Liebert 30-130kVA manual With the load on UPS, PhaseB output KVA

Page 91

Operation

Table 7

Alarms, functions, and corrective actions (continued)

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

 

 

 

 

 

 

 

Displayed

 

Description

Fault

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

With the load on UPS, PhaseB output KVA

 

 

 

 

 

 

 

 

or KW or RMS current has exceeded 105%

 

 

Inverter

 

 

 

 

 

of the nominal per phase rating. The UPS

Inv Ovld

 

 

 

 

 

 

will begin sending the time remaining until a

 

Overload

Alarm

NO

YES

NO

YES

Phase C

 

transfer or shutdown will occur, per the

 

Phase C

 

 

 

 

 

 

 

 

 

 

 

 

Overload vs. Time Curve. The alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condition will clear when the overload

 

 

 

 

 

 

 

 

returns to below the nominal rating.

 

 

Low Power

 

 

 

 

 

On any output phase that is supplying at

Low Pwr

 

 

 

 

 

 

least 15% of its rated KVA, the measured

 

Factor

Alarm

NO

YES

NO

YES

Factor Warn

 

output power factor is below 0.50, leading

 

Warning

 

 

 

 

 

 

 

 

 

 

 

 

or lagging.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With the load being supplied by the inverter,

 

 

 

 

 

 

 

 

the measured load current exceeds the

 

 

 

 

 

 

 

 

auto-Parallel Current Limit or the Pulse-by-

 

 

 

 

 

 

 

 

Pulse Current Limit set point values. If the

Pulse

 

Pulse Parallel

 

 

 

 

 

Static Bypass is available, the SBS supplies

 

Alarm

NO

YES

NO

YES

supplemental power. If at the end of 10

Paralleling

 

Activated

 

 

 

 

 

 

cycles the load current has not returned to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

below 105%, the Static Bypass will be left

 

 

 

 

 

 

 

 

on and the inverter will be turned off. If the

 

 

 

 

 

 

 

 

over current has cleared the Inverter will be

 

 

 

 

 

 

 

 

left on and the SBS will be turned off.

 

 

 

 

 

 

 

 

After performing a recoverable transfer to

 

 

 

 

 

 

 

 

bypass, with Auto Rexfer enabled, the Auto

 

 

 

 

 

 

 

 

Rexfer time out (default=5minutes) has

 

 

Auto

 

 

 

 

 

elapsed before retransfer could be

Auto rexfer

 

 

 

 

 

 

performed. A manual retransfer must be

 

Retransfer

Alarm

YES

YES

NO

YES

failed

 

performed, which will then clear the lockout

 

Failed

 

 

 

 

 

 

 

 

 

 

 

 

and zero the retransfer/ hour counter. If the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

manual transfer is inhibited, the Inverter

 

 

 

 

 

 

 

 

may be latched off due to another fault.

 

 

 

 

 

 

 

 

Contact Liebert Global Services.

 

 

 

 

 

 

 

 

The UPS has determined that the actual

 

 

 

 

 

 

 

 

number of Auto Retransfers in the past hour

 

 

 

 

 

 

 

 

has exceeded the permitted maximum.

Excessive

 

Excessive

 

 

 

 

 

(user settable, default=5). This alarm

 

Auto

Alarm

YES

YES

NO

YES

should not be issued if auto retransfers are

Auto Rexfer

 

 

Retransfer

 

 

 

 

 

disabled by setting the maximum attempts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to “0”. A manual retransfer must be

 

 

 

 

 

 

 

 

performed, which will then clear the lockout

 

 

 

 

 

 

 

 

and zero the retransfer/hour counter.

 

 

 

 

 

 

 

 

If the unit is supplying power to an Auxiliary

Aux Power

 

Aux Power Fail

Alarm

NO

YES

NO

YES

device, this alarm indicates that the system

Fail

 

has detected a failure in the Aux. Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

circuit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the unit is supplying power to an Auxiliary

EPO Power

 

EPO Power

Alarm

NO

YES

NO

YES

device, this alarm indicates that the system

Fail

 

Fail

has detected a failure in the Aux. Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

circuit.

