Liebert 30-130kVA manual RMS input current has reached

Page 89

Operation

Table 7

Alarms, functions, and corrective actions (continued)

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

 

 

 

 

 

 

 

Displayed

 

Description

Fault

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

For all of these input problems the system

 

 

 

 

 

 

 

 

will supply power from the battery until the

Input

 

Input Over

 

 

 

 

 

end of discharge. At that point single input

 

Alarm

NO

NO

NO

YES

systems will lose power to the load. Dual

OverVoltage

 

Voltage

 

 

 

 

 

 

input systems will attempt to transfer to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bypass if qualified and available. Call

 

 

 

 

 

 

 

 

Liebert Global Services for Assistance.

Input current

 

Input Current

 

 

 

 

 

The RMS input current has reached the

 

Alarm

NO

YES

NO

YES

Input Current Limit setting. Check the UPS

limit

 

Limit

 

 

 

 

 

 

load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The module battery circuit breaker (MBD) is

 

 

 

 

 

 

 

 

open. This circuit breaker might have been

 

 

 

 

 

 

 

 

opened either manually or automatically in

 

 

 

 

 

 

 

 

a UPS shutdown procedure. If the UPS is

Battery CB

 

Battery CB

 

 

 

 

 

operating with this breaker open, the critical

 

Alarm

NO

YES

NO

YES

load is not protected from loss of the utility

Open

 

Open

 

 

 

 

 

 

source power. Manual closure of the battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

breaker is inhibited. You must use the front

 

 

 

 

 

 

 

 

panel to set up the sequence for manual

 

 

 

 

 

 

 

 

battery re-closure. Follow the instructions in

 

 

 

 

 

 

 

 

manual start-up.

 

 

 

 

 

 

 

 

This condition is indicated when the Batt

 

 

Batt sup-

 

 

 

 

 

Discharging and Input Undervoltage alarms

Batt Supp

 

 

 

 

 

 

are simultaneously active. The alarm will

 

plement is

Alarm

NO

YES

NO

YES

Active

 

clear when the Inp. Undervoltage alarm

 

active

 

 

 

 

 

 

 

 

 

 

 

 

clears and/or if the rectifier turns off and/or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

if the Batt Dischg alarm clears.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The bypass is out of sync to a sufficient

 

 

 

 

 

 

 

 

degree that transfer to Static Bypass is

Bypass Sync

 

Bypass Sync

Alarm

NO

YES

NO

YES

inhibited. An interrupted transfer will be

Error

 

Error

permitted only in the case of a critical fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If this alarm persists, contact Liebert Global

 

 

 

 

 

 

 

 

Services.

 

 

 

 

 

 

 

 

One or more bypass voltages is below 80%

 

 

 

 

 

 

 

 

or above 115% of the nominal value. If the

 

 

 

 

 

 

 

 

load is on UPS, and the unit is a dual input

Byp out

 

Bypass

 

 

 

 

 

unit, transfers to bypass will be inhibited. If

 

Voltage Out of

Alarm

NO

YES

NO

YES

the unit is a single input unit, the system will

Tolerance

 

 

Tolerance

 

 

 

 

 

shut down. The Alarm will be cleared 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

seconds after all voltage are again with 85-

 

 

 

 

 

 

 

 

110% of nominal. If the load has been shut

 

 

 

 

 

 

 

 

down, re-start will be required.

 

 

 

 

 

 

 

 

The bypass source has dropped below 35V

 

 

 

 

 

 

 

 

per phase. On single input units, the UPS

 

 

 

 

 

 

 

 

will shut down. On dual input units, transfer

Bypass Line

 

Bypass Line

Alarm

NO

YES

NO

YES

to the bypass will be inhibited. The alarm

Fail

 

Fail

will be cleared five seconds after all

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltages again exceed 45V. If the unit is

 

 

 

 

 

 

 

 

already on Bypass when this occurs, power

 

 

 

 

 

 

 

 

to the load will be lost.

