Operation
Table 7 | Alarms, functions, and corrective actions (continued) |
| |||||||
|
|
|
|
|
|
|
|
| |
Actual |
|
|
|
|
|
|
|
| |
Alarm/fault |
|
|
|
|
|
|
| ||
Name |
|
|
|
|
|
|
|
| |
Displayed | Description | Fault |
|
|
|
|
| ||
On Front |
| of Alarm/ | Or | Latch | Dial | Freeze | Event Log |
| |
Panel |
| Fault | Alarm | Mask | Mask | Mask | Mask | Meaning and Corrective Action(s) | |
|
|
|
|
|
|
|
| The instantaneous inverter current of any | |
|
|
|
|
|
|
|
| one phase has exceeded its Pulse by Pulse | |
|
|
|
|
|
|
|
| current limit value. An “Inverter Current | |
|
|
|
|
|
|
|
| Limit” alarm was already issued and pulse | |
|
|
|
|
|
|
|
| parallel operation was initiated. At the end | |
|
|
|
|
|
|
|
| of pulse parallel the load current has not be | |
|
| Inverter |
|
|
|
|
| reduced below 150% The load will transfer | |
Inv I limit xfer | Current Limit | Fault | NO | YES | NO | YES | to Static Bypass. If the fault or over load | ||
|
| Transfer |
|
|
|
|
| clears the unit will retransfer to UPS. Check | |
|
|
|
|
|
|
|
| the total load compared to the UPS rating, | |
|
|
|
|
|
|
|
| reduce load where necessary. If the UPS | |
|
|
|
|
|
|
|
| does not retransfer when the load is below | |
|
|
|
|
|
|
|
| 100% of the rated load or if the unit shuts | |
|
|
|
|
|
|
|
| down, contact Liebert Global Services | |
|
|
|
|
|
|
|
| Immediately. | |
|
|
|
|
|
|
|
| With the battery breaker closed and the | |
|
|
|
|
|
|
|
| Battery Overtemp…Breaker Trip” option | |
|
|
|
|
|
|
|
| enabled, the internal battery temperature | |
|
|
|
|
|
|
|
| has exceeded its Maximum set point value. | |
|
|
|
|
|
|
|
| The battery UV trip will be activate and the | |
|
| Battery |
|
|
|
|
| battery will be disconnected from the UPS. | |
Batt ovtemp |
|
|
|
|
| Battery Back up is no longer available. | |||
Overtemp CB | Fault | YES | YES | NO | YES | ||||
cb trip |
| Check the battery to determine the possible | |||||||
| Trip |
|
|
|
|
| |||
|
|
|
|
|
|
| cause of the overload and remove if | ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| possible. Once the battery has cooled | |
|
|
|
|
|
|
|
| below the set point temperature, the battery | |
|
|
|
|
|
|
|
| may be brought on line again. If the | |
|
|
|
|
|
|
|
| problem recurs contact Liebert Global | |
|
|
|
|
|
|
|
| Services. | |
|
|
|
|
|
|
|
| With BGF option installed, BGF breaker trip | |
|
|
|
|
|
|
|
| enabled, and batt breaker closed, Comms | |
Batt gnd | CB | Batt gnd fault |
|
|
|
|
| DPS sees its BGF input asserted by the | |
Fault | NO | YES | NO | YES | SWGR. It will issue a batt breaker UV trip | ||||
trip |
| CB trip | |||||||
|
|
|
|
|
| and motor op disable. To correct, repair and | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| restart batt via the MM. Contact Liebert | |
|
|
|
|
|
|
|
| Global Services for assistance. | |
|
|
|
|
|
|
|
| With Bypass source available, the UPS has | |
|
|
|
|
|
|
|
| determined that the bypass power supply | |
Byp pwr |
| Bypass Power |
|
|
|
|
| has failed. The SBS will be turned off and | |
| Fault | NO | YES | NO | YES | the contactors opened. SBS will not be | |||
supply fail | Supply Fail | ||||||||
|
|
|
|
| available. This fault will inhibit transfers and | ||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| immediately. | |
|
|
|
|
|
|
|
| The Emergency Power Off switch has been | |
|
|
|
|
|
|
|
| pressed, which caused the UPS system to | |
EPO |
| EPO |
|
|
|
|
| shut down and remove all power from the | |
| Fault | NO | YES | NO | YES | critical load. Determine the cause of the | |||
shutdown |
| Shutdown | |||||||
|
|
|
|
|
| emergency condition and correct it if | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| possible. Contact Liebert Global Services if | |
|
|
|
|
|
|
|
| you require assistance. |