Falcon XG2.2K-1T, XG1.5K-1T, XG3K-1T manual Bypass Mode, Green Mode, Turning the UPS on

Page 16

BYPASS MODE

The UPS will automatically go to BYPASS mode in the event it is overloaded or suffers an internal failure. When in bypass, the UPS will transfer the connected loads directly to utility power. When in bypass mode, BATTERY MODE will not be available. However, the utility power continues to be passively filtered by the UPS. The UPS will sound an audible alarm and switch to BYPASS MODE automatically when:

The UPS has an overtemperature condition.

The UPS has an overload condition of 101 to 110% over 120 seconds.

The UPS has an overload condition of 111 to 150% over 20 seconds.

The UPS has an overload condition of over 150%.

The UPS detects a fault in the battery or UPS electronics.

The display shows the UPS in BYPASS MODE. The solid line is connected from the Input to Load. Another solid line is connected from the Input to Battery in charging. The Fan is in low speed; Line and Charger icons are illuminated.

GREEN MODE

When Green Mode is turned on, the XG unit is automatically switched to “GREEN MODE”, once the connected load drops to less than 3% of the UPS rated output. The load will operate directly from utility power, similar to BYPASS MODE. The display indicates the UPS is in BYPASS MODE, with a flash “GREEN MODE BULB”. If the load is increased to over 3% of the UPS output rating, the UPS will switch back to NORMAL ON-LINE operation. All XG models are shipped from the factory with GREEN MODE turned off. To enable “GREEN MODE”, refer to the section on UPS “CONFIGURATION”. See the green mode configuration section for further details and cautions.

TURNING THE UPS ON

Once installation is complete, the UPS can be powered up. With utility power present, turn on the UPS INPUT BREAKER. The UPS will enter Auto-Start State; all of the indicators on the display are illuminated. Ten seconds later, the unit goes to ON-LINE operation.

How to DC Start the UPS

To turn on the UPS without utility power available, press the “BYPASS” button. The UPS will start on battery and supply power to the connected loads until the batteries are depleted. Recharge the batteries immediately after a full battery discharge.

16

Image 16
Contents Owners Operating Manual Table of Contents Battery InstallationStorage and Transportation Introduction Block Diagram Circuit DescriptionsInstallation FREE-STANDING UPS Installation RACK-MOUNT UPS SetupInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation Display & Controls SET/ALARM Silence BypassFUNCTION/TEST Indicators and Icons Located on the LCD Display Controls FUNCTION/TEST ButtonNormal ON-LINE Mode Battery ModeOperation Operating ModesGreen Mode Bypass ModeTurning the UPS on UPS Setup Configuration How To Place The UPS Into Setup/CONFIGURATION ModeGreen Mode Function BIT Turning the UPS OFFHow to Set the UPS Output Voltage How to Enable or Disable Green ModeConfiguration Mode An Example of How to Set the UPS Output Voltage to 115Vac CommunicationsRS-232 Port PIN #Standard Dry Contact Interface Card Novell style UA88374 Relay Option BoardMaintenance UPS and Battery CareWhen to Replace Batteries Battery Pack ReplacementInternal Battery Pack Replacement Testing NEW Batteries Recycling the Used BatteryFuse Replacement Troubleshooting Troubleshooting GuideTroubleshooting Guide UPSDimensions WeightInternal Battery Pack InputModel Number XG2.2K-1T Battery RUN Times Warranty General Provisions