81

Image 89
Contents Npower UPS Page Table of Contents Communication Interfaces MaintenanceFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Factory Backup and Service Assistance Safety PrecautionsReliability VersatilityModes Of Operation Input Power FailureNormal Load On UPS RechargeSYS. Status Mimic DisplayCHG Options Operator ControlsUPS Module Battery SystemGeneral Component Description Firmware Detailed Component DescriptionsControls Hardware Battery Charging Circuit Input Power FactorRectifier/Charger OperationBattery Charge Current Limiting Battery DisconnectBattery Equalize Charge Circuit Operation After End-of-dischargeUnbalanced Load Characteristics Nonlinear Load CharacteristicsStatic Bypass Switch Static Switch Backfeed ProtectionTransfer and Retransfer Conditions Operation Operation Navigation Buttons Operator Control PanelRotary switch Rotary SwitchUser Settings ConfigurationSecurity Access and Passwords Prev Cancel Save & ExitMenu Tree Display Screens and ProceduresSecondary Screens Primary ScreensMimic Display Screen Main Menu ScreenFaults / Alarms FaultsRect DischgSYS. Status Mimic DisplayInput Status DC BUS / Battery StatusFreq Temps DEG C Inlet AIR Outlet AIR Heat SinksOutput Load Status Freq .9 HZ 213 214 Phase DiffBypass Input Status Faults and Alarms Active Faults and AlarmsUser Shutdown EXI TNext System RatingsAuto Startup Manual StartupSecond Scenario Modify DC BUS SET Point Target and Ramp Values Input Modify Current Limit Target and Ramp ValuesServ Skip AbortExternal maintenance bypass switch, dual-input UPS SIB External Maintenance BypassExternal maintenance bypass switch, single-input UPS External Maintenance Bypass Switch Configurations Multiple Battery CabinetsShutdown User ShutdownSystem Status Status ReportsHistory LOG Clear History Logs Clear Event LOG Status ReportsEvent Log Event LOGTotal 02 / 10 History LOGOUT-V IN-V Load Freq OutputInput of / UF SBS Line Trap SBS LoadExit Configuration ScreensInput Frequency DC BUS VoltsOutput Frequency PrevCancel Save & Exit System SettingsSystem Settings Current DateCurrent Time Next PREV. Cancel Save & ExitOrder Number TimeSingle / Dual Input Enter PasswordDual Output Transformer Bypass WIND. noOptions 10% Passive Filter SettingsActive Filter LBS Generator Auto Restart OptionsAlternate Power Pole FAN no Pulse Rectifier Battery GND Fault Green MachineLine Drop Compensation Prev ExitNext Exit Communication OptionsAuto Dial Pager Enabled Pager Number Pager PIN Pager Support ConfigurationModem Health Check Auto Dial YES Auto Dial OUT PagerPREV. Cancel Next PREV. Cancel Next Cancel 10 % Passive Filter SettingsFactory Settings Latching Alarm MaskDial FreezeAlarm / Fault Name Battery Fuse Fail Alarm / Fault NameAlarm / Fault Name F E Save & Exit CancelAuto Dial Customer Alarm InterfaceRemote LED Board # Customer Alarm InterfaceProgrammable Output Relay Board # STD SET Relay AssignmentsSTD SET User Defined UP Down ADD Remove Clear Exit Prog Relay #Manual Transfer Navigating ProtocolBattery Test Battery ManagementAuto Test Battery Duration Battery CycleBattery Equalizer MIN MAX WeeksAuto Enabled DisabledManual Stop StartTemperature Battery Temp Compensation ChargeBattery Temperature Compensation Charge Equalize Time PeriodBattery Cycle Monitor Battery Temp CompensationClear Summary YES / no Battery Cycle MonitorSummary Clear BCM Time Down Seconds Discharge CyclesSummary BATT. EOD Lower SET Point BATT. EOD Upper SET Point Battery Time Low WarningAuto Restart Battery SupplementBATT. Time LOW Warning Auto Restart Trigger Condition Alarm NotificationsSystem Status Monitoring System StatusSign OFF Date 10/30/01 System StatusNext Prev Save & Exit Sign OFF Date 10/30/02Accumulated Operating Hours on UPS Accumulated Backup HoursAccumulated Operating Hours on Bypass Accumulated # of Brown OutsFaults Faults, Alarms, StatusOn Battery Input Contact #1 Alarm / Fault Name F E DelayUP Down Description L Latching...D DialSummary Alarms, functions, and corrective actions Alarm MessagesContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Status Communication InterfacesAuto-Dial 1 RS-232 Port Local Reporting TerminalWorldwide Reporting Dial Out Pager Requesting InformationSiteScan Remote Alarm Status PanelOK to Transfer Setting Up External Communication DevicesLoad on Bypass Momentary Overloads Input Power Failure Load on BatteryOverloads Automatic OperationsAutomatic Transfers to Bypass Automatic Re-transfers to UPSAutomatic Module Off Line Maintenance Battery Maintenance Routine MaintenanceRecord Log Air FiltersBattery Safety Precautions Torque Requirements Battery voltage recordDetecting Trouble Reporting a ProblemCorrective Actions Recommended Test EquipmentMaintenance 101 Maintenance 102 Page Ne t