Liebert 30-130kVA manual Battery Management, Battery Test

Page 65

Operation

Figure 82 Manual transfer / retransfer screen when transfer is not allowed

MANUAL TRANSFER / RETRANSFER

BYPASS

NOT OK

INVERTER

OK

INTERNAL BYPASS SWITCH

NORMAL

EXT. MAINT. SWITCH

ON-LINE

INVERTER

IN SYNC

TRANSFER NOT ALLOWED

OK

EXIT

In the figure above, the message “TRANSFER NOT ALLOWED” will be flashing.

3.3.7Battery Management

The Battery Management screens display information on battery self tests, battery equalization, bat- tery temperature, and battery cycle monitoring. This information enables the operator to immediately see the effects of load shedding on time remaining and to accurately assess remaining power resources. The Battery Management screen is accessed from the Main Menu.

Figure 83 Battery management screen

BATTERY MANAGEMENT

BATTERY TEST

BATTERY EQUALIZER

BATTERY TEMP COMPENSATION CHARGE

BATTERY CYCLE MONITOR

BATTERY TIME REMAINING

CANCEL

SAVE & EXIT

Battery Test

The Battery Test screen allows the Operator to select between Auto Test and Manual Test.

Figure 84 Battery test screen

BATTERY TEST

MANUAL TEST

LAST BATTERY TEST: BATTERY TEST PASSED

EXIT

The auto battery self test can be enabled / disabled from the Battery Test Screen. It is performed unattended by programming Time, Date, Test Cycle and Test Duration in Battery Self Test Screen. Selecting MANUAL TEST from the Battery Test screen will perform an Operator-initiated test.

57

Image 65
Contents Npower UPS Page Table of Contents Communication Interfaces MaintenanceFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Factory Backup and Service Assistance Safety PrecautionsReliability VersatilityModes Of Operation Input Power FailureNormal Load On UPS RechargeSYS. Status Mimic DisplayCHG Options Operator ControlsUPS Module Battery SystemGeneral Component Description Firmware Detailed Component DescriptionsControls Hardware Battery Charging Circuit Input Power FactorRectifier/Charger OperationBattery Charge Current Limiting Battery DisconnectBattery Equalize Charge Circuit Operation After End-of-dischargeUnbalanced Load Characteristics Nonlinear Load CharacteristicsStatic Bypass Switch Static Switch Backfeed ProtectionTransfer and Retransfer Conditions Operation Operation Navigation Buttons Operator Control PanelRotary switch Rotary SwitchUser Settings ConfigurationSecurity Access and Passwords Prev Cancel Save & ExitMenu Tree Display Screens and ProceduresSecondary Screens Primary ScreensMimic Display Screen Main Menu ScreenFaults / Alarms FaultsRect DischgSYS. Status Mimic DisplayInput Status DC BUS / Battery StatusFreq Temps DEG C Inlet AIR Outlet AIR Heat SinksOutput Load Status Freq .9 HZ 213 214 Phase DiffBypass Input Status Faults and Alarms Active Faults and AlarmsUser Shutdown EXI TNext System RatingsAuto Startup Manual StartupSecond Scenario Modify DC BUS SET Point Target and Ramp Values Input Modify Current Limit Target and Ramp ValuesServ Skip AbortExternal maintenance bypass switch, dual-input UPS SIB External Maintenance BypassExternal maintenance bypass switch, single-input UPS External Maintenance Bypass Switch Configurations Multiple Battery CabinetsShutdown User ShutdownSystem Status Status ReportsHistory LOG Clear History Logs Clear Event LOG Status ReportsEvent Log Event LOGTotal 02 / 10 History LOGOUT-V IN-V Load Freq OutputInput of / UF SBS Line Trap SBS LoadExit Configuration ScreensInput Frequency DC BUS VoltsOutput Frequency PrevCancel Save & Exit System SettingsSystem Settings Current DateCurrent Time Next PREV. Cancel Save & ExitOrder Number TimeSingle / Dual Input Enter PasswordDual Output Transformer Bypass WIND. noOptions 10% Passive Filter SettingsActive Filter LBS Generator Auto Restart OptionsAlternate Power Pole FAN no Pulse Rectifier Battery GND Fault Green MachineLine Drop Compensation Prev ExitNext Exit Communication OptionsAuto Dial Pager Enabled Pager Number Pager PIN Pager Support ConfigurationModem Health Check Auto Dial YES Auto Dial OUT PagerPREV. Cancel Next PREV. Cancel Next Cancel 10 % Passive Filter SettingsFactory Settings Latching Alarm MaskDial FreezeAlarm / Fault Name Battery Fuse Fail Alarm / Fault NameAlarm / Fault Name F E Save & Exit CancelAuto Dial Customer Alarm InterfaceRemote LED Board # Customer Alarm InterfaceProgrammable Output Relay Board # STD SET Relay AssignmentsSTD SET User Defined UP Down ADD Remove Clear Exit Prog Relay #Manual Transfer Navigating ProtocolBattery Test Battery ManagementAuto Test Battery Duration Battery CycleBattery Equalizer MIN MAX WeeksAuto Enabled DisabledManual Stop StartTemperature Battery Temp Compensation ChargeBattery Temperature Compensation Charge Equalize Time PeriodBattery Cycle Monitor Battery Temp CompensationClear Summary YES / no Battery Cycle MonitorSummary Clear BCM Time Down Seconds Discharge CyclesSummary BATT. EOD Lower SET Point BATT. EOD Upper SET Point Battery Time Low WarningAuto Restart Battery SupplementBATT. Time LOW Warning Auto Restart Trigger Condition Alarm NotificationsSystem Status Monitoring System StatusSign OFF Date 10/30/01 System StatusNext Prev Save & Exit Sign OFF Date 10/30/02Accumulated Operating Hours on UPS Accumulated Backup HoursAccumulated Operating Hours on Bypass Accumulated # of Brown OutsFaults Faults, Alarms, StatusOn Battery Input Contact #1 Alarm / Fault Name F E DelayUP Down Description L Latching...D DialSummary Alarms, functions, and corrective actions Alarm MessagesContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Status Communication InterfacesAuto-Dial 1 RS-232 Port Local Reporting TerminalWorldwide Reporting Dial Out Pager Requesting InformationSiteScan Remote Alarm Status PanelOK to Transfer Setting Up External Communication DevicesLoad on Bypass Momentary Overloads Input Power Failure Load on BatteryOverloads Automatic OperationsAutomatic Transfers to Bypass Automatic Re-transfers to UPSAutomatic Module Off Line Maintenance Battery Maintenance Routine MaintenanceRecord Log Air FiltersBattery Safety Precautions Torque Requirements Battery voltage recordDetecting Trouble Reporting a ProblemCorrective Actions Recommended Test EquipmentMaintenance 101 Maintenance 102 Page Ne t