Falcon XG3K-1T, XG1.5K-1T Turning the UPS OFF, UPS Setup Configuration, Green Mode Function BIT

Page 17

TURNING THE UPS OFF

To turn off the UPS:

While in Normal On-line mode, press the BYPASS button for one second. The UPS will go into BYPASS MODE. Next, turn off the INPUT BREAKER. The unit will shut down immediately.

NOTE!

DURING SHUT DOWN, DO NOT PRESS ANY BUTTON SINCE UPS MIGHT BE RE- ENERGIZED AND DELIVER POWER TO ITS OUTPUT UNEXPECTEDLY.

6.0 UPS SETUP CONFIGURATION

This section describes how to reconfigure the internal UPS setup options, by entering the CONFIGURATION MODE. The setup parameters includes: UPS output voltage & enable or disable GREEN MODE.

CAUTION

Never change the voltage settings when the UPS is ON and powering any connected loads.

NOTE!

Setting the UPS output voltage to 100 VAC will derate the UPS output VA and WATTAGE ratings. Please refer to the SPECIFICATIONS located at the end of this manual for information on your specific UPS model.

How To Place The UPS Into Setup/CONFIGURATION Mode

To put the UPS into configuration mode, press the “FUNTION/TEST” and “SET/ALARM SILENCE” buttons at same time and hold them for one second. The unit will emit one audible beep and then enter CONFIGURATION MODE.

 

 

Note that on the display panel, you will see a single row, 8

 

 

BIT column located at the bottom of the display. The most

 

 

right bit is function “BIT 0”, the far left is status “BIT 7”.

 

 

Note that there is an illuminated dot “.” in BIT 0 when the

 

 

unit is in CONFIGURATION MODE.

 

 

Pressing the “FUNCTION/TEST” button will move the dot

 

 

from function BIT 0 to function BIT 6. When selecting

 

 

function BIT 0 through BIT 6, observe whether status BIT

 

 

7 is selected (dot) or deselected (no dot,) for the function

 

 

bit selected. To select (dot) or deselect (no dot) the

 

 

function you are presently in, press the “SET/ALARM

 

BIT 7

SLIENCE” button to set or deselect function BIT 7. Press

 

 

the “SET/ALARM SLIENCE” and FUNCTION/TEST”

 

 

buttons at same time again and hold for one second. The

BIT 7

BIT 0

alarm buzzer will sound one short beep to acknowledge

the UPS has stored the settings.

GREEN MODE (Function BIT 3)

17

Image 17
Contents Owners Operating Manual Table of Contents Storage and Transportation InstallationBattery Introduction Circuit Descriptions Block DiagramInstallation Inspecting the Equipment RACK-MOUNT UPS SetupFREE-STANDING UPS Installation Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation FUNCTION/TEST SET/ALARM Silence BypassDisplay & Controls Indicators and Icons Located on the LCD Display FUNCTION/TEST Button ControlsBattery Mode Normal ON-LINE ModeOperation Operating ModesTurning the UPS on Bypass ModeGreen Mode How To Place The UPS Into Setup/CONFIGURATION Mode UPS Setup ConfigurationGreen Mode Function BIT Turning the UPS OFFConfiguration Mode How to Enable or Disable Green ModeHow to Set the UPS Output Voltage Communications An Example of How to Set the UPS Output Voltage to 115VacPIN # RS-232 PortUA88374 Relay Option Board Standard Dry Contact Interface Card Novell styleUPS and Battery Care MaintenanceWhen to Replace Batteries Battery Pack ReplacementInternal Battery Pack Replacement Recycling the Used Battery Testing NEW BatteriesFuse Replacement Troubleshooting Guide TroubleshootingUPS Troubleshooting GuideWeight DimensionsInternal Battery Pack InputModel Number XG2.2K-1T Battery RUN Times General Provisions Warranty