Liebert 30-130kVA manual Output kVA or kW or RMS current has

Page 90

Operation

Table 7

Alarms, functions, and corrective actions (continued)

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

 

 

 

 

 

 

 

Displayed

 

Description

Fault

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

With the load on Static Bypass, the phase A

 

 

 

 

 

 

 

 

output kVA or kW or RMS current has

 

 

 

 

 

 

 

 

exceeded 115% of the nominal per-phase

SBS Ovld

 

SBS Overload

Alarm

NO

NO

NO

YES

kVA or kW or RMS current rating. The UPS

Phase A

 

Phase A

will show time remaining until a shutdown

 

 

 

 

 

 

 

 

 

 

 

 

 

 

will occur, per the Overload vs. time curve.

 

 

 

 

 

 

 

 

The alarm will clear when the overload falls

 

 

 

 

 

 

 

 

to below 110% of the rating.

 

 

 

 

 

 

 

 

With the load on Static Bypass, the phase B

 

 

 

 

 

 

 

 

output kVA or kW or RMS current has

 

 

 

 

 

 

 

 

exceeded 115% of the nominal per-phase

SBS Ovld

 

SBS Overload

Alarm

NO

NO

NO

YES

kVA or kW or RMS current rating. The UPS

Phase B

 

Phase B

will show time remaining until a shutdown

 

 

 

 

 

 

 

 

 

 

 

 

 

 

will occur, per the Overload vs. time curve.

 

 

 

 

 

 

 

 

The alarm will clear when the overload falls

 

 

 

 

 

 

 

 

to below 110% of the rating.

 

 

 

 

 

 

 

 

With the load on Static Bypass, the phase C

 

 

 

 

 

 

 

 

output kVA or kW or RMS current has

 

 

 

 

 

 

 

 

exceeded 115% of the nominal per-phase

SBS Ovld

 

SBS Overload

Alarm

NO

NO

NO

YES

kVA or kW or RMS current rating. The UPS

Phase C

 

Phase C

will show time remaining until a shutdown

 

 

 

 

 

 

 

 

 

 

 

 

 

 

will occur, per the Overload vs. time curve.

 

 

 

 

 

 

 

 

The alarm will clear when the overload falls

 

 

 

 

 

 

 

 

to below 110% of the rating.

 

 

 

 

 

 

 

 

The instantaneous inverter current of any

Inverter I

 

Inverter

 

 

 

 

 

one phase has exceeded its pulse-by-pulse

 

Alarm

NO

NO

NO

YES

current limit value. The UPS will shutdown

Limit

 

Current Limit

 

 

 

 

 

 

when the Current Overload vs. time curve is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exceeded.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output frequency differs from the nominal

Output OF/UF

Output OF/UF

Alarm

NO

YES

NO

YES

(60Hz) by more than 0.5Hz. No transfer or

shutdown occurs. Contact Liebert Global

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Services at once.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With the load on UPS, Phase x output KVA

 

 

 

 

 

 

 

 

or KW or RMS current has exceeded 105%

 

 

Inverter

 

 

 

 

 

of the nominal per phase rating. The UPS

Inv Ovld

 

 

 

 

 

 

will begin sending the time remaining until a

 

Overload

Alarm

NO

YES

NO

YES

Phase A

 

transfer or shutdown will occur, per the

 

Phase A

 

 

 

 

 

 

 

 

 

 

 

 

Overload vs. Time Curve. The alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condition will clear when the overload

 

 

 

 

 

 

 

 

returns to below the nominal rating.

 

 

 

 

 

 

 

 

With the load on UPS, Phase A output kVA

 

 

 

 

 

 

 

 

or kW or RMS current has exceeded 105%

 

 

Inverter

 

 

 

 

 

of the nominal per phase rating. The UPS

Inv Ovld

 

 

 

 

 

 

will begin sending the time remaining until a

 

Overload

Alarm

NO

YES

NO

YES

Phase B

 

transfer or shutdown will occur, per the

 

Phase B

 

 

 

 

 

 

 

 

 

 

 

 

Overload vs. Time Curve. The alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

condition will clear when the overload

 

 

 

 

 

 

 

 

returns to below the nominal rating.

