Liebert 30-130kVA manual See 3.3.7 Battery Management

Page 94

Operation

Table 7

Alarms, functions, and corrective actions (continued)

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

 

 

 

 

 

 

 

Displayed

 

Description

Fault

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

The generator option is installed, the

Delayed Batt

 

Delayed

 

 

 

 

 

system is on generator and the “Delayed

 

Alarm

NO

NO

NO

YES

Battery Charge” is suppressing battery

Charge

 

Battery Charge

 

 

 

 

 

 

 

 

charging to reduce the load on the

 

 

 

 

 

 

 

 

generator.

Reduced I

 

Reduced

 

 

 

 

 

The UPS recognizes that the source is a

 

Alarm

NO

NO

NO

YES

generator and has reduced the current limit

Limit

 

Current Limit

 

 

 

 

 

 

setting to avoid generator overloading.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Per the user request, all event logs have

Event Log

 

Event Log

Alarm

NO

NO

NO

YES

been cleared. This will be the first alarm in

Clear

 

Clear

the new log. Momentary display. Sets flag

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in the event history log.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With the battery breaker closed, the battery

 

 

 

 

 

 

 

 

voltage has not reached 95% of the units

Batt Not

 

Battery Not

 

 

 

 

 

“DC Float Voltage” set point within a

 

Alarm

YES

NO

NO

YES

calculated time (based on the test duration.)

Charging

 

Charging

 

 

 

 

 

 

This calculation will start immediately at the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

end of a successful (“Passed”) battery self

 

 

 

 

 

 

 

 

test.

 

 

 

 

 

 

 

 

The UPS has detected a communication

UPSC-MM

 

UPSC-MM

Alarm

YES

YES

NO

YES

failure between its UPS controls and it

comm. Fail

 

Comm Fail

monitoring system. Contact Liebert Global

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service.

 

 

 

 

 

 

 

 

 

User

 

User

 

 

 

 

 

The User has initiated an “Inverter Off” or

 

Alarm

YES

YES

NO

YES

“System Shutdown” through the User

Shutdown

 

Shutdown

 

 

 

 

 

 

Shutdown screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cant Exec

 

Cannot

 

 

 

 

 

The battery test could not be performed.

 

Execute

Alarm

NO

NO

NO

YES

See 3.3.7 - Battery Management.

Batt Test

 

 

Battery Test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Batt Not

 

Battery Not

Alarm

NO

NO

NO

YES

A battery test cannot be executed because

Charged

 

Charged

the battery charge is less than 90%.

 

 

 

 

 

 

Sys Time Set

System Time

 

 

 

 

 

The User has changed the Date or Time

Set By

Alarm

YES

YES

NO

YES

from the front Panel. Momentary display.

By Op

 

 

Operator

 

 

 

 

 

Sets flag in the event history log.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The User has ordered a manual transfer

Manual XFER

Manual

Alarm

NO

NO

NO

YES

from UPS to Bypass from the front panel

Transfer

controls. Momentary display. Sets flag in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the event history log.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The User has ordered a manual transfer

Manual

 

Manual

Alarm

NO

NO

NO

YES

from Bypass to UPS from the front panel

ReXFER

 

Retransfer

controls. Momentary display. Sets flag in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the event history log.

 

 

 

 

 

 

 

 

 

Batt Cycle

 

 

 

 

 

 

 

With batt breaker closed, Monitor has

 

Battery Cycle

Alarm

NO

NO

NO

YES

determined that the buffer that keeps track

Buff Full

 

Buffer Full

of the number of hits the battery has taken

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is full. No action required.

 

 

 

 

 

 

 

 

 

