Falcon XG1.5K-1T, XG3K-1T How to Enable or Disable Green Mode, How to Set the UPS Output Voltage

Page 18

Green Mode is a power saving feature that should only be used in non-critical applications. When the Green Mode is enabled and the connected load decreases to less than 3% of the full rated UPS output capacity, the UPS will automatically change from ON-LINE MODE to BYPASS MODE, 30 seconds after the drop in load has been detected. After the UPS has switched to BYPASS MODE, the “GREEN MODE BULB” on the display panel will flash to indicate the UPS is in the energy saving Green Mode. When the load increases to greater than 3% of the UPS’s full output rating, the UPS will automatically return to NORMAL On-line MODE operation.

CAUTION- When green mode is enabled, and the UPS has switched to BYPASS MODE due to a reduction in load, THE UPS WILL NOT GO TO BATTERY MODE IN THE EVENT OF A UTILITY FAILURE. THE CONNECTED LOAD WILL BE DROPPED.

How to Enable or Disable Green Mode

To Enable:

1.Press the “FUNCTION/TEST” and “SET/ALARM SILENCE” buttons at same time and hold them for one second. The unit will sound one beep and then enter the setup

CONFIGURATION MODE.

2.Press the “FUNCTION/TEST” button repeatedly and move the dot from function BIT 0 to function BIT 3 (Green Mode Function).

3.Press the “SET/ALARM SLIENCE” button to set (dot) BIT 7.

4.Press the “SET/ALARM SLIENCE” and “FUNCTION/TEST” buttons at same time again and hold for one second. The alarm buzzer will sound one short beep to acknowledge the UPS has stored the setting.

To Disable: (Factory Default)

1.Press the “FUNCTION/TEST” and “SET/ALARM SILENCE” buttons at same time and hold them for one second. The unit will sound one beep and then enter the setup

CONFIGURATION MODE.

2.Press the “FUNCTION/TEST” button repeatedly and move the dot from function BIT 0 to function BIT 3 (Green Mode Function).

3.Press the “SET/ALARM SLIENCE” button to deselect (no dot) BIT 7.

4.Press the “SET/ALARM SLIENCE” and “FUNCTION/TEST” buttons at same time again and hold for one second. The alarm buzzer will sound one short beep to acknowledge the UPS has stored the setting.

How to Set the UPS Output Voltage

The XG Series UPS is shipped configured from the factory with its output voltage set to 120Vac. For most North American application the UPS output voltage WILL NOT HAVE TO BE CHANGED.

CAUTION: NEVER CHANGE THE UPS OUTPUT VOLTAGE WHILE IT HAS EQUIPMENT CONNECTED TO ITS OUTPUT RECEPTACLES. Make output voltage configuration changes and verify the desired output voltage is present at the UPS output using the UPS output voltage display function. Next verify that all of the equipment to be connected to the UPS will operate satisfactorily on the newly selected output voltage. If in doubt, contact the Falcon Electric Customer Service Department

18

Image 18
Contents Owners Operating Manual Table of Contents Installation BatteryStorage and Transportation Introduction Block Diagram Circuit DescriptionsInstallation RACK-MOUNT UPS Setup FREE-STANDING UPS InstallationInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation SET/ALARM Silence Bypass Display & ControlsFUNCTION/TEST Indicators and Icons Located on the LCD Display Controls FUNCTION/TEST ButtonOperation Normal ON-LINE ModeBattery Mode Operating ModesBypass Mode Green ModeTurning the UPS on Green Mode Function BIT UPS Setup ConfigurationHow To Place The UPS Into Setup/CONFIGURATION Mode Turning the UPS OFFHow to Enable or Disable Green Mode How to Set the UPS Output VoltageConfiguration Mode An Example of How to Set the UPS Output Voltage to 115Vac CommunicationsRS-232 Port PIN #Standard Dry Contact Interface Card Novell style UA88374 Relay Option BoardWhen to Replace Batteries MaintenanceUPS and Battery Care Battery Pack ReplacementInternal Battery Pack Replacement Testing NEW Batteries Recycling the Used BatteryFuse Replacement Troubleshooting Troubleshooting GuideTroubleshooting Guide UPSInternal Battery Pack DimensionsWeight InputModel Number XG2.2K-1T Battery RUN Times Warranty General Provisions