Falcon XG2.2K-1T, XG1.5K-1T, XG3K-1T manual Dimensions, Weight, Input, Output, Internal Battery Pack

Page 28

SPECIFICATIONS

 

Model Number

XG1.5K-1T

 

Model Rating

1500VA/1050W

 

DIMENSIONS

 

 

Unit

 

16.8 x 21.5 x 3.5 (2U)

 

W x D x H in. (mm)

(426 x 546 x 88)

 

Shipping

 

22 x 25.75 x 8.5

 

W x D x H in. (mm)

(560 x 654 x 215)

 

WEIGHT

 

 

 

Unit

lbs (kg)

51 (23.2)

 

Shipping

lbs (kg)

58(26.4)

 

INPUT

 

 

 

Voltage Range

120 VAC nominal; variable based on output load

 

 

 

80 – 138 VAC full load,

 

 

 

60 – 138 VAC 25% load, without using battery

 

Frequency

45 – 65 Hz auto sensing

 

Power Factor

>0.98 at full load

 

Current Harmonics

< 9% at full load

 

Protection

Fuse

 

Power Cord

6 ft. attached with NEMA 5-15 plug

 

OUTPUT

 

 

 

Output Receptacles

(4) NEMA 5-15R

 

Voltage

 

100/110/115/120 (user selectable) VAC

 

Voltage Regulation

+ 2% of nominal

 

Frequency

60 Hz

 

Waveform/Distortion

Sine wave/ THD < 3% @ full linear load

 

 

 

 

 

Overload

 

100~110% for 120 seconds,

 

 

 

111~150% for 20 seconds,

 

 

 

151% immediately, transfer to bypass within 4 ms

 

Short Circuit Protection

15A Fuse for per 2 output outlets

 

INTERNAL BATTERY PACK

 

Type

 

Sealed Lead Acid, Valve-regulated, Rechargeable

 

Qty x V x Rating

4 x 12 V x 7.2 AH per pack

 

Replacement Battery

BA04009

 

Pack Part #

 

 

 

Back-up time

See Battery Run Time charts

 

Recharge time

4 hours to 90% capacity after full discharge

28

Image 28
Contents Owners Operating Manual Table of Contents Battery InstallationStorage and Transportation Introduction Block Diagram Circuit DescriptionsInstallation FREE-STANDING UPS Installation RACK-MOUNT UPS SetupInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation Display & Controls SET/ALARM Silence BypassFUNCTION/TEST Indicators and Icons Located on the LCD Display Controls FUNCTION/TEST ButtonNormal ON-LINE Mode Battery ModeOperation Operating ModesGreen Mode Bypass ModeTurning the UPS on UPS Setup Configuration How To Place The UPS Into Setup/CONFIGURATION ModeGreen Mode Function BIT Turning the UPS OFFHow to Set the UPS Output Voltage How to Enable or Disable Green ModeConfiguration Mode An Example of How to Set the UPS Output Voltage to 115Vac CommunicationsRS-232 Port PIN #Standard Dry Contact Interface Card Novell style UA88374 Relay Option BoardMaintenance UPS and Battery CareWhen to Replace Batteries Battery Pack ReplacementInternal Battery Pack Replacement Testing NEW Batteries Recycling the Used BatteryFuse Replacement Troubleshooting Troubleshooting GuideTroubleshooting Guide UPSDimensions WeightInternal Battery Pack InputModel Number XG2.2K-1T Battery RUN Times Warranty General Provisions