86

Image 94
Contents Npower UPS Page Table of Contents Maintenance Communication InterfacesFigures Page Tables Page Important Safety Instructions Overview of Manual System Description Reliability Safety PrecautionsFactory Backup and Service Assistance VersatilityNormal Load On UPS Input Power FailureModes Of Operation RechargeCHG Mimic DisplaySYS. Status Operator Controls OptionsGeneral Component Description Battery SystemUPS Module Controls Hardware Detailed Component DescriptionsFirmware Rectifier/Charger Input Power FactorBattery Charging Circuit OperationBattery Equalize Charge Circuit Battery DisconnectBattery Charge Current Limiting Operation After End-of-dischargeStatic Bypass Switch Nonlinear Load CharacteristicsUnbalanced Load Characteristics Static Switch Backfeed ProtectionTransfer and Retransfer Conditions Operation Operation Operator Control Panel Navigation ButtonsRotary Switch Rotary switchSecurity Access and Passwords ConfigurationUser Settings Prev Cancel Save & ExitDisplay Screens and Procedures Menu TreePrimary Screens Secondary ScreensMain Menu Screen Mimic Display ScreenRect FaultsFaults / Alarms DischgMimic Display SYS. StatusFreq DC BUS / Battery StatusInput Status Temps DEG C Inlet AIR Outlet AIR Heat SinksBypass Input Status Freq .9 HZ 213 214 Phase DiffOutput Load Status User Shutdown Active Faults and AlarmsFaults and Alarms EXI TSystem Ratings NextSecond Scenario Manual StartupAuto Startup Serv Input Modify Current Limit Target and Ramp ValuesModify DC BUS SET Point Target and Ramp Values Skip AbortSIB External Maintenance Bypass External maintenance bypass switch, dual-input UPSExternal maintenance bypass switch, single-input UPS Multiple Battery Cabinets External Maintenance Bypass Switch ConfigurationsUser Shutdown ShutdownHistory LOG Clear History Logs Clear Event LOG Status ReportsSystem Status Status ReportsTotal Event LOGEvent Log OUT-V IN-V Load Freq History LOG02 / 10 OutputSBS Line Trap SBS Load Input of / UFConfiguration Screens ExitOutput Frequency DC BUS VoltsInput Frequency PrevSystem Settings System SettingsCancel Save & Exit Current DateOrder Number Next PREV. Cancel Save & ExitCurrent Time TimeDual Enter PasswordSingle / Dual Input Output Transformer Bypass WIND. noActive Filter LBS Generator Auto Restart 10% Passive Filter SettingsOptions OptionsLine Drop Compensation Pulse Rectifier Battery GND Fault Green MachineAlternate Power Pole FAN no Prev ExitAuto Dial Communication OptionsNext Exit Modem Health Check Pager Support ConfigurationPager Enabled Pager Number Pager PIN Auto Dial YES Auto Dial OUT PagerPREV. Cancel Next PREV. Cancel Factory Settings 10 % Passive Filter SettingsNext Cancel Dial Alarm MaskLatching FreezeAlarm / Fault Name F E Alarm / Fault NameAlarm / Fault Name Battery Fuse Fail Save & Exit CancelCustomer Alarm Interface Auto DialProgrammable Output Relay Board # Customer Alarm InterfaceRemote LED Board # STD SET User Defined Relay AssignmentsSTD SET Prog Relay # UP Down ADD Remove Clear ExitNavigating Protocol Manual TransferBattery Management Battery TestAuto Test Battery Equalizer Battery CycleBattery Duration MIN MAX WeeksManual Enabled DisabledAuto Stop StartBattery Temperature Compensation Charge Battery Temp Compensation ChargeTemperature Equalize Time PeriodBattery Temp Compensation Battery Cycle MonitorSummary Clear BCM Battery Cycle MonitorClear Summary YES / no Summary Seconds Discharge CyclesTime Down Battery Time Low Warning BATT. EOD Lower SET Point BATT. EOD Upper SET PointBATT. Time LOW Warning Battery SupplementAuto Restart Alarm Notifications Auto Restart Trigger ConditionSystem Status System Status MonitoringNext Prev Save & Exit System StatusSign OFF Date 10/30/01 Sign OFF Date 10/30/02Accumulated Operating Hours on Bypass Accumulated Backup HoursAccumulated Operating Hours on UPS Accumulated # of Brown OutsFaults, Alarms, Status FaultsUP Down Alarm / Fault Name F E DelayOn Battery Input Contact #1 Description L Latching...D DialSummary Alarm Messages Alarms, functions, and corrective actionsContact Liebert Global Service to check Excess load from the UPS and attempt to EPO Maximum heat sink temperature limit This is a summary event based on Battery is discharging. This occurs RMS input current has reached Output kVA or kW or RMS current has With the load on UPS, PhaseB output KVA Condition only causes an alarm, but should Push-button switch located on See 3.3.7 Battery Management All of the alarms before attempting to Communication Interfaces StatusWorldwide Reporting 1 RS-232 Port Local Reporting TerminalAuto-Dial Requesting Information Dial Out PagerRemote Alarm Status Panel SiteScanLoad on Bypass Setting Up External Communication DevicesOK to Transfer Input Power Failure Load on Battery Momentary OverloadsAutomatic Transfers to Bypass Automatic OperationsOverloads Automatic Re-transfers to UPSAutomatic Module Off Line Maintenance Record Log Routine MaintenanceBattery Maintenance Air FiltersBattery Safety Precautions Battery voltage record Torque RequirementsCorrective Actions Reporting a ProblemDetecting Trouble Recommended Test EquipmentMaintenance 101 Maintenance 102 Page Ne t