82

Image 90
Contents Npower UPS Page Table of Contents Maintenance Communication InterfacesFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Reliability Safety PrecautionsFactory Backup and Service Assistance VersatilityNormal Load On UPS Input Power FailureModes Of Operation RechargeMimic Display CHGSYS. Status Operator Controls OptionsBattery System General Component DescriptionUPS Module Detailed Component Descriptions Controls HardwareFirmware Rectifier/Charger Input Power FactorBattery Charging Circuit OperationBattery Equalize Charge Circuit Battery DisconnectBattery Charge Current Limiting Operation After End-of-dischargeStatic Bypass Switch Nonlinear Load CharacteristicsUnbalanced Load Characteristics Static Switch Backfeed ProtectionTransfer and Retransfer Conditions Operation Operation Operator Control Panel Navigation ButtonsRotary Switch Rotary switchSecurity Access and Passwords ConfigurationUser Settings Prev Cancel Save & ExitDisplay Screens and Procedures Menu TreePrimary Screens Secondary ScreensMain Menu Screen Mimic Display ScreenRect FaultsFaults / Alarms DischgMimic Display SYS. StatusFreq DC BUS / Battery StatusInput Status Temps DEG C Inlet AIR Outlet AIR Heat SinksFreq .9 HZ 213 214 Phase Diff Bypass Input StatusOutput Load Status User Shutdown Active Faults and AlarmsFaults and Alarms EXI TSystem Ratings NextManual Startup Second ScenarioAuto Startup Serv Input Modify Current Limit Target and Ramp ValuesModify DC BUS SET Point Target and Ramp Values Skip AbortSIB External Maintenance Bypass External maintenance bypass switch, dual-input UPSExternal maintenance bypass switch, single-input UPS Multiple Battery Cabinets External Maintenance Bypass Switch ConfigurationsUser Shutdown ShutdownHistory LOG Clear History Logs Clear Event LOG Status ReportsSystem Status Status ReportsEvent LOG TotalEvent Log OUT-V IN-V Load Freq History LOG02 / 10 OutputSBS Line Trap SBS Load Input of / UFConfiguration Screens ExitOutput Frequency DC BUS VoltsInput Frequency PrevSystem Settings System SettingsCancel Save & Exit Current DateOrder Number Next PREV. Cancel Save & ExitCurrent Time TimeDual Enter PasswordSingle / Dual Input Output Transformer Bypass WIND. noActive Filter LBS Generator Auto Restart 10% Passive Filter SettingsOptions OptionsLine Drop Compensation Pulse Rectifier Battery GND Fault Green MachineAlternate Power Pole FAN no Prev ExitCommunication Options Auto DialNext Exit Modem Health Check Pager Support ConfigurationPager Enabled Pager Number Pager PIN Auto Dial YES Auto Dial OUT PagerPREV. Cancel Next PREV. Cancel 10 % Passive Filter Settings Factory SettingsNext Cancel Dial Alarm MaskLatching FreezeAlarm / Fault Name F E Alarm / Fault NameAlarm / Fault Name Battery Fuse Fail Save & Exit CancelCustomer Alarm Interface Auto DialCustomer Alarm Interface Programmable Output Relay Board #Remote LED Board # Relay Assignments STD SET User DefinedSTD SET Prog Relay # UP Down ADD Remove Clear ExitNavigating Protocol Manual TransferBattery Management Battery TestAuto Test Battery Equalizer Battery CycleBattery Duration MIN MAX WeeksManual Enabled DisabledAuto Stop StartBattery Temperature Compensation Charge Battery Temp Compensation ChargeTemperature Equalize Time PeriodBattery Temp Compensation Battery Cycle MonitorBattery Cycle Monitor Summary Clear BCMClear Summary YES / no Seconds Discharge Cycles SummaryTime Down Battery Time Low Warning BATT. EOD Lower SET Point BATT. EOD Upper SET PointBattery Supplement BATT. Time LOW WarningAuto Restart Alarm Notifications Auto Restart Trigger ConditionSystem Status System Status MonitoringNext Prev Save & Exit System StatusSign OFF Date 10/30/01 Sign OFF Date 10/30/02Accumulated Operating Hours on Bypass Accumulated Backup HoursAccumulated Operating Hours on UPS Accumulated # of Brown OutsFaults, Alarms, Status FaultsUP Down Alarm / Fault Name F E DelayOn Battery Input Contact #1 Description L Latching...D DialSummary Alarm Messages Alarms, functions, and corrective actionsContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Communication Interfaces Status1 RS-232 Port Local Reporting Terminal Worldwide ReportingAuto-Dial Requesting Information Dial Out PagerRemote Alarm Status Panel SiteScanSetting Up External Communication Devices Load on BypassOK to Transfer Input Power Failure Load on Battery Momentary OverloadsAutomatic Transfers to Bypass Automatic OperationsOverloads Automatic Re-transfers to UPSAutomatic Module Off Line Maintenance Record Log Routine MaintenanceBattery Maintenance Air FiltersBattery Safety Precautions Battery voltage record Torque RequirementsCorrective Actions Reporting a ProblemDetecting Trouble Recommended Test EquipmentMaintenance 101 Maintenance 102 Page Ne t