Liebert 30-130kVA manual Alarm Messages, Alarms, functions, and corrective actions

Page 82

Operation

Alarm Messages

The alarm message area displays the alarm conditions that are present within the UPS system. The table below shows the default values of masks for each alarm/fault, the meaning of the Alarm and possible corrective actions.

The following information applies to the table.

1.Latch Masks, Dial Masks and unshaded Event log masks may be changed by the user. The user may not change any Freeze Masks.

2.The default alarm names for Input Contact 1 through Input Contact 8 can be modified by the user.

Table 7

Alarms, functions, and corrective actions

 

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

Description

Fault

 

 

 

 

 

Displayed

 

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

Control Logic has determined that the

 

 

 

 

 

 

 

 

battery breaker(s) is closed and the battery

Battery Fuse

 

Battery Fuse

Fault

YES

YES

NO

YES

fuse has been open for 10 seconds or

Fail

 

Fail

longer. Battery back-up is no longer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

available. Liebert Global Services should

 

 

 

 

 

 

 

 

be called immediately.

 

 

 

 

 

 

 

 

Control Logic has determined that the

 

 

 

 

 

 

 

 

battery breaker(s) is closed and the battery

 

 

 

 

 

 

 

 

voltage has dropped below the End of

 

 

 

 

 

 

 

 

Discharge limit. The UPS will transfer to

 

 

 

 

 

 

 

 

bypass. If the transfer is successful, the

Battery Low

 

Battery Low

 

 

 

 

 

UPS will be shut down. If the transfer was

 

Fault

YES

YES

YES

YES

unsuccessful, logic will attempt to complete

xfer

 

Transfer

 

 

 

 

 

 

a System Shutdown before control power is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lost. Verify that input power is now available

 

 

 

 

 

 

 

 

and restart the UPS following the

 

 

 

 

 

 

 

 

instructions in this manual. If the system

 

 

 

 

 

 

 

 

fails to restart properly contact Liebert

 

 

 

 

 

 

 

 

Global Services.

 

 

 

 

 

 

 

 

DC bus voltage is 15% or more over the

DC Ov

 

DC Overvolt

 

 

 

 

 

nominal DC Bus Voltage. The UPS will

 

Fault

YES

YES

NO

YES

transfer the load to Bypass and will shut

Transient

 

Transient

 

 

 

 

 

 

down and isolate the UPS Module. Contact

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liebert Global Services immediately

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The power conductors on the Input line are

 

 

 

 

 

 

 

 

not wired to the UPS in the required

 

 

 

 

 

 

 

 

sequence. This alarm should appear only

Inp Phase

 

Input Phase

Fault

NO

NO

NO

YES

during initial start-up or after a repair to the

Rot Error

 

Rotation Error

source power system. Disconnect power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from the Input line and correct the wiring.

 

 

 

 

 

 

 

 

Liebert Global Services must be present

 

 

 

 

 

 

 

 

during initial start-up of your UPS System.

 

 

 

 

 

 

 

 

At least one fuse has opened. The UPS

 

 

 

 

 

 

 

 

automatically transfers the critical load to

Rectifier Fuse

Rectifier Fuse

 

 

 

 

 

the bypass line. Contactors trip open to

Fault

YES

YES

NO

YES

shut down and isolate the UPS module.

Fail

 

Fail

 

 

 

 

 

 

Contact Liebert Global Services

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

immediately. Do not attempt to reset the

 

 

 

 

 

 

 

 

circuit breakers.

