Falcon XG1.5K-1T, XG2.2K-1T, XG3K-1T manual Battery RUN Times

Page 30

Qty x V x Rating Pack

4 x 12 V x 7.2 AH

ENVIRONMENTAL

 

Operating Temperature

+32oF to +104oF (0oC to +40oC)

Storage Temperature

+5oF to +122oF (-15oC to +50oC)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft (3000m) at 104oF without de-rating

Audible Noise

<45 dbA, at 1 meter from rear

AGENCY

 

Safety

UL 1778, UL Listed

RFI/EMI

FCC Part 15, Subpart B, Class B

Surge Immunity

IEC 61000-4-5 (1995)/IEC 801-5 (1989)

Transportation

ISTA Procedure 1A

COMMUNICATIONS

 

Serial Port

RS-232

Slot

Option for SNMP, USB card or DB 9 card

SOFTWARE

 

UPSILON

Supplied bundled to support Windows 95, 98,

 

NT, ME, 2000, XP

BATTERY RUN TIMES

RUN TIME CHART in Minutes

 

UPS

800VA

1000VA

1500VA

2000VA

3000VA

 

Model

(560W)

(700W)

(1050W)

(1400W)

(2100W)

XG1.5K-1T

13

9

5

 

 

+ 1 Battery Module

62

53

31

 

 

+ 2 Battery Modules

131

96

60

 

 

+ 3 Battery Modules

193

154

92

 

 

XG2,2K-1T

 

 

 

 

 

+ 1 Battery Module

40

27

16

11

 

+ 2 Battery Modules

89

65

47

30

 

+ 3

Battery Modules

159

121

68

56

 

XG3K-1T

 

 

 

 

 

+ 1

Battery Module

38

26

15

10

5

+ 2

Battery Modules

86

63

46

29

16

+ 3

Battery Modules

153

118

67

54

31

NOTE:

1.Approximate discharge time is in minutes and at 77oF (25oC) with a 100% resistive load.

2.For extended battery modules please order them from Falcon Electric Sales.

30

Image 30
Contents Owners Operating Manual Table of Contents Installation BatteryStorage and Transportation Introduction Block Diagram Circuit DescriptionsInstallation RACK-MOUNT UPS Setup FREE-STANDING UPS InstallationInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation SET/ALARM Silence Bypass Display & ControlsFUNCTION/TEST Indicators and Icons Located on the LCD Display Controls FUNCTION/TEST ButtonOperation Normal ON-LINE ModeBattery Mode Operating ModesBypass Mode Green ModeTurning the UPS on Green Mode Function BIT UPS Setup ConfigurationHow To Place The UPS Into Setup/CONFIGURATION Mode Turning the UPS OFFHow to Enable or Disable Green Mode How to Set the UPS Output VoltageConfiguration Mode An Example of How to Set the UPS Output Voltage to 115Vac CommunicationsRS-232 Port PIN #Standard Dry Contact Interface Card Novell style UA88374 Relay Option BoardWhen to Replace Batteries MaintenanceUPS and Battery Care Battery Pack ReplacementInternal Battery Pack Replacement Testing NEW Batteries Recycling the Used BatteryFuse Replacement Troubleshooting Troubleshooting GuideTroubleshooting Guide UPSInternal Battery Pack DimensionsWeight InputModel Number XG2.2K-1T Battery RUN Times Warranty General Provisions