BYPASS MODE
The UPS will automatically go to BYPASS mode in the event it is overloaded or suffers an internal failure. When in bypass, the UPS will transfer the connected loads directly to utility power. When in bypass mode, BATTERY MODE will not be available. However, the utility power continues to be passively filtered by the UPS. The UPS will sound an audible alarm and switch to BYPASS MODE automatically when:
•The UPS has an overtemperature condition.
•The UPS has an overload condition of 101 to 110% over 120 seconds.
•The UPS has an overload condition of 111 to 150% over 20 seconds.
•The UPS has an overload condition of over 150%.
•The UPS detects a fault in the battery or UPS electronics.
The display shows the UPS in BYPASS MODE. The solid line is connected from the Input to Load. Another solid line is connected from the Input to Battery in charging. The Fan is in low speed; Line and Charger icons are illuminated.
GREEN MODE
When Green Mode is turned on, the XG unit is automatically switched to “GREEN MODE”, once the connected load drops to less than 3% of the UPS rated output. The load will operate directly from utility power, similar to BYPASS MODE. The display indicates the UPS is in BYPASS MODE, with a flash “GREEN MODE BULB”. If the load is increased to over 3% of the UPS output rating, the UPS will switch back to NORMAL
TURNING THE UPS ON
Once installation is complete, the UPS can be powered up. With utility power present, turn on the UPS INPUT BREAKER. The UPS will enter
How to DC Start the UPS
To turn on the UPS without utility power available, press the “BYPASS” button. The UPS will start on battery and supply power to the connected loads until the batteries are depleted. Recharge the batteries immediately after a full battery discharge.
16