74

Image 82
Contents Npower UPS Page Table of Contents Maintenance Communication InterfacesFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Reliability Safety PrecautionsFactory Backup and Service Assistance VersatilityNormal Load On UPS Input Power FailureModes Of Operation RechargeCHG Mimic DisplaySYS. Status Operator Controls OptionsGeneral Component Description Battery SystemUPS Module Controls Hardware Detailed Component DescriptionsFirmware Rectifier/Charger Input Power FactorBattery Charging Circuit OperationBattery Equalize Charge Circuit Battery DisconnectBattery Charge Current Limiting Operation After End-of-dischargeStatic Bypass Switch Nonlinear Load CharacteristicsUnbalanced Load Characteristics Static Switch Backfeed ProtectionTransfer and Retransfer Conditions Operation Operation Operator Control Panel Navigation ButtonsRotary Switch Rotary switchSecurity Access and Passwords ConfigurationUser Settings Prev Cancel Save & ExitDisplay Screens and Procedures Menu TreePrimary Screens Secondary ScreensMain Menu Screen Mimic Display ScreenRect FaultsFaults / Alarms DischgMimic Display SYS. StatusFreq DC BUS / Battery StatusInput Status Temps DEG C Inlet AIR Outlet AIR Heat SinksBypass Input Status Freq .9 HZ 213 214 Phase DiffOutput Load Status User Shutdown Active Faults and AlarmsFaults and Alarms EXI TSystem Ratings NextSecond Scenario Manual StartupAuto Startup Serv Input Modify Current Limit Target and Ramp ValuesModify DC BUS SET Point Target and Ramp Values Skip AbortSIB External Maintenance Bypass External maintenance bypass switch, dual-input UPSExternal maintenance bypass switch, single-input UPS Multiple Battery Cabinets External Maintenance Bypass Switch ConfigurationsUser Shutdown ShutdownHistory LOG Clear History Logs Clear Event LOG Status ReportsSystem Status Status ReportsTotal Event LOGEvent Log OUT-V IN-V Load Freq History LOG02 / 10 OutputSBS Line Trap SBS Load Input of / UFConfiguration Screens ExitOutput Frequency DC BUS VoltsInput Frequency PrevSystem Settings System SettingsCancel Save & Exit Current DateOrder Number Next PREV. Cancel Save & ExitCurrent Time TimeDual Enter PasswordSingle / Dual Input Output Transformer Bypass WIND. noActive Filter LBS Generator Auto Restart 10% Passive Filter SettingsOptions OptionsLine Drop Compensation Pulse Rectifier Battery GND Fault Green MachineAlternate Power Pole FAN no Prev ExitAuto Dial Communication OptionsNext Exit Modem Health Check Pager Support ConfigurationPager Enabled Pager Number Pager PIN Auto Dial YES Auto Dial OUT PagerPREV. Cancel Next PREV. Cancel Factory Settings 10 % Passive Filter SettingsNext Cancel Dial Alarm MaskLatching FreezeAlarm / Fault Name F E Alarm / Fault NameAlarm / Fault Name Battery Fuse Fail Save & Exit CancelCustomer Alarm Interface Auto DialProgrammable Output Relay Board # Customer Alarm InterfaceRemote LED Board # STD SET User Defined Relay AssignmentsSTD SET Prog Relay # UP Down ADD Remove Clear ExitNavigating Protocol Manual TransferBattery Management Battery TestAuto Test Battery Equalizer Battery CycleBattery Duration MIN MAX WeeksManual Enabled DisabledAuto Stop StartBattery Temperature Compensation Charge Battery Temp Compensation ChargeTemperature Equalize Time PeriodBattery Temp Compensation Battery Cycle MonitorSummary Clear BCM Battery Cycle MonitorClear Summary YES / no Summary Seconds Discharge CyclesTime Down Battery Time Low Warning BATT. EOD Lower SET Point BATT. EOD Upper SET PointBATT. Time LOW Warning Battery SupplementAuto Restart Alarm Notifications Auto Restart Trigger ConditionSystem Status System Status MonitoringNext Prev Save & Exit System StatusSign OFF Date 10/30/01 Sign OFF Date 10/30/02Accumulated Operating Hours on Bypass Accumulated Backup HoursAccumulated Operating Hours on UPS Accumulated # of Brown OutsFaults, Alarms, Status FaultsUP Down Alarm / Fault Name F E DelayOn Battery Input Contact #1 Description L Latching...D DialSummary Alarm Messages Alarms, functions, and corrective actionsContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Communication Interfaces StatusWorldwide Reporting 1 RS-232 Port Local Reporting TerminalAuto-Dial Requesting Information Dial Out PagerRemote Alarm Status Panel SiteScanLoad on Bypass Setting Up External Communication DevicesOK to Transfer Input Power Failure Load on Battery Momentary OverloadsAutomatic Transfers to Bypass Automatic OperationsOverloads Automatic Re-transfers to UPSAutomatic Module Off Line Maintenance Record Log Routine MaintenanceBattery Maintenance Air FiltersBattery Safety Precautions Battery voltage record Torque RequirementsCorrective Actions Reporting a ProblemDetecting Trouble Recommended Test EquipmentMaintenance 101 Maintenance 102 Page Ne t