Liebert 30-130kVA manual Navigating Protocol, Manual Transfer

Page 64

Operation

Navigating Protocol

For the screen above and others like it, the normal screen navigation rules are changed. It is impor- tant to differentiate between the selections at the bottom of the display screen (UP/DOWN/ADD/ REMOVE/CLEAR/EXIT) and the navigation buttons or arrow keys below the display screen. To scroll up the Alarm/Fault list, use the arrow keys to highlight the UP selection at the bottom of the display screen. Next, press the SELECT navigation button. Continue this sequence until you have positioned the proper Alarm/Fault in the active position at the top of the list. To scroll down the list, use the arrow key to highlight the DOWN selection at the bottom of the display screen. Next, press the SELECT navigation. Continue until the proper alarm is positioned at the top of the list.

When the selected Alarm/Fault is in the active position at the top of the list, it will be flashing. To attach this alarm to a Programmable Relay, use the arrow keys to highlight ADD at the bottom of the display screen. Press SELECT and your selection will now appear in the right hand box.

You may attach up to four alarms to each relay by following this procedure. Since there are almost 200 alarms, it is advised that you review the entire list and note which alarms you want connected to each relay before beginning your selections. Keep in mind that if you attach more than 1 alarm to the relay, and the relay is triggered, you will not be advised which of the alarms is activated. You may be able to determine this through other diagnostic features of the Npower, but it will not be evident from this feature.

If you decide to remove an alarm from the selected alarm set, scroll the list to put the alarm you want to remove in the top (flashing) position on the ALARM/FAULT NAME list. Use the arrow keys to move the cursor to REMOVE. Press SELECT to remove the alarm from the right hand (connected) list.

If you wish to clear all the alarms and start over, move the cursor to CLEAR and press SELECT.

After you have selected the alarms you want connected to PROG RELAY #1 use the arrow keys to move the cursor to EXIT, press SELECT. This will put you back to the PROGRAMMABLE OUTPUT RELAY BOARD # 1 screen. Follow the procedure above to program the next relay. When all of the relays you wish to program have been completed, highlight SAVE & EXIT and press SELECT.

! CAUTION

You must select save & exit from the programmable output relay board screen or your selections will not be saved.

If you have a second relay board installed, from the CUSTOMER ALARM INTERFACE screen, repeat the same procedures for RELAY BOARD # 2.

3.3.6Manual Transfer

The Manual Transfer screen allows the Operator to transfer the critical load to and from bypass through the static bypass switch. This screen can only be accessed when the rotary switch is on Nor- mal position. To access the screen, start at the MAIN MENU. Highlight MANUAL TRANSFER and press SELECT. There are 3 status options for the Inverter: In sync, lag x degrees, and lead x degrees.

The message Retransfer to UPS or Transfer to Bypass will appear depending on status of the critical load. The Operator can proceed with the transfer/retransfer by highlighting OK and pressing SELECT or EXIT. If a transfer or retransfer is not allowed, the FLASHING message Transfer Not Allowed is displayed and the only option is to Exit. If the Operator chooses to Exit, the screen returns to the Main Menu.

Figure 81 Manual transfer / retransfer screen when transfer is allowed

MANUAL TRANSFER / RETRANSFER

BYPASS

OK

 

INVERTER

OK

 

INT. BYP. SWITCH

NORMAL

 

EXT. MAINT. SWITCH

ON-LINE

 

INVERTER LAG 1 DEGREE

 

 

 

TRANSFER TO BYPASS

EXIT

 

OK

 

 

 

