Operation
Alarm Messages
The alarm message area displays the alarm conditions that are present within the UPS system. The table below shows the default values of masks for each alarm/fault, the meaning of the Alarm and possible corrective actions.
The following information applies to the table.
1.Latch Masks, Dial Masks and unshaded Event log masks may be changed by the user. The user may not change any Freeze Masks.
2.The default alarm names for Input Contact 1 through Input Contact 8 can be modified by the user.
Table 7 | Alarms, functions, and corrective actions |
|
| ||||||
|
|
|
|
|
|
|
|
| |
Actual |
|
|
|
|
|
|
|
| |
Alarm/fault |
|
|
|
|
|
|
|
| |
Name |
| Description | Fault |
|
|
|
|
| |
Displayed |
|
|
|
|
|
| |||
On Front |
| of Alarm/ | Or | Latch | Dial | Freeze | Event Log |
| |
Panel |
| Fault | Alarm | Mask | Mask | Mask | Mask | Meaning and Corrective Action(s) | |
|
|
|
|
|
|
|
| Control Logic has determined that the | |
|
|
|
|
|
|
|
| battery breaker(s) is closed and the battery | |
Battery Fuse |
| Battery Fuse | Fault | YES | YES | NO | YES | fuse has been open for 10 seconds or | |
Fail |
| Fail | longer. Battery | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| available. Liebert Global Services should | |
|
|
|
|
|
|
|
| be called immediately. | |
|
|
|
|
|
|
|
| Control Logic has determined that the | |
|
|
|
|
|
|
|
| battery breaker(s) is closed and the battery | |
|
|
|
|
|
|
|
| voltage has dropped below the End of | |
|
|
|
|
|
|
|
| Discharge limit. The UPS will transfer to | |
|
|
|
|
|
|
|
| bypass. If the transfer is successful, the | |
Battery Low |
| Battery Low |
|
|
|
|
| UPS will be shut down. If the transfer was | |
| Fault | YES | YES | YES | YES | unsuccessful, logic will attempt to complete | |||
xfer |
| Transfer | |||||||
|
|
|
|
|
| a System Shutdown before control power is | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| lost. Verify that input power is now available | |
|
|
|
|
|
|
|
| and restart the UPS following the | |
|
|
|
|
|
|
|
| instructions in this manual. If the system | |
|
|
|
|
|
|
|
| fails to restart properly contact Liebert | |
|
|
|
|
|
|
|
| Global Services. | |
|
|
|
|
|
|
|
| DC bus voltage is 15% or more over the | |
DC Ov |
| DC Overvolt |
|
|
|
|
| nominal DC Bus Voltage. The UPS will | |
| Fault | YES | YES | NO | YES | transfer the load to Bypass and will shut | |||
Transient |
| Transient | |||||||
|
|
|
|
|
| down and isolate the UPS Module. Contact | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Liebert Global Services immediately | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| The power conductors on the Input line are | |
|
|
|
|
|
|
|
| not wired to the UPS in the required | |
|
|
|
|
|
|
|
| sequence. This alarm should appear only | |
Inp Phase |
| Input Phase | Fault | NO | NO | NO | YES | during initial | |
Rot Error |
| Rotation Error | source power system. Disconnect power | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| from the Input line and correct the wiring. | |
|
|
|
|
|
|
|
| Liebert Global Services must be present | |
|
|
|
|
|
|
|
| during initial | |
|
|
|
|
|
|
|
| At least one fuse has opened. The UPS | |
|
|
|
|
|
|
|
| automatically transfers the critical load to | |
Rectifier Fuse | Rectifier Fuse |
|
|
|
|
| the bypass line. Contactors trip open to | ||
Fault | YES | YES | NO | YES | shut down and isolate the UPS module. | ||||
Fail |
| Fail | |||||||
|
|
|
|
|
| Contact Liebert Global Services | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| immediately. Do not attempt to reset the | |
|
|
|
|
|
|
|
| circuit breakers. |
74