Liebert 30-130kVA Nonlinear Load Characteristics, Unbalanced Load Characteristics, Load Transfers

Page 20

Theory of Operation

Nonlinear Load Characteristics

Computers and computer equipment with switching power supplies generate nonlinear currents rich in fifth and seventh harmonics.

The inverter pulse-width-modulated waveform, coupled with the output filter, provides a natural path for reducing the fifth and seventh harmonic currents produced by the load. The inverter/filter limits the output voltage THD to less than 3% with up to 100% typical electronic data processing (EDP) loads. EDP equipment characteristically includes both nonlinear and linear load components.

Unbalanced Load Characteristics

Unbalanced loads are actively regulated. The phase-to-phase voltage balance is maintained to within 2%, even with a 50% load imbalance.

2.2.5Static Bypass Switch

A static bypass switch is an integral part of the UPS. An automatic transfer control circuit senses the status of the operator controls, UPS logic signals and alarm messages, and critical bus operating con- ditions. If the inverter output can no longer supply the critical load, the static bypass switch automat- ically transfers the critical load to the bypass source without interruption.

Static Switch Backfeed Protection

The static bypass system is equipped with redundant disconnect circuits that prevent backfeed of lethal voltage to the bypass input in the event of a shorted static switch SCR. If a shorted SCR is detected, the static bypass switch is isolated and an alarm is annunciated at the UPS control panel, while the critical load remains on UPS output power.

Pulsed Parallel Operation

When an overload condition such as magnetic inrush current or a branch load circuit fault exceeds 200% of the full-load current rating, the static bypass switch pulses on for 10 cycles. This allows up to 6000 amperes from the bypass line to clear the overload without a complete transfer to bypass (a Lie- bert design exclusive). The bypass source is in parallel with the UPS system, permitting the bypass source to carry the initial overload current. If the overload clears before 10 cycles, a load transfer to bypass is not made. If the overload condition continues to exceed the inverter capacity, the automatic transfer is made (maintaining the load voltage within the specified limits).

Load Transfers

Transfers to (transfer) or from (retransfer) the bypass may be performed automatically or manually in a make-before-break (MBB) sequence.

Manual load transfers and retransfers are initiated by the Operator from the UPS Control Panel.

Automatic transfers are initiated by the UPS system control logic when an overload is beyond the specified capabilities of the UPS inverter or when a fault occurs within the UPS module. An auto- matic retransfer is initiated if this function is enabled and if system conditions for a retransfer are present.

12

Image 20
Contents Npower UPS Page Table of Contents Maintenance Communication InterfacesFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Safety Precautions Factory Backup and Service AssistanceReliability VersatilityInput Power Failure Modes Of OperationNormal Load On UPS RechargeSYS. Status Mimic DisplayCHG Operator Controls OptionsUPS Module Battery SystemGeneral Component Description Firmware Detailed Component DescriptionsControls Hardware Input Power Factor Battery Charging CircuitRectifier/Charger OperationBattery Disconnect Battery Charge Current LimitingBattery Equalize Charge Circuit Operation After End-of-dischargeNonlinear Load Characteristics Unbalanced Load CharacteristicsStatic Bypass Switch Static Switch Backfeed ProtectionTransfer and Retransfer Conditions Operation Operation Operator Control Panel Navigation ButtonsRotary Switch Rotary switchConfiguration User SettingsSecurity Access and Passwords Prev Cancel Save & ExitDisplay Screens and Procedures Menu TreePrimary Screens Secondary ScreensMain Menu Screen Mimic Display ScreenFaults Faults / AlarmsRect DischgMimic Display SYS. StatusDC BUS / Battery Status Input StatusFreq Temps DEG C Inlet AIR Outlet AIR Heat SinksOutput Load Status Freq .9 HZ 213 214 Phase DiffBypass Input Status Active Faults and Alarms Faults and AlarmsUser Shutdown EXI TSystem Ratings NextAuto Startup Manual StartupSecond Scenario Input Modify Current Limit Target and Ramp Values Modify DC BUS SET Point Target and Ramp ValuesServ Skip AbortSIB External Maintenance Bypass External maintenance bypass switch, dual-input UPSExternal maintenance bypass switch, single-input UPS Multiple Battery Cabinets External Maintenance Bypass Switch ConfigurationsUser Shutdown ShutdownStatus Reports System StatusHistory LOG Clear History Logs Clear Event LOG Status ReportsEvent Log Event LOGTotal History LOG 02 / 10OUT-V IN-V Load Freq OutputSBS Line Trap SBS Load Input of / UFConfiguration Screens ExitDC BUS Volts Input FrequencyOutput Frequency PrevSystem Settings Cancel Save & ExitSystem Settings Current DateNext PREV. Cancel Save & Exit Current TimeOrder Number TimeEnter Password Single / Dual InputDual Output Transformer Bypass WIND. no10% Passive Filter Settings OptionsActive Filter LBS Generator Auto Restart OptionsPulse Rectifier Battery GND Fault Green Machine Alternate Power Pole FAN noLine Drop Compensation Prev ExitNext Exit Communication OptionsAuto Dial Pager Support Configuration Pager Enabled Pager Number Pager PINModem Health Check Auto Dial YES Auto Dial OUT PagerPREV. Cancel Next PREV. Cancel Next Cancel 10 % Passive Filter SettingsFactory Settings Alarm Mask LatchingDial FreezeAlarm / Fault Name Alarm / Fault Name Battery Fuse FailAlarm / Fault Name F E Save & Exit CancelCustomer Alarm Interface Auto DialRemote LED Board # Customer Alarm InterfaceProgrammable Output Relay Board # STD SET Relay AssignmentsSTD SET User Defined Prog Relay # UP Down ADD Remove Clear ExitNavigating Protocol Manual TransferBattery Management Battery TestAuto Test Battery Cycle Battery DurationBattery Equalizer MIN MAX WeeksEnabled Disabled AutoManual Stop StartBattery Temp Compensation Charge TemperatureBattery Temperature Compensation Charge Equalize Time PeriodBattery Temp Compensation Battery Cycle MonitorClear Summary YES / no Battery Cycle MonitorSummary Clear BCM Time Down Seconds Discharge CyclesSummary Battery Time Low Warning BATT. EOD Lower SET Point BATT. EOD Upper SET PointAuto Restart Battery SupplementBATT. Time LOW Warning Alarm Notifications Auto Restart Trigger ConditionSystem Status System Status MonitoringSystem Status Sign OFF Date 10/30/01Next Prev Save & Exit Sign OFF Date 10/30/02Accumulated Backup Hours Accumulated Operating Hours on UPSAccumulated Operating Hours on Bypass Accumulated # of Brown OutsFaults, Alarms, Status FaultsAlarm / Fault Name F E Delay On Battery Input Contact #1UP Down Description L Latching...D DialSummary Alarm Messages Alarms, functions, and corrective actionsContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Communication Interfaces StatusAuto-Dial 1 RS-232 Port Local Reporting TerminalWorldwide Reporting Requesting Information Dial Out PagerRemote Alarm Status Panel SiteScanOK to Transfer Setting Up External Communication DevicesLoad on Bypass Input Power Failure Load on Battery Momentary OverloadsAutomatic Operations OverloadsAutomatic Transfers to Bypass Automatic Re-transfers to UPSAutomatic Module Off Line Maintenance Routine Maintenance Battery MaintenanceRecord Log Air FiltersBattery Safety Precautions Battery voltage record Torque RequirementsReporting a Problem Detecting TroubleCorrective Actions Recommended Test EquipmentMaintenance 101 Maintenance 102 Page Ne t