will move you to the MIMIC screen that will look like Figure 22. You are now ready to follow the instructions for automatic start up; see Auto Startup on page 28. Service technicians may alternately use the Manual Start Up procedure for troubleshooting purposes in Manual Startup on page 29.

Figure 22 Mimic display screen with load on bypass and switches closed

MIMIC DISPLAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RECT.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INV.

 

 

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYS STATUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

Image 35
Contents Npower UPS Page Table of Contents Communication Interfaces MaintenanceFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Versatility Safety PrecautionsFactory Backup and Service Assistance ReliabilityRecharge Input Power FailureModes Of Operation Normal Load On UPSSYS. Status Mimic DisplayCHG Options Operator ControlsUPS Module Battery SystemGeneral Component Description Firmware Detailed Component DescriptionsControls Hardware Operation Input Power FactorBattery Charging Circuit Rectifier/ChargerOperation After End-of-discharge Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitStatic Switch Backfeed Protection Nonlinear Load CharacteristicsUnbalanced Load Characteristics Static Bypass SwitchTransfer and Retransfer Conditions Operation Operation Navigation Buttons Operator Control PanelRotary switch Rotary SwitchPrev Cancel Save & Exit ConfigurationUser Settings Security Access and PasswordsMenu Tree Display Screens and ProceduresSecondary Screens Primary ScreensMimic Display Screen Main Menu ScreenDischg FaultsFaults / Alarms RectSYS. Status Mimic DisplayTemps DEG C Inlet AIR Outlet AIR Heat Sinks DC BUS / Battery StatusInput Status FreqOutput Load Status Freq .9 HZ 213 214 Phase DiffBypass Input Status EXI T Active Faults and AlarmsFaults and Alarms User ShutdownNext System RatingsAuto Startup Manual StartupSecond Scenario Skip Abort Input Modify Current Limit Target and Ramp ValuesModify DC BUS SET Point Target and Ramp Values ServExternal maintenance bypass switch, dual-input UPS SIB External Maintenance BypassExternal maintenance bypass switch, single-input UPS External Maintenance Bypass Switch Configurations Multiple Battery CabinetsShutdown User ShutdownStatus Reports Status ReportsSystem Status History LOG Clear History Logs Clear Event LOGEvent Log Event LOGTotal Output History LOG02 / 10 OUT-V IN-V Load FreqInput of / UF SBS Line Trap SBS LoadExit Configuration ScreensPrev DC BUS VoltsInput Frequency Output FrequencyCurrent Date System SettingsCancel Save & Exit System SettingsTime Next PREV. Cancel Save & ExitCurrent Time Order NumberOutput Transformer Bypass WIND. no Enter PasswordSingle / Dual Input DualOptions 10% Passive Filter SettingsOptions Active Filter LBS Generator Auto RestartPrev Exit Pulse Rectifier Battery GND Fault Green MachineAlternate Power Pole FAN no Line Drop CompensationNext Exit Communication OptionsAuto Dial Auto Dial YES Auto Dial OUT Pager Pager Support ConfigurationPager Enabled Pager Number Pager PIN Modem Health CheckPREV. Cancel Next PREV. Cancel Next Cancel 10 % Passive Filter SettingsFactory Settings Freeze Alarm MaskLatching DialSave & Exit Cancel Alarm / Fault NameAlarm / Fault Name Battery Fuse Fail Alarm / Fault Name F EAuto Dial Customer Alarm InterfaceRemote LED Board # Customer Alarm InterfaceProgrammable Output Relay Board # STD SET Relay AssignmentsSTD SET User Defined UP Down ADD Remove Clear Exit Prog Relay #Manual Transfer Navigating ProtocolBattery Test Battery ManagementAuto Test MIN MAX Weeks Battery CycleBattery Duration Battery EqualizerStop Start Enabled DisabledAuto ManualEqualize Time Period Battery Temp Compensation ChargeTemperature Battery Temperature Compensation ChargeBattery Cycle Monitor Battery Temp CompensationClear Summary YES / no Battery Cycle MonitorSummary Clear BCM Time Down Seconds Discharge CyclesSummary BATT. EOD Lower SET Point BATT. EOD Upper SET Point Battery Time Low WarningAuto Restart Battery SupplementBATT. Time LOW Warning Auto Restart Trigger Condition Alarm NotificationsSystem Status Monitoring System StatusSign OFF Date 10/30/02 System StatusSign OFF Date 10/30/01 Next Prev Save & ExitAccumulated # of Brown Outs Accumulated Backup HoursAccumulated Operating Hours on UPS Accumulated Operating Hours on BypassFaults Faults, Alarms, StatusDescription L Latching...D Dial Alarm / Fault Name F E DelayOn Battery Input Contact #1 UP DownSummary Alarms, functions, and corrective actions Alarm MessagesContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Status Communication InterfacesAuto-Dial 1 RS-232 Port Local Reporting TerminalWorldwide Reporting Dial Out Pager Requesting InformationSiteScan Remote Alarm Status PanelOK to Transfer Setting Up External Communication DevicesLoad on Bypass Momentary Overloads Input Power Failure Load on BatteryAutomatic Re-transfers to UPS Automatic OperationsOverloads Automatic Transfers to BypassAutomatic Module Off Line Maintenance Air Filters Routine MaintenanceBattery Maintenance Record LogBattery Safety Precautions Torque Requirements Battery voltage recordRecommended Test Equipment Reporting a ProblemDetecting Trouble Corrective ActionsMaintenance 101 Maintenance 102 Page Ne t