56

Image 64
Contents Npower UPS Page Table of Contents Maintenance Communication InterfacesFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Safety Precautions Factory Backup and Service AssistanceReliability VersatilityInput Power Failure Modes Of OperationNormal Load On UPS RechargeCHG Mimic DisplaySYS. Status Operator Controls OptionsGeneral Component Description Battery SystemUPS Module Controls Hardware Detailed Component DescriptionsFirmware Input Power Factor Battery Charging CircuitRectifier/Charger OperationBattery Disconnect Battery Charge Current LimitingBattery Equalize Charge Circuit Operation After End-of-dischargeNonlinear Load Characteristics Unbalanced Load CharacteristicsStatic Bypass Switch Static Switch Backfeed ProtectionTransfer and Retransfer Conditions Operation Operation Operator Control Panel Navigation ButtonsRotary Switch Rotary switchConfiguration User SettingsSecurity Access and Passwords Prev Cancel Save & ExitDisplay Screens and Procedures Menu TreePrimary Screens Secondary ScreensMain Menu Screen Mimic Display ScreenFaults Faults / AlarmsRect DischgMimic Display SYS. StatusDC BUS / Battery Status Input StatusFreq Temps DEG C Inlet AIR Outlet AIR Heat SinksBypass Input Status Freq .9 HZ 213 214 Phase DiffOutput Load Status Active Faults and Alarms Faults and AlarmsUser Shutdown EXI TSystem Ratings NextSecond Scenario Manual StartupAuto Startup Input Modify Current Limit Target and Ramp Values Modify DC BUS SET Point Target and Ramp ValuesServ Skip AbortSIB External Maintenance Bypass External maintenance bypass switch, dual-input UPSExternal maintenance bypass switch, single-input UPS Multiple Battery Cabinets External Maintenance Bypass Switch ConfigurationsUser Shutdown ShutdownStatus Reports System StatusHistory LOG Clear History Logs Clear Event LOG Status ReportsTotal Event LOGEvent Log History LOG 02 / 10OUT-V IN-V Load Freq OutputSBS Line Trap SBS Load Input of / UFConfiguration Screens ExitDC BUS Volts Input FrequencyOutput Frequency PrevSystem Settings Cancel Save & ExitSystem Settings Current DateNext PREV. Cancel Save & Exit Current TimeOrder Number TimeEnter Password Single / Dual InputDual Output Transformer Bypass WIND. no10% Passive Filter Settings OptionsActive Filter LBS Generator Auto Restart OptionsPulse Rectifier Battery GND Fault Green Machine Alternate Power Pole FAN noLine Drop Compensation Prev ExitAuto Dial Communication OptionsNext Exit Pager Support Configuration Pager Enabled Pager Number Pager PINModem Health Check Auto Dial YES Auto Dial OUT PagerPREV. Cancel Next PREV. Cancel Factory Settings 10 % Passive Filter SettingsNext Cancel Alarm Mask LatchingDial FreezeAlarm / Fault Name Alarm / Fault Name Battery Fuse FailAlarm / Fault Name F E Save & Exit CancelCustomer Alarm Interface Auto DialProgrammable Output Relay Board # Customer Alarm InterfaceRemote LED Board # STD SET User Defined Relay AssignmentsSTD SET Prog Relay # UP Down ADD Remove Clear ExitNavigating Protocol Manual TransferBattery Management Battery TestAuto Test Battery Cycle Battery DurationBattery Equalizer MIN MAX WeeksEnabled Disabled AutoManual Stop StartBattery Temp Compensation Charge TemperatureBattery Temperature Compensation Charge Equalize Time PeriodBattery Temp Compensation Battery Cycle MonitorSummary Clear BCM Battery Cycle MonitorClear Summary YES / no Summary Seconds Discharge CyclesTime Down Battery Time Low Warning BATT. EOD Lower SET Point BATT. EOD Upper SET PointBATT. Time LOW Warning Battery SupplementAuto Restart Alarm Notifications Auto Restart Trigger ConditionSystem Status System Status MonitoringSystem Status Sign OFF Date 10/30/01Next Prev Save & Exit Sign OFF Date 10/30/02Accumulated Backup Hours Accumulated Operating Hours on UPSAccumulated Operating Hours on Bypass Accumulated # of Brown OutsFaults, Alarms, Status FaultsAlarm / Fault Name F E Delay On Battery Input Contact #1UP Down Description L Latching...D DialSummary Alarm Messages Alarms, functions, and corrective actionsContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Communication Interfaces StatusWorldwide Reporting 1 RS-232 Port Local Reporting TerminalAuto-Dial Requesting Information Dial Out PagerRemote Alarm Status Panel SiteScanLoad on Bypass Setting Up External Communication DevicesOK to Transfer Input Power Failure Load on Battery Momentary OverloadsAutomatic Operations OverloadsAutomatic Transfers to Bypass Automatic Re-transfers to UPSAutomatic Module Off Line Maintenance Routine Maintenance Battery MaintenanceRecord Log Air FiltersBattery Safety Precautions Battery voltage record Torque RequirementsReporting a Problem Detecting TroubleCorrective Actions Recommended Test EquipmentMaintenance 101 Maintenance 102 Page Ne t