Liebert 30-130kVA manual Auto Test

Page 66

Operation

The following conditions and features apply to either Auto or Manual Mode:

If you go to the battery screen, it will indicate “Battery Test in Progress”. When the test is com- plete, the indication “Last Battery Test” will either say “Battery Test Passed” or “Battery Test Failed.”

One of two alarms are logged in the event log screen: “Battery Test Passed” or “Battery Test Failed”. If failed, there will be accompanying alarm messages in the event log to describe the rea- son for failure. (i.e. Battery Recharging). “Battery Test Failed” message is also latched in the active alarm/fault window of the Mimic screen.

There are a number of pre-conditions which must exist before it is possible to start a battery test:

The Battery CB, Input and Output contactors must all be closed.

All phases of Input and Bypass volts must be within defined limits of 80% to 115%.

Battery Charge must be greater than 90%.

The test is interlocked to “Batt Ov Temp Warning” alarm. When this alarm is present, battery test won’t start.

DC volts must be greater than the DC Bus Float Voltage of 540 VDC.

A load must be greater than 15% of rated kVA.

The On Generator status must be False.

Input frequency must be within limits.

Auto and Manual tests are interlocked; only one can be active at a time.

The recommended default time settings based on the battery size are shown in the table below.

Table 5

Default time settings

 

 

 

Battery Type

Test Duration

 

15 Minute

 

1

Minute

 

 

 

 

 

 

30 Minute

 

2

Minutes

 

 

 

 

 

 

45 Minute

 

3

Minutes

 

 

 

 

 

 

60 Minute

 

4

Minutes

 

 

 

 

 

 

75 Minute

 

5

Minutes

 

 

 

 

 

 

90 Minute

 

6

Minutes

 

 

 

 

 

 

The factory default setting is 60 seconds and can be set between 30 to 900 seconds.

The test starts by commanding the rectifier control circuit to lower the Rectifier output voltage. The rectifier stays on, but is phased back. This means the Rectifier is still available to support the load if the battery fails.

A battery test will be aborted if any of the following become true:

The battery Over-Temperature Warning becomes active.

Battery CB, Input or Output contactors open.

Any phase of the Bypass or Input volts exceeds the limit of 80% and 115%.

If the battery voltage falls too quickly during the test.

Figure 85 Automatic test screen

AUTO TEST

BATT. TEST TIME

01:02:03

BATT. TEST DATE

07/13/00

CYCLE

2

DURATION

30

EXIT

 

 

58

Image 66
Contents Npower UPS Page Table of Contents Maintenance Communication InterfacesFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Reliability Safety PrecautionsFactory Backup and Service Assistance VersatilityNormal Load On UPS Input Power FailureModes Of Operation RechargeMimic Display CHGSYS. Status Operator Controls OptionsBattery System General Component DescriptionUPS Module Detailed Component Descriptions Controls HardwareFirmware Rectifier/Charger Input Power FactorBattery Charging Circuit OperationBattery Equalize Charge Circuit Battery DisconnectBattery Charge Current Limiting Operation After End-of-dischargeStatic Bypass Switch Nonlinear Load CharacteristicsUnbalanced Load Characteristics Static Switch Backfeed ProtectionTransfer and Retransfer Conditions Operation Operation Operator Control Panel Navigation ButtonsRotary Switch Rotary switchSecurity Access and Passwords ConfigurationUser Settings Prev Cancel Save & ExitDisplay Screens and Procedures Menu TreePrimary Screens Secondary ScreensMain Menu Screen Mimic Display ScreenRect FaultsFaults / Alarms DischgMimic Display SYS. StatusFreq DC BUS / Battery StatusInput Status Temps DEG C Inlet AIR Outlet AIR Heat SinksFreq .9 HZ 213 214 Phase Diff Bypass Input StatusOutput Load Status User Shutdown Active Faults and AlarmsFaults and Alarms EXI TSystem Ratings NextManual Startup Second ScenarioAuto Startup Serv Input Modify Current Limit Target and Ramp ValuesModify DC BUS SET Point Target and Ramp Values Skip AbortSIB External Maintenance Bypass External maintenance bypass switch, dual-input UPSExternal maintenance bypass switch, single-input UPS Multiple Battery Cabinets External Maintenance Bypass Switch ConfigurationsUser Shutdown ShutdownHistory LOG Clear History Logs Clear Event LOG Status ReportsSystem Status Status ReportsEvent LOG TotalEvent Log OUT-V IN-V Load Freq History LOG02 / 10 OutputSBS Line Trap SBS Load Input of / UFConfiguration Screens ExitOutput Frequency DC BUS VoltsInput Frequency PrevSystem Settings System SettingsCancel Save & Exit Current DateOrder Number Next PREV. Cancel Save & ExitCurrent Time TimeDual Enter PasswordSingle / Dual Input Output Transformer Bypass WIND. noActive Filter LBS Generator Auto Restart 10% Passive Filter SettingsOptions OptionsLine Drop Compensation Pulse Rectifier Battery GND Fault Green MachineAlternate Power Pole FAN no Prev ExitCommunication Options Auto DialNext Exit Modem Health Check Pager Support ConfigurationPager Enabled Pager Number Pager PIN Auto Dial YES Auto Dial OUT PagerPREV. Cancel Next PREV. Cancel 10 % Passive Filter Settings Factory SettingsNext Cancel Dial Alarm MaskLatching FreezeAlarm / Fault Name F E Alarm / Fault NameAlarm / Fault Name Battery Fuse Fail Save & Exit CancelCustomer Alarm Interface Auto DialCustomer Alarm Interface Programmable Output Relay Board #Remote LED Board # Relay Assignments STD SET User DefinedSTD SET Prog Relay # UP Down ADD Remove Clear ExitNavigating Protocol Manual TransferBattery Management Battery TestAuto Test Battery Equalizer Battery CycleBattery Duration MIN MAX WeeksManual Enabled DisabledAuto Stop StartBattery Temperature Compensation Charge Battery Temp Compensation ChargeTemperature Equalize Time PeriodBattery Temp Compensation Battery Cycle MonitorBattery Cycle Monitor Summary Clear BCMClear Summary YES / no Seconds Discharge Cycles SummaryTime Down Battery Time Low Warning BATT. EOD Lower SET Point BATT. EOD Upper SET PointBattery Supplement BATT. Time LOW WarningAuto Restart Alarm Notifications Auto Restart Trigger ConditionSystem Status System Status MonitoringNext Prev Save & Exit System StatusSign OFF Date 10/30/01 Sign OFF Date 10/30/02Accumulated Operating Hours on Bypass Accumulated Backup HoursAccumulated Operating Hours on UPS Accumulated # of Brown OutsFaults, Alarms, Status FaultsUP Down Alarm / Fault Name F E DelayOn Battery Input Contact #1 Description L Latching...D DialSummary Alarm Messages Alarms, functions, and corrective actionsContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Communication Interfaces Status1 RS-232 Port Local Reporting Terminal Worldwide ReportingAuto-Dial Requesting Information Dial Out PagerRemote Alarm Status Panel SiteScanSetting Up External Communication Devices Load on BypassOK to Transfer Input Power Failure Load on Battery Momentary OverloadsAutomatic Transfers to Bypass Automatic OperationsOverloads Automatic Re-transfers to UPSAutomatic Module Off Line Maintenance Record Log Routine MaintenanceBattery Maintenance Air FiltersBattery Safety Precautions Battery voltage record Torque RequirementsCorrective Actions Reporting a ProblemDetecting Trouble Recommended Test EquipmentMaintenance 101 Maintenance 102 Page Ne t