Falcon XG2.2K-1T manual An Example of How to Set the UPS Output Voltage to 115Vac, Communications

Page 19

CAUTION: When the UPS output voltage is set to 100Vac, the maximum amount of load that can be connected to the UPS must be derated (reduced). See the Specifications at the end of this manual for the derating information on your model.

Output Voltage

Function BIT(s)

120Vac

BIT 0 & BIT 1

115Vac

BIT 0 & BIT 1

110Vac

BIT 0 & BIT 1

100Vac

BIT 0 & BIT 1

Status Bit (BIT 7)

BIT 0 Enabled (dot), BIT 1 Enabled (dot) BIT 0 Disabled (no dot, BIT 1 Enabled (dot) BIT 0 Enabled (dot, BIT 1 Disabled (no dot)

BIT 0 Disabled (no dot, BIT 1 Disabled (no dot)

An Example of How to Set the UPS Output Voltage to 115Vac

1.Press the “FUNTION/TEST” and “SET/ALARM SILENCE” buttons at same time and hold them for one second. The unit will emit one alarm beep and then enter the setup CONFIGURATION MODE.

2.Press the “FUNCTION/TEST” button repeatedly and move the dot to function BIT 0.

3.Press the “SET/ALARM SLIENCE” button once or twice to Disable (no dot) Status BIT 7.

4.Press the “FUNCTION/TEST” button repeatedly and move the dot to function BIT 1.

5.Press the “SET/ALARM SLIENCE” button once or twice to Enable (dot) Status BIT 7.

6.Press the “SET/ALARM SLIENCE” and “FUNCTION/TEST” buttons at same time again and hold for one second. The alarm buzzer will sound one short beep to acknowledge the UPS has stored the settings.

7.You must now restart the UPS to affect the new voltage setting.

7.0COMMUNICATIONS

All XG Series UPSs are provided with the following communication ports:

RS-232 port with standard DB-9F serial port connector.

An advanced communications option slot is provided on the rear panel of the UPS. Unless an advanced communications option has been previously purchased and installed, the port will be covered with a small cover plate. This plate will be secured with screws.

CAUTION: NEVER INSTALL OPTION CARDS THAT HAVE NOT BEEN SUPPLIED BY FALCON ELECTRIC AS UPS DAMAGE MAY RESULT.

Advanced communications option cards available from Falcon are:

Internal SNMP/HTTP Agent Board

Standard Dry Contact Interface Board (Novell style)

Dry Contact Interface Board with On-Bypass Signal

Standard Optically-Isolated Contact Interface Board

APC Style Dry Contact Interface Board

19

Image 19
Contents Owners Operating Manual Table of Contents Battery InstallationStorage and Transportation Introduction Circuit Descriptions Block DiagramInstallation FREE-STANDING UPS Installation RACK-MOUNT UPS SetupInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation Display & Controls SET/ALARM Silence BypassFUNCTION/TEST Indicators and Icons Located on the LCD Display FUNCTION/TEST Button ControlsOperating Modes Normal ON-LINE ModeBattery Mode OperationGreen Mode Bypass ModeTurning the UPS on Turning the UPS OFF UPS Setup ConfigurationHow To Place The UPS Into Setup/CONFIGURATION Mode Green Mode Function BITHow to Set the UPS Output Voltage How to Enable or Disable Green ModeConfiguration Mode Communications An Example of How to Set the UPS Output Voltage to 115VacPIN # RS-232 PortUA88374 Relay Option Board Standard Dry Contact Interface Card Novell styleBattery Pack Replacement MaintenanceUPS and Battery Care When to Replace BatteriesInternal Battery Pack Replacement Recycling the Used Battery Testing NEW BatteriesFuse Replacement Troubleshooting Guide TroubleshootingUPS Troubleshooting GuideInput DimensionsWeight Internal Battery PackModel Number XG2.2K-1T Battery RUN Times General Provisions Warranty