Falcon XG1.5K-1T, XG2.2K-1T, XG3K-1T manual FREE-STANDING UPS Installation

Page 9

7.Install the slide assemblies, with brackets into the rack enclosure.

The return flanges on the mounting brackets and outer parts fit to the inside of the rack-mounting rails.

8.Make sure the slide assemblies are in the same alignment position on all four rack- mounting rails. After checking alignment, TIGHTEN ALL SCREWS.

9.Insert the UPS, with inner parts attached, into the slide assemblies. You may need to depress the locking mechanisms on the inner and outer parts of the slide assemblies to allow the slides to retract. The UPS should move smoothly forward and backward on the slide assemblies. If not, recheck alignment.

10.Once the UPS is installed in the rack, the load may be connected.

Ensure the load equipment is turned off; plug all loads into the output receptacles on the rear of the UPS. Plug the UPS into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with national and local electrical codes.

Use a 15 amp rated device for 1000, or 1500 VA units, 20 amp for the 2200VA, and 30 amp for 3000VA. The wall receptacle must be grounded.

11.To turn on the UPS switch on the INPUT BREAKER; then turn on the connected equipment.

FREE-STANDING UPS INSTALLATION

When using the XG Series UPS in a free-standing configuration, the XG1.5K-1T model is provided with mounting feet (shown below, left) to stabilize the UPS. The XG2.2K-1T and XG3K-1T models are provided with keyhole hardware to “lock” the units together in free standing mode. This key lock is also required if additional battery packs are added.

9

Image 9
Contents Owners Operating Manual Table of Contents Installation BatteryStorage and Transportation Introduction Circuit Descriptions Block DiagramInstallation RACK-MOUNT UPS Setup FREE-STANDING UPS InstallationInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation SET/ALARM Silence Bypass Display & ControlsFUNCTION/TEST Indicators and Icons Located on the LCD Display FUNCTION/TEST Button ControlsBattery Mode Normal ON-LINE ModeOperation Operating ModesBypass Mode Green ModeTurning the UPS on How To Place The UPS Into Setup/CONFIGURATION Mode UPS Setup ConfigurationGreen Mode Function BIT Turning the UPS OFFHow to Enable or Disable Green Mode How to Set the UPS Output VoltageConfiguration Mode Communications An Example of How to Set the UPS Output Voltage to 115VacPIN # RS-232 PortUA88374 Relay Option Board Standard Dry Contact Interface Card Novell styleUPS and Battery Care MaintenanceWhen to Replace Batteries Battery Pack ReplacementInternal Battery Pack Replacement Recycling the Used Battery Testing NEW BatteriesFuse Replacement Troubleshooting Guide TroubleshootingUPS Troubleshooting GuideWeight DimensionsInternal Battery Pack InputModel Number XG2.2K-1T Battery RUN Times General Provisions Warranty