 

 

 

 

 

 

 

 

 

LBS Power

 

LBS Power

 

 

 

 

 

Power to the Load Bus Sync circuit has

 

Alarm

NO

YES

NO

YES

been lost. Check external wiring. Contact

Fail

 

Fail

 

 

 

 

 

 

Liebert Global Services.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

83

Image 91
Contents Npower UPS Page Table of Contents Communication Interfaces MaintenanceFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Versatility Safety PrecautionsFactory Backup and Service Assistance ReliabilityRecharge Input Power FailureModes Of Operation Normal Load On UPSCHG Mimic DisplaySYS. Status Options Operator ControlsGeneral Component Description Battery SystemUPS Module Controls Hardware Detailed Component DescriptionsFirmware Operation Input Power FactorBattery Charging Circuit Rectifier/ChargerOperation After End-of-discharge Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitStatic Switch Backfeed Protection Nonlinear Load CharacteristicsUnbalanced Load Characteristics Static Bypass SwitchTransfer and Retransfer Conditions Operation Operation Navigation Buttons Operator Control PanelRotary switch Rotary SwitchPrev Cancel Save & Exit ConfigurationUser Settings Security Access and PasswordsMenu Tree Display Screens and ProceduresSecondary Screens Primary ScreensMimic Display Screen Main Menu ScreenDischg FaultsFaults / Alarms RectSYS. Status Mimic DisplayTemps DEG C Inlet AIR Outlet AIR Heat Sinks DC BUS / Battery StatusInput Status FreqBypass Input Status Freq .9 HZ 213 214 Phase DiffOutput Load Status EXI T Active Faults and AlarmsFaults and Alarms User ShutdownNext System RatingsSecond Scenario Manual StartupAuto Startup Skip Abort Input Modify Current Limit Target and Ramp ValuesModify DC BUS SET Point Target and Ramp Values ServExternal maintenance bypass switch, dual-input UPS SIB External Maintenance BypassExternal maintenance bypass switch, single-input UPS External Maintenance Bypass Switch Configurations Multiple Battery CabinetsShutdown User ShutdownStatus Reports Status ReportsSystem Status History LOG Clear History Logs Clear Event LOGTotal Event LOGEvent Log Output History LOG02 / 10 OUT-V IN-V Load FreqInput of / UF SBS Line Trap SBS LoadExit Configuration ScreensPrev DC BUS VoltsInput Frequency Output FrequencyCurrent Date System SettingsCancel Save & Exit System SettingsTime Next PREV. Cancel Save & ExitCurrent Time Order NumberOutput Transformer Bypass WIND. no Enter PasswordSingle / Dual Input DualOptions 10% Passive Filter SettingsOptions Active Filter LBS Generator Auto RestartPrev Exit Pulse Rectifier Battery GND Fault Green MachineAlternate Power Pole FAN no Line Drop CompensationAuto Dial Communication OptionsNext Exit Auto Dial YES Auto Dial OUT Pager Pager Support ConfigurationPager Enabled Pager Number Pager PIN Modem Health CheckPREV. Cancel Next PREV. Cancel Factory Settings 10 % Passive Filter SettingsNext Cancel Freeze Alarm MaskLatching DialSave & Exit Cancel Alarm / Fault NameAlarm / Fault Name Battery Fuse Fail Alarm / Fault Name F EAuto Dial Customer Alarm InterfaceProgrammable Output Relay Board # Customer Alarm InterfaceRemote LED Board # STD SET User Defined Relay AssignmentsSTD SET UP Down ADD Remove Clear Exit Prog Relay #Manual Transfer Navigating ProtocolBattery Test Battery ManagementAuto Test MIN MAX Weeks Battery CycleBattery Duration Battery EqualizerStop Start Enabled DisabledAuto ManualEqualize Time Period Battery Temp Compensation ChargeTemperature Battery Temperature Compensation ChargeBattery Cycle Monitor Battery Temp CompensationSummary Clear BCM Battery Cycle MonitorClear Summary YES / no Summary Seconds Discharge CyclesTime Down BATT. EOD Lower SET Point BATT. EOD Upper SET Point Battery Time Low WarningBATT. Time LOW Warning Battery SupplementAuto Restart Auto Restart Trigger Condition Alarm NotificationsSystem Status Monitoring System StatusSign OFF Date 10/30/02 System StatusSign OFF Date 10/30/01 Next Prev Save & ExitAccumulated # of Brown Outs Accumulated Backup HoursAccumulated Operating Hours on UPS Accumulated Operating Hours on BypassFaults Faults, Alarms, StatusDescription L Latching...D Dial Alarm / Fault Name F E DelayOn Battery Input Contact #1 UP DownSummary Alarms, functions, and corrective actions Alarm MessagesContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Status Communication InterfacesWorldwide Reporting 1 RS-232 Port Local Reporting TerminalAuto-Dial Dial Out Pager Requesting InformationSiteScan Remote Alarm Status PanelLoad on Bypass Setting Up External Communication DevicesOK to Transfer Momentary Overloads Input Power Failure Load on BatteryAutomatic Re-transfers to UPS Automatic OperationsOverloads Automatic Transfers to BypassAutomatic Module Off Line Maintenance Air Filters Routine MaintenanceBattery Maintenance Record LogBattery Safety Precautions Torque Requirements Battery voltage recordRecommended Test Equipment Reporting a ProblemDetecting Trouble Corrective ActionsMaintenance 101 Maintenance 102 Page Ne t