Operation
Table 7 | Alarms, functions, and corrective actions (continued) |
| |||||||
|
|
|
|
|
|
|
|
| |
Actual |
|
|
|
|
|
|
|
| |
Alarm/fault |
|
|
|
|
|
|
|
| |
Name |
|
|
|
|
|
|
|
| |
Displayed |
| Description | Fault |
|
|
|
|
| |
On Front |
| of Alarm/ | Or | Latch | Dial | Freeze | Event Log |
| |
Panel |
| Fault | Alarm | Mask | Mask | Mask | Mask | Meaning and Corrective Action(s) | |
|
|
|
|
|
|
|
| The generator option is installed, the | |
Delayed Batt |
| Delayed |
|
|
|
|
| system is on generator and the “Delayed | |
| Alarm | NO | NO | NO | YES | Battery Charge” is suppressing battery | |||
Charge |
| Battery Charge | |||||||
|
|
|
|
|
|
|
| charging to reduce the load on the | |
|
|
|
|
|
|
|
| generator. | |
Reduced I |
| Reduced |
|
|
|
|
| The UPS recognizes that the source is a | |
| Alarm | NO | NO | NO | YES | generator and has reduced the current limit | |||
Limit |
| Current Limit | |||||||
|
|
|
|
|
| setting to avoid generator overloading. | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Per the user request, all event logs have | |
Event Log |
| Event Log | Alarm | NO | NO | NO | YES | been cleared. This will be the first alarm in | |
Clear |
| Clear | the new log. Momentary display. Sets flag | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| in the event history log. | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| With the battery breaker closed, the battery | |
|
|
|
|
|
|
|
| voltage has not reached 95% of the units | |
Batt Not |
| Battery Not |
|
|
|
|
| “DC Float Voltage” set point within a | |
| Alarm | YES | NO | NO | YES | calculated time (based on the test duration.) | |||
Charging |
| Charging | |||||||
|
|
|
|
|
| This calculation will start immediately at the | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| end of a successful (“Passed”) battery self | |
|
|
|
|
|
|
|
| test. | |
|
|
|
|
|
|
|
| The UPS has detected a communication | |
| Alarm | YES | YES | NO | YES | failure between its UPS controls and it | |||
comm. Fail |
| Comm Fail | monitoring system. Contact Liebert Global | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| Service. | |
|
|
|
|
|
|
|
|
| |
User |
| User |
|
|
|
|
| The User has initiated an “Inverter Off” or | |
| Alarm | YES | YES | NO | YES | “System Shutdown” through the User | |||
Shutdown |
| Shutdown | |||||||
|
|
|
|
|
| Shutdown screen. | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
Cant Exec |
| Cannot |
|
|
|
|
| The battery test could not be performed. | |
| Execute | Alarm | NO | NO | NO | YES | See 3.3.7 - Battery Management. | ||
Batt Test |
| ||||||||
| Battery Test |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
Batt Not |
| Battery Not | Alarm | NO | NO | NO | YES | A battery test cannot be executed because | |
Charged |
| Charged | the battery charge is less than 90%. | ||||||
|
|
|
|
|
| ||||
Sys Time Set | System Time |
|
|
|
|
| The User has changed the Date or Time | ||
Set By | Alarm | YES | YES | NO | YES | from the front Panel. Momentary display. | |||
By Op |
| ||||||||
| Operator |
|
|
|
|
| Sets flag in the event history log. | ||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| The User has ordered a manual transfer | |
Manual XFER | Manual | Alarm | NO | NO | NO | YES | from UPS to Bypass from the front panel | ||
Transfer | controls. Momentary display. Sets flag in | ||||||||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| the event history log. | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| The User has ordered a manual transfer | |
Manual |
| Manual | Alarm | NO | NO | NO | YES | from Bypass to UPS from the front panel | |
ReXFER |
| Retransfer | controls. Momentary display. Sets flag in | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| the event history log. | |
|
|
|
|
|
|
|
|
| |
Batt Cycle |
|
|
|
|
|
|
| With batt breaker closed, Monitor has | |
| Battery Cycle | Alarm | NO | NO | NO | YES | determined that the buffer that keeps track | ||
Buff Full |
| Buffer Full | of the number of hits the battery has taken | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| is full. No action required. | |
|
|
|
|
|
|
|
|
|
86